Hydrotech Acquires Isaacs
Hydrotech ecommerce supports the continental US only

BOSCH REXROTH
S20-DO-16/3
R911172534

I/O IndraControl S20 Digital:Output

$584.12

BOSCH REXROTH

MATERIAL:  R911172534

SUMMARY:  I/O IndraControl S20 Digital:Output

Quantity in stock: 1

Quantity Details:
  • Hydrotech Stock: 0 can ship May 6, 2024
  • Factory Stock: 1 can ship June 24, 2024
Add to Cart

This module is designed for use within an S20 station. It is used to output digital signals. Actuators with up to three conductors can be connected. The outputs are protected against short circuits and overload.

General data

Type

S20-DO-16/3

Color

Gray

Weight

g

234

Ambient temperature (operation)

-25 °C ... +60 °C

Ambient temperature (storage/transport)

-40 °C ... +85 °C

Permissible relative humidity (operation)

5 % ... 95 % acc. to DIN EN 61131-2

Permissible relative humidity (storage/transport)

5 % ... 95 % acc. to DIN EN 61131-2

Air pressure (operation)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Air pressure (storage/transport)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Protection type

IP20

Protection class

III, IEC 61140, EN 61140, VDE 0140-1

Connection data

Type

S20-DO-16/3

Designation

S20 connector

Connection type

Spring-cage connection with direct plug technology

Conductor cross-section solid/flexible/AWG

0.2 mm² ... 1.5 mm²
0.2 mm² ... 1.5 mm²
24 ... 16

Stripping length

mm

8

Interface local bus

Type

S20-DO-16/3

Connection type

Bus base module

Transmission speed

MBit/s

100

Power supply to logic

Type

S20-DO-16/3

Logic voltage UBus 1)

V DC

5

Maximum current consumption from UBus

mA

120

Maximum power consumption from UBus

mW

600
1) Via bus base module

Power supply to peripherals

Type

S20-DO-16/3

Feed to digital output modules UO

V DC

24

Maximum permitted voltage range 1)

​19.2 V DC ... ​30 V DC

Current consumption from UO 2)

A

8

Typical power consumption from UO 3)

mW

300

Maximum power consumption from UO 4)

W

240

Overvoltage/reverse polarity protection supply voltage

Electronic (35 V, 0.5 s) / parallel diode; with external security 5 A (only for commissioning)

Guarantee 5)

A

≤ 8
1) Including all tolerances, including ripple
2) Secure externally
3) Without actuators
4) From that, 560 mW internal losses
5) Reverse polarity protection up to 5 A

Digital outputs

Type

S20-DO-16/3

Number of digital outputs

16

Connection type

Direct plug-in technology

Connectivity technology

2-, 3-wire technology

Nominal output voltage

24 V DC

Output current per channel

mA

≤ 500

Output current per device 1)

A

≤ 8

Nominal load

Ohmic

48 Ω; for nominal voltage

W

≤ 12

Lamps

for nominal voltage

W

≤ 12

Inductance

1.2 H, 48 Ω; for nominal voltage

VA

≤ 12

Signal delay upon activation

µs

≤ 100

Signal delay upon deactivation 2)

µs

≤ 100

Switching frequency

Max. 10000 per second (for minimum 50 mA load current)
Max. 1 per second (for inductive nominal load)
Max. 16 per second (for lamp nominal load)

Load

≥ 10

Energy consumption

See diagram

Limited inductive cut-off voltage

UDemag = UO - 45 V (UDemag = demagnetization voltage)

Output voltage in deactivated state

V

≤ 1

Output current in deactivated state

μA

≤ 300

Behavior

For overload

Shutdown with automatic restart

For inductive overload

Output can be destroyed

Reverse voltage protection from short pulses

Limited reverse voltage protection up to 0.5 A for 1 s

Overcurrent cutoff

A

> 0.7

Output current upon overvoltage in deactivated state

mA

< 1

Short-circuit protection, overload protection of the outputs

Electronic
1) Secure externally
2) With at least 50 mA load current

Error messages to the higher-level control or computer system

Type

S20-DO-16/3

Error message

Short-circuit/overload of digital outputs

Electrical isolation/insulation of the voltage ranges

Type

S20-DO-16/3

Test distance

Test voltage

5 V supply (logic)/24 V supply (peripherals)

500 V AC, 50 Hz, 1 min.

5 V supply (logic)/function earth

500 V AC, 50 Hz, 1 min.

24 V supply (peripherals)/function earth

500 V AC, 50 Hz, 1 min.

Mechanical tests

Type

S20-DO-16/3

Vibration resistance 1)

g

5

Shock 2)

25 g, 11 ms duration, semi-sinusoidal shock pulse

Continuous shock 3)

g

10
1) Acc. to IEC 60068-2-6
2) Acc. to IEC 60068-2-27
3) Acc. to EN 60068-2-29

Conformity

Type

S20-DO-16/3

Conforms with

Testing of interference immunity acc. to EN 61000-6-2

Discharge of static electricity (ESD)

Criterion B; 6 kV contact discharge; 8 kV air discharge acc. to EN 61000-4-2/IEC 61000-4-2

Electro-magnetic fields

Criterion A; field strength: 10 V/m acc. to EN 61000-4-3/IEC 61000-4-3

Fast transients (burst)

Criterion B; 2 kV acc. to EN 61000-4-4/IEC 61000-4-4

Transient overvoltage (surge)

Criterion B; supply lines DC: ±0.5 kV/±0.5 kV (symmetric/asymmetric) acc. to EN 61000-4-5/IEC 61000-4-5

Line-fed disturbances

Criterion A; test voltage 10 V acc. to EN 61000-4-6/IEC 61000-4-6

Testing of disturbance transmission acc. to EN 61000-6-3

Radio disturbance characteristics

Class B acc. to EN 55022

Approvals

The current approvals can be found at www.boschrexroth.com.

technical illustration-S20-DO-16/3-I/O IndraControl S20 Digital:Output

Dimensions

Type

S20-DO-16/3

A

mm

53.6

B

mm

129.9

C

mm

54

Note on dimensions