BOSCH REXROTH
R-IBILAI4/I-PAC
R911172894
I/O Rexroth Inline Analogue modules
BOSCH REXROTH
MATERIAL: R911172894
SUMMARY: I/O Rexroth Inline Analogue modules
Quantity in stock: 1
Quantity Details:- Hydrotech Stock: 0 can ship June 10, 2024
- Factory Stock: 1 can ship July 29, 2024
This module is designed for use within an Inline station. It is used to acquire analog current signals.
General data
Type |
R-IB IL AI 4/I-PAC | |
Color |
Gray | |
Weight 1) |
g |
66 |
Ambient temperature (operation) |
-25 °C ... +55 °C | |
Ambient temperature (storage/transport) |
-25 °C ... +85 °C | |
Permissible relative humidity (operation) |
10 % ... 95 % acc. to DIN EN 61131-2 | |
Permissible relative humidity (storage/transport) |
10 % ... 95 % acc. to DIN EN 61131-2 | |
Air pressure (operation) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
Air pressure (storage/transport) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
Protection type |
IP20, IEC 60529 | |
Protection class |
III, IEC 61140, EN 61140, VDE 0140-1 |
1) | Including plug |
Connection data
Type |
R-IB IL AI 4/I-PAC | |
Designation |
Inline connection plug | |
Connection type |
Spring-cage connection | |
Conductor cross-section solid/flexible/AWG |
0.2 mm² ... 1.5 mm² 0.2 mm² ... 1.5 mm² 24 ... 16 |
Interface local bus
Type |
R-IB IL AI 4/I-PAC | |
Connection type |
Inline data jumper | |
Transmission speed |
kBit/s |
500 |
Transfer physics |
Copper |
Inline potentials/performance balance
Type |
R-IB IL AI 4/I-PAC | |
Logic voltage UL 1) |
V DC |
7.5 |
Typical current consumption from UL |
mA |
55 |
Peripheral supply voltage UANA |
V DC |
24 |
Typical current consumption from UANA |
mA |
30 |
Typical power consumption total |
W |
0.94 |
1) | Via potential jumpers |
Analog inputs
Type |
R-IB IL AI 4/I-PAC | |
Number of analog inputs 1) |
4 | |
Connectivity technology |
2-wire technology | |
Current input signal |
0 mA ... 20 mA 4 mA ... 20 mA - |
|
Resolution A/D |
bits |
12 |
A/D conversion time |
µs |
≤ 6.5 |
Limit frequency (3 dB) |
Hz |
300 |
Measurement representation |
13 bits (12 bits + sign) - - - - - |
|
Data formats |
IB IL, S7 compatible | |
Process data update 2) |
µs |
250 |
Filtering |
None or averaged over 4, 16 or 32 measured values | |
Overload protection |
Max. ±5.2 V DC, Imax = 50 mA | |
Typical input resistance power input |
Ω |
113 |
Open circiut response |
Regulating toward 0 mA; wire break detection for 4 mA ... 20 Ma |
1) | Differential inputs, current |
2) | All channels |
Programming data
Type |
R-IB IL AI 4/I-PAC | |
ID code (hex) |
7F | |
ID code (dec) |
127 | |
Length code (hex) |
04 | |
Length code (dec) |
04 | |
Process data channel |
bits |
64 |
Input address room |
byte |
8 |
Output address room |
byte |
8 |
Parameter channel (PCP) |
byte |
0 |
Register length (bus) |
bits |
64 |
Fieldbus data telegram
Type |
R-IB IL AI 4/I-PAC | |
Need for parameter data |
byte |
10 |
Need for configuration data |
byte |
5 |
Error messages to the higher-level control or computer system
Type |
R-IB IL AI 4/I-PAC | |
Error message |
Upon failure of the internal peripheral power supply: Peripheral error message to the bus coupler Upon failure of the peripheral power supply: Message in the diagnostic code (in format IB IL) When the measurement range is exceeded or undershot: Message in the diagnostic code (in format IB IL) Upon invalid configuration: Message in the diagnostic code (in format IB IL) |
Electrical isolation/insulation of the voltage ranges
Type |
R-IB IL AI 4/I-PAC | |
Test distance |
Test voltage | |
5 V supply incoming remote bus/7.5 V supply (bus logic) |
500 V AC, 50 Hz, 1 min. | |
5 V supply to further remote bus/7.5 V supply (bus logic) |
500 V AC, 50 Hz, 1 min. | |
7.5 V supply (bus logic), 24 V supply UANA/peripherals |
500 V AC, 50 Hz, 1 min. | |
7.5 V supply (bus logic), 24 V supply UANA/function earth |
500 V AC, 50 Hz, 1 min. | |
Peripherals/function earth |
500 V AC, 50 Hz, 1 min. |
Conformity
Type |
R-IB IL AI 4/I-PAC | ||
Conforms with |
|||
Testing of interference immunity acc. to EN 61000-6-2 |
Discharge of static electricity (ESD) |
Criterion B; 6 kV contact discharge; 8 kV air discharge acc. to EN 61000-4-2/IEC 61000-4-2 | |
Electro-magnetic fields |
Criterion A; field strength: 10 V/m acc. to EN 61000-4-3/IEC 61000-4-3 | ||
Fast transients (burst) |
Criterion B; 2 kV acc. to EN 61000-4-4/IEC 61000-4-4 | ||
Transient overvoltage (surge) |
Criterion B; supply lines DC: ±1 kV/±1 kV (symmetric/asymmetric); ±1 kV on shielded I/O lines acc. to EN 61000-4-5/IEC 61000-4-5 | ||
Line-fed disturbances |
Criterion A; test voltage 10 V acc. to EN 61000-4-6/IEC 61000-4-6 | ||
Testing of disturbance transmission acc. to EN 61000-6-3 |
Radio disturbance characteristics |
Class A acc. to EN 55022 |
Approvals |
The current approvals can be found at www.boschrexroth.com. |
Dimensions
Type |
R-IB IL AI 4/I-PAC | |
A |
mm |
12.2 |
B |
mm |
120 |
C |
mm |
71.5 |
Note on dimensions |
The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715). |