BOSCH REXROTH
S20-DI-16/1-HS
R911173344
All Other Products
I/O IndraControl S20 Digital:Input
BOSCH REXROTH
MATERIAL: R911173344
SUMMARY: I/O IndraControl S20 Digital:Input
Quantity in stock: 2
Quantity Details:- Hydrotech Stock: 0 can ship April 30, 2024
- Factory Stock: 2 can ship June 18, 2024
This module is designed for use within an S20 station. It is used to acquire digital signals. The internal update time of < 5 μs makes it possible to applicatively implement a counting function using the module. The input frequency for counting can be a maximum 100 kHz.
General data
Type |
S20-DI-16/1 HS | |
Color |
Gray | |
Weight 1) |
g |
133 |
Ambient temperature (operation) |
-25 °C ... +60 °C | |
Ambient temperature (storage/transport) |
-40 °C ... +85 °C | |
Permissible relative humidity (operation) |
5 % ... 95 %, no dewing | |
Permissible relative humidity (storage/transport) |
5 % ... 95 %, no dewing | |
Air pressure (operation) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
Air pressure (storage/transport) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
Protection type |
IP20 | |
Protection class |
III, IEC 61140, EN 61140, VDE 0140-1 | |
Installation position |
Any (no temperature derating) |
1) | Including plug and bus base module |
Connection data
Type |
S20-DI-16/1 HS | |
Designation |
S20 connector | |
Connection type |
Push-in technology | |
Conductor cross-section solid/flexible/AWG |
0.2 mm² ... 1.5 mm² 0.2 mm² ... 1.5 mm² 24 ... 16 |
|
Stripping length |
mm |
8 |
Interface local bus
Type |
S20-DI-16/1 HS | |
Connection type |
Bus base module | |
Transmission speed |
MBit/s |
100 |
Power supply to logic
Type |
S20-DI-16/1 HS | |
Logic voltage UBus 1) |
V DC |
5 |
Maximum current consumption from UBus |
mA |
120 |
Maximum power consumption from UBus |
mW |
600 |
1) | Via bus base module |
Power supply to peripherals
Type |
S20-DI-16/1 HS | |
Feed to digital input modules UI |
V DC |
24 |
Maximum permitted voltage range 1) |
19.2 V DC ... 30 V DC | |
Current consumption from UI |
mA |
20 |
Typical power consumption from UI |
mW |
380 |
Maximum power consumption from UI |
mW |
480 |
Overvoltage/reverse polarity protection supply voltage |
Electronic (35 V, 0.5 s) / parallel diode; with external security 5 A (only for commissioning) | |
Guarantee 2) |
A |
≤ 8 |
1) | Including all tolerances, including ripple |
2) | Reverse polarity protection up to 5 A |
Digital inputs
Type |
S20-DI-16/1 HS | |
Number of digital inputs |
16 | |
Connection type |
Push-in technology | |
Connectivity technology |
1-wire technology | |
Description of the input |
Acc. to EN 61131-2 type 1 and type 3 | |
Nominal input voltage |
V DC |
24 |
Input voltage range |
-3 V DC ... 30 V DC | |
Nominal input current |
mA |
2.3 |
Current profile |
Linear up to nominal current, then constant around 2.3 mA | |
Input voltage range "0" signal |
-3 V DC ... 8.4 V DC | |
Input voltage range "1" signal |
9.4 V ... 30 V DC | |
Input filter time |
< 5 μs | |
Process data update 1) |
µs |
< 5 |
Reverse polarity protection |
Parallel diode (30 V, 5 s) |
1) | Bus synchronous |
PROFIBUS telegram data
Type |
S20-DI-16/1 HS | |
Need for parameter data |
byte |
3 |
Need for configuration data |
byte |
6 |
Error messages to the higher-level control or computer system
Type |
S20-DI-16/1 HS | |
Error message |
Failure in peripheral supply |
Electrical isolation/insulation of the voltage ranges
Type |
S20-DI-16/1 HS | |
Test distance |
Test voltage | |
5 V supply (logic)/24 V supply (peripherals) |
500 V AC, 50 Hz, 1 min. | |
5 V supply (logic)/function earth |
500 V AC, 50 Hz, 1 min. | |
24 V supply (peripherals)/function earth |
500 V AC, 50 Hz, 1 min. |
Mechanical tests
Type |
S20-DI-16/1 HS | |
Vibration resistance 1) |
g |
5 |
Shock 2) |
g |
30 |
Continuous shock 2) |
g |
10 |
1) | Acc. to EN 60068-2-6/IEC 60068-2-6 |
2) | Acc. to EN 60068-2-27/IEC 60068-2-27 |
Conformity
Type |
S20-DI-16/1 HS | ||
Conforms with |
|||
Testing of interference immunity acc. to EN 61000-6-2 |
Discharge of static electricity (ESD) |
Criterion B; 6 kV contact discharge; 8 kV air discharge acc. to EN 61000-4-2/IEC 61000-4-2 | |
Electro-magnetic fields |
Criterion A; field strength: 10 V/m acc. to EN 61000-4-3/IEC 61000-4-3 | ||
Fast transients (burst) |
Criterion B; 2 kV acc. to EN 61000-4-4/IEC 61000-4-4 | ||
Transient overvoltage (surge) |
Criterion B; supply lines DC: ±0.5 kV/±0.5 kV (symmetric/asymmetric) acc. to EN 61000-4-5/IEC 61000-4-5 | ||
Line-fed disturbances |
Criterion A; test voltage 10 V acc. to EN 61000-4-6/IEC 61000-4-6 | ||
Testing of disturbance transmission acc. to EN 61000-6-3 |
Radio disturbance characteristics |
Class B acc. to EN 55022 |
Approvals |
The current approvals can be found at www.boschrexroth.com. |
Dimensions
Type |
S20-DI-16/1 HS | |
A |
mm |
35 |
B |
mm |
126.1 |
C |
mm |
54 |
Note on dimensions |