Hydrotech Acquires Isaacs
Hydrotech ecommerce supports the continental US only

BOSCH REXROTH
R-IBILAO2/UI-PAC
R911173634
All Other Products

I/O Rexroth Inline Analogue modules

$494.56

BOSCH REXROTH

MATERIAL:  R911173634

SUMMARY:  I/O Rexroth Inline Analogue modules

Quantity in stock: 1

Quantity Details:
  • Hydrotech Stock: 0 can ship May 8, 2024
  • Factory Stock: 1 can ship June 26, 2024
Add to Cart

This module is designed for use within an Inline station. It is used to output analog current or voltage signals.

General data

Type

R-IB IL AO 2/UI-PAC

Weight 1)

g

66

Ambient temperature (operation)

-25 °C ... +55 °C

Ambient temperature (storage/transport)

-25 °C ... +85 °C

Permissible relative humidity (operation)

10 % ... 95 % acc. to DIN EN 61131-2

Permissible relative humidity (storage/transport)

10 % ... 95 % acc. to DIN EN 61131-2

Air pressure (operation)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Air pressure (storage/transport)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Protection type

IP20

Protection class

III, IEC 61140, EN 61140, VDE 0140-1
1) Including plug

Connection data

Type

R-IB IL AO 2/UI-PAC

Designation

Inline connection plug

Connection type

Spring-cage connection

Conductor cross-section solid/flexible/AWG

0.08 mm² ... 1.5 mm²
0.08 mm² ... 1.5 mm²
28 ... 16

Interface local bus

Type

R-IB IL AO 2/UI-PAC

Connection type

Inline data jumper

Number

2

Transmission speed

kBit/s

500

Transfer physics

Copper

Inline potentials/performance balance

Type

R-IB IL AO 2/UI-PAC

Logic voltage UL 1)

V DC

7.5

Typical current consumption from UL

mA

55

Maximum current consumption from UL

mA

65

Peripheral supply voltage UANA

V DC

24

Typical current consumption from UANA

No load

mA

24

Voltage nominal load UOUT1/2 = 10 V, RL = 1 kΩ

mA

38

Power nominal load IOUT1/2 = 20 mA, RL = 0 Ω

mA

65

Maximum current consumption from UANA

No load

mA

30

Voltage nominal load UOUT1/2 = 10 V, RL = 1 kΩ

mA

45

Power nominal load IOUT1/2 = 20 mA, RL = 0 Ω

mA

75

Typical power consumption

Voltage nominal load UOUT1/2 = 10 V, RL = 1 kΩ

W

1.32

Power nominal load IOUT1/2 = 20 mA, RL = 0 Ω

W

1.97
1) Via potential jumpers

Analog outputs

Type

R-IB IL AO 2/UI-PAC

Number of analog outputs

2

Connectivity technology

2-wire technology (shielded, twisted pair)

Resolution D/A

bits

12

D/A conversion time

µs

10

Output value representation

12 bits (11 bits + sign)

Data formats

IB IL

Process data update

Bus synchronous

Permissible cable length 1)

m

≤ 250

Short-circuit protection, overload protection

Electronic

Transient protection

Suppressor diode
1) The information relates to nominal operation in compliance with the installation regulations and refer to the following reference line type: Shielded power plant line: LiYCY; 2 x 2 x 0.5 mm2; VDE0812

Analog outputs, current

Type

R-IB IL AO 2/UI-PAC

Current output signal

0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA

Output load current output

Ω

≤ 450

Precision

Typ. 0.1 % (of the output range end value)

Analog outputs, voltage

Type

R-IB IL AO 2/UI-PAC

Voltage output signal

0 V ... 10 V
-10 V ... 10 V

Output load voltage output

> 1

Precision

Typ. 0.1 % (of the output range end value)

Programming data

Type

R-IB IL AO 2/UI-PAC

ID code (hex)

5B

ID code (dec)

91

Length code (hex)

04

Length code (dec)

04

Process data channel

bits

64

Input address room

byte

8

Output address room

byte

8

Parameter channel (PCP)

byte

0

Register length (bus)

bits

64

Fieldbus data telegram

Type

R-IB IL AO 2/UI-PAC

Need for parameter data

byte

10

Need for configuration data

byte

5

Error messages to the higher-level control or computer system

Type

R-IB IL AO 2/UI-PAC

Error message

Upon failure of the internal peripheral power supply: Peripheral error message to the bus coupler
Upon failure of the peripheral power supply: Message in the diagnostic code (in format IB IL)
Upon short-circuit/overload of outputs: Message in the diagnostic code (in format IB IL)
Upon invalid configuration: Message in the diagnostic code (in format IB IL)

Electrical isolation/insulation of the voltage ranges

Type

R-IB IL AO 2/UI-PAC

Test distance

Test voltage

7.5 V supply (bus logic), 24 V supply UANA/peripherals

500 V AC, 50 Hz, 1 min.

7.5 V supply (bus logic), 24 V supply UANA/function earth

500 V AC, 50 Hz, 1 min.

24 V supply (peripherals)/function earth

500 V AC, 50 Hz, 1 min.

Conformity

Type

R-IB IL AO 2/UI-PAC

Conforms with

Testing of interference immunity acc. to EN 61000-6-2

Discharge of static electricity (ESD)

Criterion B; 6 kV contact discharge; 8 kV air discharge acc. to EN 61000-4-2/IEC 61000-4-2

Electro-magnetic fields

Criterion A; field strength: 10 V/m acc. to EN 61000-4-3/IEC 61000-4-3

Fast transients (burst)

Criterion B; 2 kV acc. to EN 61000-4-4/IEC 61000-4-4

Transient overvoltage (surge)

Criterion B; supply lines DC: ±0.5 kV/±0.5 kV (symmetric/asymmetric); ±1 kV on shielded I/O lines acc. to EN 61000-4-5/IEC 61000-4-5

Line-fed disturbances

Criterion A; test voltage 10 V acc. to EN 61000-4-6/IEC 61000-4-6

Testing of disturbance transmission acc. to EN 61000-6-3

Radio disturbance characteristics

Class A acc. to EN 55022

Approvals

The current approvals can be found at www.boschrexroth.com.

technical illustration-R-IBILAO2/UI-PAC-I/O Rexroth Inline Analogue modules

Dimensions

Type

R-IB IL AO 2/UI-PAC

A

mm

12.2

B

mm

136.8

C

mm

71.5

Note on dimensions