BOSCH REXROTH
S20-DO-64/1
R911173742
All Other Products
I/O IndraControl S20 Digital:Output
BOSCH REXROTH
MATERIAL: R911173742
SUMMARY: I/O IndraControl S20 Digital:Output
Quantity in stock: 1
Quantity Details:- Hydrotech Stock: 0 can ship April 29, 2024
- Factory Stock: 1 can ship June 17, 2024
This module is designed for use within an S20 station. It is used to output digital signals. The outputs are protected against short circuits and overload.
General data
Type |
S20-DO-64/1 | |
Color |
Gray | |
Weight 1) |
g |
260 |
Ambient temperature (operation) |
-25 °C ... +60 °C | |
Ambient temperature (storage/transport) |
-40 °C ... +85 °C | |
Permissible relative humidity (operation) |
5 % ... 95 %, no dewing | |
Permissible relative humidity (storage/transport) |
5 % ... 95 %, no dewing | |
Air pressure (operation) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
Air pressure (storage/transport) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
Protection type |
IP20 | |
Protection class |
III, IEC 61140, EN 61140, VDE 0140-1 | |
Installation position |
Any (no temperature derating) |
1) | Including plug and bus base module |
Connection data
Type |
S20-DO-64/1 | |
Designation |
S20 connector | |
Connection type |
Push-in technology | |
Conductor cross-section solid/flexible/AWG |
0.2 mm² ... 1.5 mm² 0.2 mm² ... 1.5 mm² 24 ... 16 |
|
Stripping length |
mm |
8 |
Interface local bus
Type |
S20-DO-64/1 | |
Connection type |
Bus base module | |
Transmission speed |
MBit/s |
100 |
Power supply to logic
Type |
S20-DO-64/1 | |
Logic voltage UBus 1) |
V DC |
5 |
Maximum current consumption from UBus |
mA |
120 |
Maximum power consumption from UBus |
mW |
600 |
1) | Via bus base module |
Power supply to peripherals
Type |
S20-DO-64/1 | |
Feed to digital output modules UO |
V DC |
24 |
Maximum permitted voltage range 1) |
19.2 V DC ... 30 V DC | |
Current consumption from UO 2) |
A |
≤ 16 |
Typical power consumption from UO 3) |
W |
1.2 |
Maximum power consumption from UO 4) |
W |
480 |
Overvoltage/reverse polarity protection supply voltage |
Electronic (35 V, 0.5 s) / parallel diode; with external security 5 A (only for commissioning) | |
Guarantee 5) |
A |
≤ 16 |
1) | Including all tolerances, including ripple |
2) | For parallel power supply, secure externally |
3) | Without actuators |
4) | Of which 1.8 W internal losses |
5) | Reverse polarity protection up to 5 A |
Digital outputs
Type |
S20-DO-64/1 | |||
Number of digital outputs |
64 | |||
Connection type |
Push-in technology | |||
Connectivity technology |
1-wire | |||
Nominal output voltage |
24 V DC | |||
Output current per channel |
mA |
≤ 500 | ||
Output current per device 1) |
A |
≤ 16 | ||
Nominal load |
Ohmic |
48 Ω; for nominal voltage |
W |
≤ 12 |
Lamps |
for nominal voltage |
W |
≤ 12 | |
Inductance |
1.2 H, 48 Ω; for nominal voltage |
VA |
≤ 12 | |
Signal delay upon activation |
µs |
≤ 100 | ||
Signal delay upon deactivation |
µs |
≤ 100 | ||
Switching frequency |
Max. 10000 per second (for ohmic nominal load) Max. 1 per second (for inductive nominal load) Max. 16 per second (for lamp nominal load) |
|||
Load |
kΩ |
≥ 10 | ||
Energy consumption |
See diagram | |||
Limited inductive cut-off voltage |
-25.8 V ... -15 V | |||
Output voltage in deactivated state |
V |
≤ 1 | ||
Output current in deactivated state |
μA |
≤ 300 | ||
Behavior |
For overload |
Shutdown with automatic restart | ||
For inductive overload |
Output can be destroyed | |||
Reverse voltage protection from short pulses |
Limited reverse voltage protection up to 0.5 A for 1 s | |||
Overcurrent cutoff |
A |
> 0.7 | ||
Output current upon overvoltage in deactivated state |
mA |
< 1 | ||
Short-circuit protection, overload protection of the outputs |
Electronic |
1) | Secure externally |
PROFIBUS telegram data
Type |
S20-DO-64/1 | |
Need for parameter data |
byte |
1 |
Need for configuration data |
byte |
6 |
Error messages to the higher-level control or computer system
Type |
S20-DO-64/1 | |
Error message |
Short-circuit/overload of digital outputs |
Electrical isolation/insulation of the voltage ranges
Type |
S20-DO-64/1 | |
Test distance |
Test voltage | |
5 V supply (logic)/24 V supply (peripherals) |
500 V AC, 50 Hz, 1 min. | |
5 V supply (logic)/function earth |
500 V AC, 50 Hz, 1 min. | |
24 V supply (peripherals)/function earth |
500 V AC, 50 Hz, 1 min. |
Mechanical tests
Type |
S20-DO-64/1 | |
Vibration resistance 1) |
g |
5 |
Shock 2) |
g |
30 |
Continuous shock 2) |
g |
10 |
1) | Acc. to EN 60068-2-6/IEC 60068-2-6 |
2) | Acc. to EN 60068-2-27/IEC 60068-2-27 |
Conformity
Type |
S20-DO-64/1 | ||
Conforms with |
|||
Testing of interference immunity acc. to EN 61000-6-2 |
Discharge of static electricity (ESD) |
Criterion B; 6 kV contact discharge; 8 kV air discharge acc. to EN 61000-4-2/IEC 61000-4-2 | |
Electro-magnetic fields |
Criterion A; field strength: 10 V/m acc. to EN 61000-4-3/IEC 61000-4-3 | ||
Fast transients (burst) |
Criterion B; 2 kV acc. to EN 61000-4-4/IEC 61000-4-4 | ||
Transient overvoltage (surge) |
Criterion B; supply lines DC: ±0.5 kV/±0.5 kV (symmetric/asymmetric) acc. to EN 61000-4-5/IEC 61000-4-5 | ||
Line-fed disturbances |
Criterion A; test voltage 10 V acc. to EN 61000-4-6/IEC 61000-4-6 | ||
Testing of disturbance transmission acc. to EN 61000-6-3 |
Radio disturbance characteristics |
Class B acc. to EN 55022 |
Approvals |
The current approvals can be found at www.boschrexroth.com. |
Dimensions
Type |
S20-DO-64/1 | |
A |
mm |
53.6 |
B |
mm |
129.9 |
C |
mm |
54 |
Note on dimensions |
The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715). |