BOSCH REXROTH
R-IBILAI8/SF-PAC
R911308493
I/O Rexroth Inline Analogue modules
BOSCH REXROTH
MATERIAL: R911308493
SUMMARY: I/O Rexroth Inline Analogue modules
Quantity in stock: 2
Quantity Details:- Hydrotech Stock: 0 can ship April 26, 2024
- Factory Stock: 2 can ship June 14, 2024
This module is designed for use within an Inline station. It is used to acquire analog voltage or current signals.
General data
Type |
R-IB IL AI 8/SF-PAC | |
Weight 1) |
g |
213 |
Operating mode |
Process data mode with 2 words | |
Sensor connection type |
2-wire technology | |
Ambient temperature (operation) |
-25 °C ... +55 °C | |
Ambient temperature (storage/transport) |
-25 °C ... +85 °C | |
Permissible relative humidity (operation) |
10 % ... 95 % acc. to DIN EN 61131-2 | |
Permissible relative humidity (storage/transport) |
10 % ... 95 % acc. to DIN EN 61131-2 | |
Air pressure (operation) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
Air pressure (storage/transport) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
Protection type |
IP20, IEC 60529 | |
Protection class |
III, VDE 0106, IEC 60536 |
1) | Including plug |
Connection data
Type |
R-IB IL AI 8/SF-PAC | |
Designation |
Inline connection plug | |
Connection type |
Tension spring modules | |
Conductor cross-section solid/flexible/AWG |
0.2 mm² ... 1.5 mm² 0.2 mm² ... 1.5 mm² 24 ... 16 |
Interface local bus
Type |
R-IB IL AI 8/SF-PAC | |
Connection type |
Data ranking | |
Transmission speed |
kBit/s |
500 |
Inline potentials/performance balance
Type |
R-IB IL AI 8/SF-PAC | |
Logic voltage UL |
V DC |
7.5 |
Typical current consumption from UL |
mA |
48 |
Maximum current consumption from UL |
mA |
55 |
Peripheral supply voltage UANA |
V DC |
24 |
Typical current consumption from UANA |
A |
30 |
Maximum current consumption from UANA |
A |
35 |
Typical power consumption total |
mW |
1500 |
Supply of module electronics and peripherals via bus coupler/power feed module
Type |
R-IB IL AI 8/SF-PAC | |
Connectivity technology |
Potential jumpers |
Analog inputs
Type |
R-IB IL AI 8/SF-PAC | ||
Number of analog inputs 1) |
8 | ||
A/D conversion time |
µs |
≤ 10 | |
Measurement representation |
16 bits (15 bits + sign) 13 bits (12 bits + sign) 16 bits (15 bits + sign) 16 bits (15 bits + sign) 16 bits - |
||
Data formats |
IB IL, IB ST, IB RT, standardized representation, PIO | ||
Average |
None or averaged over 4, 16 or 32 measured valuesdefault setting: 16 measured values | ||
Process data update |
Bus synchronous | ||
Firmware runtime depending on the command |
0x00hex |
µs |
< 800 |
5x00hex |
µs |
< 850 | |
7000hex/7100hex |
µs |
< 1500 | |
7400hex/7500hex/7600hex/7700hex |
µs |
< 1300 | |
Overvoltage/overcurrent protection |
Maximum 100 % overload |
1) | Analog single-ended inputs |
Analog input levels
Type |
R-IB IL AI 8/SF-PAC | |
Voltage inputs |
||
Input resistance |
kΩ |
≥ 240 |
Characteristics of the input filter (input level) |
1st order | |
Cut-off frequency (–3 dB) of the input filter |
kHz |
3.5 |
Behavior upon sensor interruption |
Goes to 0 V | |
Maximum permissible voltage between analog voltage inputs and analog reference potential or between two voltage inputs |
V |
50 |
Current inputs |
||
Input resistance 1) |
Ω |
25 |
Cut-off frequency (–3 dB) of the input filter |
kHz |
3.5 |
Behavior upon sensor interruption |
Regulating toward 0 mA or 4 mA | |
Maximum permissible voltage between analog current inputs and analog reference potential or between two power inputs 2) |
V |
± 2.5 |
Maximum permissible current in each input |
mA |
± 100 |
1) | Measuring resistance |
2) | Equal to 100 mA due to the measuring resistances |
Electrical isolation/insulation of the voltage ranges
Type |
R-IB IL AI 8/SF-PAC | |
Common potentials |
||
24 V main voltage UM, 24 V segment voltage US and GND are on the same potential. FE represents a separate potential area. |
||
Separate potentials in the system of bus coupler/feed module and I/O module |
||
Test distance |
Test voltage | |
5 V supply incoming remote bus/7.5 V supply (bus logic) |
500 V AC, 50 Hz, 1 min. | |
5 V supply to further remote bus/7.5 V supply (bus logic) |
500 V AC, 50 Hz, 1 min. | |
7.5 V supply (bus logic), 24 V supply UANA/peripherals |
500 V AC, 50 Hz, 1 min. | |
7.5 V supply (bus logic), 24 V supply UANA/function earth |
500 V AC, 50 Hz, 1 min. | |
Peripherals/function earth |
500 V AC, 50 Hz, 1 min. |
Error messages to the higher-level control or computer system
Type |
R-IB IL AI 8/SF-PAC | |
Error message |
Failure of the voltage supply UANA Upon peripheral/user error: Error message about process data input words |
Approvals |
The current approvals can be found at www.boschrexroth.com. |
Dimensions
Type |
R-IB IL AI 8/SF-PAC | |
A |
mm |
48.8 |
B |
mm |
136.8 |
C |
mm |
72 |
Note on dimensions |
The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715). |