You are using an outdated browser. For a faster, safer browsing experience, upgrade for free today.

BOSCH REXROTH
R911173743


$1,085.08 USD
  • BOSCH REXROTH
  • Material:R911173743
  • Model:S20-AIAO-2

Quantity in stock: 0

Note: Sales tax, and shipping will be calculated at checkout.
***Disclaimer: The following summary contains information gathered from various sources such as product descriptions, technical specifications and catalogs. While efforts have been made to provide accurate details, inaccuracies may occur. It is advised to verify all information by contacting Bosch Rexroth directly.***
The Bosch Rexroth S20-AIAO-2 (R911173743) is a sophisticated analog input and output module designed to integrate seamlessly into an S IO cabinet station. This compact and modular unit is tailored for top hat rail mounting and offers a space-saving solution for various control applications. The model boasts an innovative assembly and installation concept that simplifies the setup process, making it an efficient choice for users seeking a streamlined approach to system configuration. Equipped with multiple channels, the S20-AIAO-2 module is capable of handling a variety of voltage ranges, including ±10V, 0-10V, ±5V, and 0-5V. These voltage signals can be individually configured to meet the specific needs of each application. The versatility of this unit allows it to accommodate different types of analog signals, making it suitable for a broad range of uses where precise signal processing is critical. With its compact design and state-of-the-art technology, the Bosch Rexroth S20-AIAO-2 module stands out as an essential component for users who require reliable and accurate analog signal acquisition and output within their control systems. Its robust construction ensures durability and consistent performance in demanding environments.


S20 I/O cabinet

Analog input and output module, 2 inputs, 2 outputs, power/voltage signals

Unpacked Weight: 0.19 kg

This module is designed for use within an S20 station. It is used for the acquisition and output of analog voltage and current signals.

Innovative assembly and installation concept
Individually combinable modules
Space-saving I/O technology for top hat rail mounting
Compact, modular and simple
Type code extensionS20-AIAO-2
Productgroup ID4,6
ctrlX configuratorhttps://www.boschrexroth.com/ctrlx-configurator/
Number of channels2
EPLANhttps://ecad-configuration.boschrexroth.com/?rootpartnr=BOS.S20-AIAO-2**&downloads=true
Weight0.19

General data

Type

S20-AIAO-2

Color

Gray

Weight 1)

g

200

Ambient temperature (operation)

-25 °C ... +60 °C

Ambient temperature (storage/transport)

-40 °C ... +85 °C

Permissible relative humidity (operation)

5 % ... 95 %, no dewing

Permissible relative humidity (storage/transport)

5 % ... 95 %, no dewing

Air pressure (operation)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Air pressure (storage/transport)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Protection type

IP20

Protection class

III, IEC 61140, EN 61140, VDE 0140-1

Installation position

Any (no temperature derating)
1) Including plug and bus base module

Connection data

Type

S20-AIAO-2

Designation

S20 connector

Connection type

Push-in technology

Conductor cross-section solid/flexible/AWG

0.2 mm² ... 1.5 mm²
0.2 mm² ... 1.5 mm²
24 ... 16

Stripping length

mm

8

Interface local bus

Type

S20-AIAO-2

Connection type

Bus base module

Transmission speed

MBit/s

100

Power supply to logic

Type

S20-AIAO-2

Logic voltage UBus 1)

V DC

5

Typical current consumption from UBus

mA

120

Maximum current consumption from UBus

mA

150

Typical power consumption from UBus

W

0.6

Maximum power consumption from UBus

W

0.75
1) Via bus base module

Power supply to peripherals

Type

S20-AIAO-2

Feed to analog modules UA

V DC

24

Maximum permitted voltage range 1)

​19.2 V DC ... ​30 V DC

Typical current consumption from UA

mA

40

Maximum current consumption from UA

mA

80

Typical power consumption from UA

W

0.96

Maximum power consumption from UA

W

1.92

Overvoltage protection

Electronic (35 V, 0.5 s)

Reverse polarity protection

Reverse polarity protection diode

Transient protection

Suppressor diode
1) Including all tolerances, including ripple

Power consumption of the entire module

Type

S20-AIAO-2

Typical power consumption 1)

W

1.56

Maximum power consumption 1)

W

2.67
1) To UBus and UA

Analog inputs

Type

S20-AIAO-2

Number of analog inputs 1)

2

Connection type

Push-in technology

Connectivity technology

2-wire technology (shielded)

Current input signal

0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA

Voltage input signal

0 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V

Resolution A/D

bits

16

A/D conversion time

µs

2

Limit frequency (3 dB)

30 Hz, 12 kHz

Measurement representation

16 bits (15 bits + sign)
-
-
-
-
-

Data formats

IB IL, standardized representation

Process data update

µs

150

Input filter

30 Hz, 12 kHz and averaging (configurable)

Precision

0.1% (of measurement range end value with active averaging and 30 Hz filter)

Transient protection of the inputs

Suppressor diode

Typical input resistance power input

Ω

104

Typical input resistance voltage input

268

Open circiut response

Regulating toward 0 V, 0 mA; wire break detection for 4 mA ... 20 Ma

Common-mode voltage range signal ‒ ground

-50 V DC ... 50 V DC

Overload protection for the power inputs

No; max. ±5.2 V DC, Imax = 50 mA

Maximum overload protection of the voltage inputs

V DC

± 30
1) Differential inputs, voltage or current individually selectable

Analog outputs

Type

S20-AIAO-2

Number of analog outputs

2

Connection type

Push-in technology

Connectivity technology

2-wire (shielded, twisted pair)

Current output signal

0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA

Voltage output signal

0 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V

Resolution D/A

bits

16

Output value representation

16 bits (15 bits + sign)

Data formats

IB IL, standardized representation

Process data update

µs

150

Load/output load current output

Ω

≤ 500

Load/output load voltage output

> 2

Precision

Typ. 0.1 % (of the output range end value)

Short-circuit protection, overload protection

Electronic

Transient protection

Suppressor diode

Configuration and parameter data in a PROFIBUS system

Type

S20-AIAO-2

Need for parameter data

byte

11

Need for configuration data

byte

7

Electrical isolation/insulation of the voltage ranges

Type

S20-AIAO-2

Test distance

Test voltage

5 V supply (logic)/24 V supply (peripherals)

500 V AC, 50 Hz, 1 min.

5 V supply (logic)/analog inputs and outputs

500 V AC, 50 Hz, 1 min.

5 V supply (logic)/function earth

500 V AC, 50 Hz, 1 min.

24 V supply (peripherals)/analog inputs and outputs

500 V AC, 50 Hz, 1 min.

24 V supply (peripherals)/function earth

500 V AC, 50 Hz, 1 min.

Analog inputs and outputs/function earth

500 V AC, 50 Hz, 1 min.

Mechanical tests

Type

S20-AIAO-2

Vibration resistance 1)

g

5

Shock 2)

g

30

Continuous shock 2)

g

10
1) Acc. to EN 60068-2-6/IEC 60068-2-6
2) Acc. to EN 60068-2-27/IEC 60068-2-27

Conformity

Type

S20-AIAO-2

Conforms with

Testing of interference immunity acc. to EN 61000-6-2

Discharge of static electricity (ESD)

Criterion B; 6 kV contact discharge; 8 kV air discharge acc. to EN 61000-4-2/IEC 61000-4-2

Electro-magnetic fields

Criterion A; field strength: 10 V/m acc. to EN 61000-4-3/IEC 61000-4-3

Fast transients (burst)

Criterion B; 2 kV acc. to EN 61000-4-4/IEC 61000-4-4

Transient overvoltage (surge)

Criterion B; supply lines DC: ±0.5 kV/±0.5 kV (symmetric/asymmetric); ±1 kV on shielded I/O lines acc. to EN 61000-4-5/IEC 61000-4-5

Line-fed disturbances

Criterion A; test voltage 10 V acc. to EN 61000-4-6/IEC 61000-4-6

Testing of disturbance transmission acc. to EN 61000-6-3

Radio disturbance characteristics

Class B acc. to EN 55022

Approvals

The current approvals can be found at www.boschrexroth.com.

technical illustration-R911173743-S20 I/O cabinet

Dimensions

Type

S20-AIAO-2

A

mm

35

B

mm

126.1

C

mm

54

Note on dimensions

The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715).