BOSCH REXROTH
R911173344
$931.35 USD
- BOSCH REXROTH
- Material:R911173344
- Model:S20-DI-16/1-HS
Quantity in stock: 0
The Bosch Rexroth S20-DI-16/1-HS (R911173344) is a high-functioning input module designed for digital signal acquisition within an S station environment. This module stands out with its ability to implement counting functions applicatively due to an internal update time of less than 1 ms, and it can handle input frequencies up to 100 kHz. The S20-DI-16/1-HS is equipped with 16 digital inputs that comply with EN 61131-2 type 1 and type 3, operating at 24 VDC with a current draw of 5 mA. This module's robust design ensures durability and reliability in various applications. Its forced ventilated axial fan contributes to stable operation under varying conditions. The compact and modular nature of the device allows for space-saving installation on top hat rails, making it an ideal choice for control cabinets or field installations. The setup process is simplified by innovative assembly and installation concepts, providing ease of handling and quick deployment. With open communication standards, the S20-DI-16/1-HS ensures seamless integration into existing systems for maximum availability. Diagnostic and status indicators on the device facilitate efficient monitoring and troubleshooting. Additionally, users can customize filter times in three stages—less than 3 ms, 3 ms, or 10 ms—to match specific application requirements. The electronic device nameplate offers vital information at a glance, while the connection of sensors and actuators using two-wire technology streamlines the wiring process. With these features combined, the Bosch Rexroth S20-DI-16/1-HS presents itself as a versatile solution for digital input collection in automated systems.
Cabinet I/O S20
The modular, compact device design of the I/O systems from Rexroth provides you with maximum flexibility for cost-effective implementation of your custom machine concepts. The I/O modules have a robust design and mechanics, Forced ventilated - Axial fan 230Vre easy to handle, have a fast reaction time and are quick to install – both in the control cabinet as well as in the field. Open communication standards allow you to perfectly integrate the I/O modules with maximum availability.
Unpacked Weight: 0.180 kg
This module is designed for use within an S20 station. It is used to acquire digital signals. The internal update time of < 5 μs makes it possible to applicatively implement a counting function using the module. The input frequency for counting can be a maximum 100 kHz.
| Individually combinable modules |
| Innovative assembly and installation concept |
| Compact, modular and simple |
| Space-saving I/O technology for top hat rail mounting |
| 2D CAD | Download 2D CAD |
| 3D CAD | Download 3D CAD |
| Type code extension | S20-DI-16/1-HS |
| Productgroup ID | 4,6 |
| ctrlX configurator | https://www.boschrexroth.com/ctrlx-configurator/ |
| Number of channels | 16 |
| EPLAN | https://ecad-configuration.boschrexroth.com/?rootpartnr=BOS.S20-DI-16%2F1%20HS**&downloads=true |
| Weight | 0.180 |
General data
|
Type |
S20-DI-16/1 HS | |
|
Color |
Gray | |
|
Weight 1) |
g |
133 |
|
Ambient temperature (operation) |
-25 °C ... +60 °C | |
|
Ambient temperature (storage/transport) |
-40 °C ... +85 °C | |
|
Permissible relative humidity (operation) |
5 % ... 95 %, no dewing | |
|
Permissible relative humidity (storage/transport) |
5 % ... 95 %, no dewing | |
|
Air pressure (operation) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
|
Air pressure (storage/transport) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
|
Protection type |
IP20 | |
|
Protection class |
III, IEC 61140, EN 61140, VDE 0140-1 | |
|
Installation position |
Any (no temperature derating) | |
| 1) | Including plug and bus base module |
Connection data
|
Type |
S20-DI-16/1 HS | |
|
Designation |
S20 connector | |
|
Connection type |
Push-in technology | |
|
Conductor cross-section solid/flexible/AWG |
0.2 mm² ... 1.5 mm² 0.2 mm² ... 1.5 mm² 24 ... 16 |
|
|
Stripping length |
mm |
8 |
Interface local bus
|
Type |
S20-DI-16/1 HS | |
|
Connection type |
Bus base module | |
|
Transmission speed |
MBit/s |
100 |
Power supply to logic
|
Type |
S20-DI-16/1 HS | |
|
Logic voltage UBus 1) |
V DC |
5 |
|
Maximum current consumption from UBus |
mA |
120 |
|
Maximum power consumption from UBus |
mW |
600 |
| 1) | Via bus base module |
Power supply to peripherals
|
Type |
S20-DI-16/1 HS | |
|
Feed to digital input modules UI |
V DC |
24 |
|
Maximum permitted voltage range 1) |
19.2 V DC ... 30 V DC | |
|
Current consumption from UI |
mA |
20 |
|
Typical power consumption from UI |
mW |
380 |
|
Maximum power consumption from UI |
mW |
480 |
|
Overvoltage/reverse polarity protection supply voltage |
Electronic (35 V, 0.5 s) / parallel diode; with external security 5 A (only for commissioning) | |
|
Guarantee 2) |
A |
≤ 8 |
| 1) | Including all tolerances, including ripple |
| 2) | Reverse polarity protection up to 5 A |
Digital inputs
|
Type |
S20-DI-16/1 HS | |
|
Number of digital inputs |
16 | |
|
Connection type |
Push-in technology | |
|
Connectivity technology |
1-wire technology | |
|
Description of the input |
Acc. to EN 61131-2 type 1 and type 3 | |
|
Nominal input voltage |
V DC |
24 |
|
Input voltage range |
-3 V DC ... 30 V DC | |
|
Nominal input current |
mA |
2.3 |
|
Current profile |
Linear up to nominal current, then constant around 2.3 mA | |
|
Input voltage range "0" signal |
-3 V DC ... 8.4 V DC | |
|
Input voltage range "1" signal |
9.4 V ... 30 V DC | |
|
Input filter time |
< 5 μs | |
|
Process data update 1) |
µs |
< 5 |
|
Reverse polarity protection |
Parallel diode (30 V, 5 s) | |
| 1) | Bus synchronous |
PROFIBUS telegram data
|
Type |
S20-DI-16/1 HS | |
|
Need for parameter data |
byte |
3 |
|
Need for configuration data |
byte |
6 |
Error messages to the higher-level control or computer system
|
Type |
S20-DI-16/1 HS | |
|
Error message |
Failure in peripheral supply | |
Electrical isolation/insulation of the voltage ranges
|
Type |
S20-DI-16/1 HS | |
|
Test distance |
Test voltage | |
|
5 V supply (logic)/24 V supply (peripherals) |
500 V AC, 50 Hz, 1 min. | |
|
5 V supply (logic)/function earth |
500 V AC, 50 Hz, 1 min. | |
|
24 V supply (peripherals)/function earth |
500 V AC, 50 Hz, 1 min. | |
Mechanical tests
|
Type |
S20-DI-16/1 HS | |
|
Vibration resistance 1) |
g |
5 |
|
Shock 2) |
g |
30 |
|
Continuous shock 2) |
g |
10 |
| 1) | Acc. to EN 60068-2-6/IEC 60068-2-6 |
| 2) | Acc. to EN 60068-2-27/IEC 60068-2-27 |
Conformity
|
Type |
S20-DI-16/1 HS | ||
|
Conforms with |
|||
|
Testing of interference immunity acc. to EN 61000-6-2 |
Discharge of static electricity (ESD) |
Criterion B; 6 kV contact discharge; 8 kV air discharge acc. to EN 61000-4-2/IEC 61000-4-2 | |
|
Electro-magnetic fields |
Criterion A; field strength: 10 V/m acc. to EN 61000-4-3/IEC 61000-4-3 | ||
|
Fast transients (burst) |
Criterion B; 2 kV acc. to EN 61000-4-4/IEC 61000-4-4 | ||
|
Transient overvoltage (surge) |
Criterion B; supply lines DC: ±0.5 kV/±0.5 kV (symmetric/asymmetric) acc. to EN 61000-4-5/IEC 61000-4-5 | ||
|
Line-fed disturbances |
Criterion A; test voltage 10 V acc. to EN 61000-4-6/IEC 61000-4-6 | ||
|
Testing of disturbance transmission acc. to EN 61000-6-3 |
Radio disturbance characteristics |
Class B acc. to EN 55022 | |
|
Approvals |
|
The current approvals can be found at www.boschrexroth.com. |
Dimensions
|
Type |
S20-DI-16/1 HS | |
|
A |
mm |
35 |
|
B |
mm |
126.1 |
|
C |
mm |
54 |
|
Note on dimensions |
The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715). | |