BOSCH REXROTH
R911173120
$2,528.29
- BOSCH REXROTH
- Material:R911173120
- Model:S20-AI6-AO2-SSI2
Quantity in stock: 2
Cabinet I/O S20
The modular, compact device design of the I/O systems from Rexroth provides you with maximum flexibility for cost-effective implementation of your custom machine concepts. The I/O modules have a robust design and mechanics, Forced ventilated - Axial fan 230Vre easy to handle, have a fast reaction time and are quick to install – both in the control cabinet as well as in the field. Open communication standards allow you to perfectly integrate the I/O modules with maximum availability.
Unpacked Weight: 0.247 kg
This module is designed for use within an S20 station. The module is used to acquire analog input signals and to output analog signals. The SSI interfaces are used to acquire the data from absolute encoders with a resolution between 8 bits and 31 bits and transmission rates up to 4 MHz.
Innovative assembly and installation concept |
Individually combinable modules |
Space-saving I/O technology for top hat rail mounting |
Compact, modular and simple |
2D CAD | Download 2D CAD |
3D CAD | Download 3D CAD |
Type code extension | S20-AI6-AO2-SSI2 |
Productgroup ID | 4,6 |
ctrlX configurator | https://www.boschrexroth.com/ctrlx-configurator/ |
Number of channels | 2 |
EPLAN | https://ecad-configuration.boschrexroth.com/?rootpartnr=BOS.S20-AI6-AO2-SSI2**&downloads=true |
Weight | 0.247 |
General data
Type |
S20-AI6-AO2-SSI2 | |
Color |
Gray | |
Weight |
g |
205 |
Ambient temperature (operation) |
-25 °C ... +60 °C | |
Ambient temperature (storage/transport) |
-40 °C ... +85 °C | |
Permissible relative humidity (operation) |
5 % ... 95 % acc. to DIN EN 61131-2, no dewing | |
Permissible relative humidity (storage/transport) |
5 % ... 95 % acc. to DIN EN 61131-2, no dewing | |
Air pressure (operation) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
Air pressure (storage/transport) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
Protection type |
IP20 | |
Protection class |
III, IEC 61140, EN 61140, VDE 0140-1 |
Connection data
Type |
S20-AI6-AO2-SSI2 | |
Designation |
S20 connector | |
Connection type |
Spring-cage connection with direct plug technology | |
Conductor cross-section solid/flexible/AWG |
0.2 mm² ... 1.5 mm² 0.2 mm² ... 1.5 mm² 24 ... 16 |
|
Stripping length |
mm |
8 |
Permissible cable length |
m |
≤ 30 |
Interface local bus
Type |
S20-AI6-AO2-SSI2 | |
Connection type |
Bus base module | |
Number |
2 | |
Transmission speed |
MBit/s |
100 |
Power supply to logic
Type |
S20-AI6-AO2-SSI2 | |
Logic voltage UBus 1) |
V DC |
5 |
Typical current consumption from UBus |
mA |
250 |
Maximum current consumption from UBus |
mA |
300 |
Typical power consumption from UBus |
W |
1.25 |
Maximum power consumption from UBus |
W |
1.5 |
1) | Via bus base module |
Power supply to peripherals
Type |
S20-AI6-AO2-SSI2 | |
Maximum permitted voltage range 1) |
19.2 V DC ... 30 V DC | |
Overvoltage/reverse polarity protection supply voltage |
Diode (in the L path) | |
Transient protection |
Suppressor diode |
1) | Including all tolerances, including ripple |
Encoder supply
Type |
S20-AI6-AO2-SSI2 | |
24 V encoder supply |
||
Short-circuit protection |
Electronic, per channel | |
Transient protection |
Suppressor diode |
Mechanical tests
Type |
S20-AI6-AO2-SSI2 | |
Vibration resistance 1) |
g |
5 |
Shock 2) |
30 g, 11 ms duration, semi-sinusoidal shock pulse | |
Continuous shock 3) |
g |
10 |
1) | Acc. to IEC 60068-2-6 |
2) | Acc. to IEC 60068-2-27 |
3) | Acc. to EN 60068-2-27 |
Conformity
Type |
S20-AI6-AO2-SSI2 | ||
Conforms with |
|||
Testing of interference immunity acc. to EN 61000-6-2 |
Discharge of static electricity (ESD) |
Criterion B; 6 kV contact discharge; 8 kV air discharge acc. to EN 61000-4-2/IEC 61000-4-2 | |
Electro-magnetic fields |
Criterion A; field strength: 10 V/m acc. to EN 61000-4-3/IEC 61000-4-3 | ||
Fast transients (burst) |
Criterion B; 2 kV acc. to EN 61000-4-4/IEC 61000-4-4 | ||
Transient overvoltage (surge) |
Criterion B; supply lines DC: ±0.5 kV/±0.5 kV (symmetric/asymmetric) acc. to EN 61000-4-5/IEC 61000-4-5 | ||
Line-fed disturbances |
Criterion A; test voltage 10 V acc. to EN 61000-4-6/IEC 61000-4-6 | ||
Testing of disturbance transmission acc. to EN 61000-6-3 |
Radio disturbance characteristics |
Class A acc. to EN 55022 |
Approvals |
The current approvals can be found at www.boschrexroth.com. |
Dimensions
Type |
S20-AI6-AO2-SSI2 | |
A |
mm |
53.6 |
B |
mm |
126.1 |
C |
mm |
54 |
Note on dimensions |
The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715). |