You are using an outdated browser. For a faster, safer browsing experience, upgrade for free today.

BOSCH REXROTH
R911172899


$2,123.73 USD
  • BOSCH REXROTH
  • Material:R911172899
  • Model:S67-S3-BK-DI8-M8

Quantity in stock: 0

Note: Sales tax, and shipping will be calculated at checkout.
***Disclaimer: The following summary contains information gathered from various sources such as product descriptions, technical specifications and catalogs. While efforts have been made to provide accurate details, inaccuracies may occur. It is advised to verify all information by contacting Bosch Rexroth directly.***
The Bosch Rexroth S67-S3-BK-DI8-M8 (R911172899) is a fieldbus coupler designed to seamlessly integrate S IO modules with a Sercos III network. This unit features 8 digital inputs, enabling it to handle multiple signals and facilitate efficient data communication within automated systems. It is engineered to support a considerable number of modules on the local system bus, enhancing its scalability and flexibility for various application requirements. The S67-S3-BK-DI8-M8 ensures reliable connectivity within an automation setup, maintaining a maximum distance of 10 meters between any two modules. This capability is critical in distributed control systems where components are spread across different locations. Moreover, it allows for a total extension of up to 50 meters per station, providing ample coverage for extensive industrial environments. Its robust design and adherence to industry standards make it suitable for a broad range of applications that require precise and secure communication between control systems and peripheral devices.

This fieldbus coupler is used to connect the S67 I/O modules to Sercos III. It comes with 8 digital inputs. It supports up to 64 modules on the local system bus. The maximum distance between two modules is 50 meters, with a maximum total extension of 500 meters per station.

General data

Type

S67-S3-BK-DI8-M8

Weight

g

≈ 360

Ambient temperature (operation)

-25 °C ... +60 °C

Permissible relative humidity (operation)

5 % ... 95 %, no dewing

Air pressure (operation)

795 ... 1080 hPa

Protection type

IP67

Interface fieldbus

Type

S67-S3-BK-DI8-M8

Fieldbus system

Sercos

Connection type

M12 connector, shielded, B-coded, 5-pin

Transmission speed 1)

​100 MBit/s

Transfer physics

Copper cable (Cat-5e, Class D)
-
-
-
1) Full-duplex

Interface local bus

Type

S67-S3-BK-DI8-M8

Designation

System bus

Connection type

M12 connector, shielded, B-coded, 5-pin

Transfer physics

Copper cable (Cat-5e, Class D)

System boundaries

Type

S67-S3-BK-DI8-M8

Number of supported participants per station 1)

≤ 63
1) I/O modules

Supply of module electronics

Type

S67-S3-BK-DI8-M8

Connection type

A-coded 4-pin M12 plug

Current carrying capacity of supply connections 1)

A

≤ 8

Voltage supply logic and sensors ULS

V DC

24

Voltage supply actuators UA

V DC

24

Current consumption from ULS

Typ. 45 mA + sensors (max. 400 mA)

Current consumption from UA

mA

5

Reverse polarity protection

For ULS + UA

Short-circuit protection of the sensor supply

Yes
1) (ULS: 4 A, UA: 4 A)

Digital inputs

Type

S67-S3-BK-DI8-M8

Number of digital inputs

8

Connection type

A-coded 3-pin M8 plug

Connectivity technology

2-, 3-wire technology

Dimensioning of inputs

Acc. to EN 61131-2 type 1

Input voltage range

24 V DC (-30 V DC < UIN < +30 V DC)

Nominal input voltage UINenn

V DC

24

Nominal input current at UINenn

mA

2.8

Input voltage range "0" signal

-30 V ... +5 V

Input voltage range "1" signal

+15 V ... +30 V

Input filter time

≤ 10 μs

Mechanical tests

Type

S67-S3-BK-DI8-M8

Vibration resistance

Acc. to IEC 60068-2-6

Shock

Acc. to IEC 60068-2-27

Approvals

The current approvals can be found at www.boschrexroth.com.

technical illustration-R911172899-

Dimensions

Type

S67-S3-BK-DI8-M8

A

mm

75

B

mm

117

C1

mm

10.7

C2

mm

25