BOSCH REXROTH
R911172894
$595.56 USD
- BOSCH REXROTH
- Material:R911172894
- Model:R-IB IL AI 4/I-PAC
Quantity in stock: 0
The Bosch Rexroth R-IB IL AI 4/I-PAC (R911172894) is an advanced analog input module crafted for seamless integration within an Inline station, primarily utilized for the precise acquisition of analog current signals. This robust module features differential input channels that accommodate a range of ...mA to ...mA, ensuring versatile applications in signal acquisition. The design incorporates a wire connection technique that facilitates straightforward installation and maintenance. Included with the R-IB IL AI 4/I-PAC are essential accessories such as a connection plug and a labeling field, which aid in organization and identification within complex systems. The labeling field is particularly useful for system operators to quickly recognize and manage the module's function within the Inline station. This input module exemplifies Bosch Rexroth's commitment to producing high-quality automation components that enhance system reliability and performance. It is engineered to meet stringent standards, ensuring it operates effectively within industrial environments that require precise monitoring and control of analog signals. The R-IB IL AI 4/I-PAC is ideal for applications where accurate data acquisition is critical, providing users with a dependable solution for their automation needs.
Inline connector
The modular, compact equipment configuration of the I/O systems from Rexroth offers you maximum flexibility for the cost-effective implementation of your individual machine concepts. The I/O modules have robust design and mechanics, are easy to use, have a quick reaction time and are quick to install – both in the control cabinet and in the field. Open communication standards allow you perfect integration of the I/O modules with maximum availability.
Unpacked Weight: 0.089 kg
This module is designed for use within an Inline station. It is used to acquire analog current signals.
| Data Sheet | Download Data Sheet |
| 3D CAD | Download 3D CAD |
| Manual | Download Manual |
| Air pressure (operation) | 70-106 kPa (up to 3,000 m above sea level) |
| Air pressure (storage / transport) | 70-106 kPa (up to 3,000 m above sea level) |
| Width | 12.2 |
| Productgroup ID | 4,6 |
| Height | 120 |
| International protection code | IP20 |
| Permissible air humidity (storage) | 10-95 |
| Permissible air humidity (transport) | 10-95 |
| A/D conversion time | 6.5 |
| Number of channels | 4 |
| Current input signal | 0-20 mA 4-20 mA |
| Connection type | Zugfederanschluss |
| Connection techniques | 2-Leitertechnik |
| Depth | 71.5 |
| Weight | 0.089 |
| Ambient temperature (during operation) | -25-55 |
| Ambient temperature (storage and transport) | -25-85 |
| Conductor cross-section | Rigid: 0.2-1.5 mm²,Flexible: 0.2-1.5 mm²,AWG: 24 ... 16 |
General data
|
Type |
R-IB IL AI 4/I-PAC | |
|
Color |
Gray | |
|
Weight 1) |
g |
66 |
|
Ambient temperature (operation) |
-25 °C ... +55 °C | |
|
Ambient temperature (storage/transport) |
-25 °C ... +85 °C | |
|
Permissible relative humidity (operation) |
10 % ... 95 % acc. to DIN EN 61131-2 | |
|
Permissible relative humidity (storage/transport) |
10 % ... 95 % acc. to DIN EN 61131-2 | |
|
Air pressure (operation) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
|
Air pressure (storage/transport) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
|
Protection type |
IP20, IEC 60529 | |
|
Protection class |
III, IEC 61140, EN 61140, VDE 0140-1 | |
| 1) | Including plug |
Connection data
|
Type |
R-IB IL AI 4/I-PAC | |
|
Designation |
Inline connection plug | |
|
Connection type |
Spring-cage connection | |
|
Conductor cross-section solid/flexible/AWG |
0.2 mm² ... 1.5 mm² 0.2 mm² ... 1.5 mm² 24 ... 16 |
|
Interface local bus
|
Type |
R-IB IL AI 4/I-PAC | |
|
Connection type |
Inline data jumper | |
|
Transmission speed |
kBit/s |
500 |
|
Transfer physics |
Copper | |
Inline potentials/performance balance
|
Type |
R-IB IL AI 4/I-PAC | |
|
Logic voltage UL 1) |
V DC |
7.5 |
|
Typical current consumption from UL |
mA |
55 |
|
Peripheral supply voltage UANA |
V DC |
24 |
|
Typical current consumption from UANA |
mA |
30 |
|
Typical power consumption total |
W |
0.94 |
| 1) | Via potential jumpers |
Analog inputs
|
Type |
R-IB IL AI 4/I-PAC | |
|
Number of analog inputs 1) |
4 | |
|
Connectivity technology |
2-wire technology | |
|
Current input signal |
0 mA ... 20 mA 4 mA ... 20 mA - |
|
|
Resolution A/D |
bits |
12 |
|
A/D conversion time |
µs |
≤ 6.5 |
|
Limit frequency (3 dB) |
Hz |
300 |
|
Measurement representation |
13 bits (12 bits + sign) - - - - - |
|
|
Data formats |
IB IL, S7 compatible | |
|
Process data update 2) |
µs |
250 |
|
Filtering |
None or averaged over 4, 16 or 32 measured values | |
|
Overload protection |
Max. ±5.2 V DC, Imax = 50 mA | |
|
Typical input resistance power input |
Ω |
113 |
|
Open circiut response |
Regulating toward 0 mA; wire break detection for 4 mA ... 20 Ma | |
| 1) | Differential inputs, current |
| 2) | All channels |
Programming data
|
Type |
R-IB IL AI 4/I-PAC | |
|
ID code (hex) |
7F | |
|
ID code (dec) |
127 | |
|
Length code (hex) |
04 | |
|
Length code (dec) |
04 | |
|
Process data channel |
bits |
64 |
|
Input address room |
byte |
8 |
|
Output address room |
byte |
8 |
|
Parameter channel (PCP) |
byte |
0 |
|
Register length (bus) |
bits |
64 |
Fieldbus data telegram
|
Type |
R-IB IL AI 4/I-PAC | |
|
Need for parameter data |
byte |
10 |
|
Need for configuration data |
byte |
5 |
Error messages to the higher-level control or computer system
|
Type |
R-IB IL AI 4/I-PAC | |
|
Error message |
Upon failure of the internal peripheral power supply: Peripheral error message to the bus coupler Upon failure of the peripheral power supply: Message in the diagnostic code (in format IB IL) When the measurement range is exceeded or undershot: Message in the diagnostic code (in format IB IL) Upon invalid configuration: Message in the diagnostic code (in format IB IL) |
|
Electrical isolation/insulation of the voltage ranges
|
Type |
R-IB IL AI 4/I-PAC | |
|
Test distance |
Test voltage | |
|
5 V supply incoming remote bus/7.5 V supply (bus logic) |
500 V AC, 50 Hz, 1 min. | |
|
5 V supply to further remote bus/7.5 V supply (bus logic) |
500 V AC, 50 Hz, 1 min. | |
|
7.5 V supply (bus logic), 24 V supply UANA/peripherals |
500 V AC, 50 Hz, 1 min. | |
|
7.5 V supply (bus logic), 24 V supply UANA/function earth |
500 V AC, 50 Hz, 1 min. | |
|
Peripherals/function earth |
500 V AC, 50 Hz, 1 min. | |
Conformity
|
Type |
R-IB IL AI 4/I-PAC | ||
|
Conforms with |
|||
|
Testing of interference immunity acc. to EN 61000-6-2 |
Discharge of static electricity (ESD) |
Criterion B; 6 kV contact discharge; 8 kV air discharge acc. to EN 61000-4-2/IEC 61000-4-2 | |
|
Electro-magnetic fields |
Criterion A; field strength: 10 V/m acc. to EN 61000-4-3/IEC 61000-4-3 | ||
|
Fast transients (burst) |
Criterion B; 2 kV acc. to EN 61000-4-4/IEC 61000-4-4 | ||
|
Transient overvoltage (surge) |
Criterion B; supply lines DC: ±1 kV/±1 kV (symmetric/asymmetric); ±1 kV on shielded I/O lines acc. to EN 61000-4-5/IEC 61000-4-5 | ||
|
Line-fed disturbances |
Criterion A; test voltage 10 V acc. to EN 61000-4-6/IEC 61000-4-6 | ||
|
Testing of disturbance transmission acc. to EN 61000-6-3 |
Radio disturbance characteristics |
Class A acc. to EN 55022 | |
|
Approvals |
|
The current approvals can be found at www.boschrexroth.com. |
Dimensions
|
Type |
R-IB IL AI 4/I-PAC | |
|
A |
mm |
12.2 |
|
B |
mm |
120 |
|
C |
mm |
71.5 |
|
Note on dimensions |