BOSCH REXROTH
R911172575
$1,464.03 USD
- BOSCH REXROTH
- Material:R911172575
- Model:R-IB IL AO 1/SF/CN-PAC
Quantity in stock: 0
The Bosch Rexroth R-IB IL AO 1/SF/CN-PAC (R911172575) is a high-precision module engineered for seamless integration within an Inline station to facilitate the output of analog current or voltage signals. This module is adept at converting digital signals from the control level to analog signals, which are then used for driving actuators or for monitoring purposes. It serves as a crucial interface between the digital world of control systems and the analog inputs and outputs found in various automation environments. The R-IB IL AO 1/SF/CN-PAC module boasts remarkable versatility, being capable of handling a wide range of signal types, which makes it suitable for diverse applications that require precise control over process parameters such as temperature, pressure, or flow rate. Its robust design ensures reliable operation even in demanding industrial conditions. This Bosch Rexroth module stands out with its ease of installation and maintenance, designed with user-friendly features that promote quick setup and minimal downtime. Its compact form factor allows efficient use of space within control cabinets, while also ensuring compatibility with other components in the Inline station series. In summary, the R911172575 model from Bosch Rexroth is a specialized output module that excels in converting digital commands into precise analog outputs necessary for controlling complex industrial processes. Its integration capabilities and reliability make it an essential component for operations seeking accuracy and efficiency in their automation systems.
This module is designed for use within an Inline station. It is used to output analog current or voltage signals.
General data
|
Type |
R-IB IL AO 1/SF(/CN)-PAC | |
|
Color |
Gray | |
|
Weight 1) |
g |
126 |
|
Operating mode |
Process data operation with 1 word | |
|
Ambient temperature (operation) |
-25 °C ... +55 °C | |
|
Ambient temperature (storage/transport) |
-25 °C ... +85 °C | |
|
Permissible relative humidity (operation) |
10 % ... 95 % acc. to DIN EN 61131-2 | |
|
Permissible relative humidity (storage/transport) |
10 % ... 95 % acc. to DIN EN 61131-2 | |
|
Air pressure (operation) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
|
Air pressure (storage/transport) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
|
Protection type |
IP20 | |
|
Protection class |
III, IEC 61140, EN 61140, VDE 0140-1 | |
| 1) | Including plug |
Connection data
|
Type |
R-IB IL AO 1/SF(/CN)-PAC | |
|
Designation |
Inline connection plug | |
|
Connection type |
Spring-cage connection | |
|
Conductor cross-section solid/flexible/AWG |
0.2 mm² ... 1.5 mm² 0.2 mm² ... 1.5 mm² 24 ... 16 |
|
Interface local bus
|
Type |
R-IB IL AO 1/SF(/CN)-PAC | |
|
Connection type |
Inline data jumper | |
|
Transmission speed |
kBit/s |
500 |
|
Transfer physics |
Copper | |
Inline potentials/performance balance
|
Type |
R-IB IL AO 1/SF(/CN)-PAC | |
|
Logic voltage UL 1) |
V DC |
7.5 |
|
Typical current consumption from UL |
mA |
30 |
|
Maximum current consumption from UL |
mA |
40 |
|
Peripheral supply voltage UANA |
V DC |
24 |
|
Typical current consumption from UANA |
mA |
50 |
|
Maximum current consumption from UANA |
mA |
65 |
|
Typical power consumption total |
W |
1.425 |
| 1) | Via potential jumpers |
Analog outputs
|
Type |
R-IB IL AO 1/SF(/CN)-PAC | |
|
Number of analog outputs |
1 | |
|
Connectivity technology |
2-wire technology (shielded) | |
|
Resolution D/A |
bits |
16 |
|
Output value representation |
16 bits | |
|
Process data update |
ms |
< 1 |
|
Transient protection |
Yes | |
Analog outputs, current
|
Type |
R-IB IL AO 1/SF(/CN)-PAC | |
|
Current output signal |
0 mA ... 20 mA 4 mA ... 20 mA - |
|
|
Output load current output |
Ω |
> 500 |
|
Precision |
Typ. 0.8 % (of the output range end value) | |
Analog outputs, voltage
|
Type |
R-IB IL AO 1/SF(/CN)-PAC | |
|
Voltage output signal |
0 V ... 10 V | |
|
Output load voltage output |
kΩ |
> 2 |
|
Precision |
Typ. 0.5 % (of the output range end value) | |
Programming data
|
Type |
R-IB IL AO 1/SF(/CN)-PAC | |
|
ID code (hex) |
7D | |
|
ID code (dec) |
125 | |
|
Length code (hex) |
01 | |
|
Length code (dec) |
01 | |
|
Process data channel |
bits |
16 |
|
Input address room |
byte |
0 |
|
Output address room |
byte |
2 |
|
Parameter channel (PCP) |
byte |
0 |
|
Register length (bus) |
bits |
16 |
Fieldbus data telegram
|
Type |
R-IB IL AO 1/SF(/CN)-PAC | |
|
Need for parameter data |
byte |
4 |
|
Need for configuration data |
byte |
4 |
Error messages to the higher-level control or computer system
|
Type |
R-IB IL AO 1/SF(/CN)-PAC | |
|
Error message |
Upon failure or undershooting of the logic voltage UL: Peripheral error message to the bus coupler | |
Electrical isolation/insulation of the voltage ranges
|
Type |
R-IB IL AO 1/SF(/CN)-PAC | |
|
Test distance |
Test voltage | |
|
7.5 V supply (bus logic), 24 V supply UANA/peripherals |
500 V AC, 50 Hz, 1 min. | |
|
7.5 V supply (bus logic), 24 V supply UANA/function earth |
500 V AC, 50 Hz, 1 min. | |
|
24 V supply (peripherals)/function earth |
500 V AC, 50 Hz, 1 min. | |
Mechanical tests
|
Type |
R-IB IL AO 1/SF(/CN)-PAC | |
|
Shock 1) |
15 g, 11 ms; 25 g, 6 ms; half sinusoidal shock pulse, 3 shocks per spatial direction | |
| 1) | Acc. to EN 60068-2-27/IEC 60068-2-27Deviation compared to DOK-CONTRL-ILSYSINS***-AW..-DE-P |
|
Approvals |
|
The current approvals can be found at www.boschrexroth.com. |
Dimensions
|
Type |
R-IB IL AO 1/SF(/CN)-PAC | |
|
A |
mm |
24.4 |
|
B |
mm |
136.8 |
|
C |
mm |
71.5 |
|
Note on dimensions |
The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715). | |