The Bosch Rexroth R-IB IL 24 SEG/F-PAC (R911170790) is a specialized module designed for integration within an Inline station, enabling the construction of a fuse-protected subcircuit segment within a main electrical circuit. This particular model is characterized by its ability to function as part of a voltage distribution control system, utilizing DC voltage. It is important to note that this module is not equipped to supply power on its own and, as such, lacks reverse polarity and overvoltage protection features. The R-IB IL 24 SEG/F-PAC module comes complete with essential accessories including a connection plug and a labeling field, which facilitate easy installation and maintenance. The inclusion of these accessories ensures that users have everything necessary for straightforward implementation into their systems. The module's design allows for efficient organization of electrical circuits by providing fuse protection for specific segments, enhancing safety and reliability in various applications. In summary, the Bosch Rexroth R-IB IL 24 SEG/F-PAC is an integral component for users looking to improve their electrical circuit management through the creation of secure, fuse-protected segments within larger systems. Its compatibility with Inline stations makes it a versatile choice for those in need of segmented voltage distribution solutions.
Inline connector
The modular, compact equipment configuration of the I/O systems from Rexroth offers you maximum flexibility for the cost-effective implementation of your individual machine concepts. The I/O modules have robust design and mechanics, are easy to use, have a quick reaction time and are quick to install – both in the control cabinet and in the field. Open communication standards allow you perfect integration of the I/O modules with maximum availability.
Unpacked Weight: 0.088 kg
This module is designed for use within an Inline station. It can be used to build a fuse-protected sub-circuit (segment circuit) within a main circuit. The module cannot be used to supply power, so it does not come with any reverse polarity or overvoltage protection.
| Data Sheet | Download Data Sheet |
| 3D CAD | Download 3D CAD |
| Manual | Download Manual |
| Air pressure (operation) | 70-106 kPa (up to 3,000 m above sea level) |
| Air pressure (storage / transport) | 70-106 kPa (up to 3,000 m above sea level) |
| Rated value; 24V periphery (main circuit UM) | The voltage is fed in the bus coupler or the power terminal. At the segment terminal, no connections are required for the supply voltage. The corresponding terminal points are only available for test purposes. |
| Width | 12.2 |
| Productgroup ID | 4,6 |
| Height | 120 |
| Maximum current | 8 |
| International protection code | IP20 |
| Permissible air humidity (storage) | 10-95 |
| Permissible air humidity (transport) | 10-95 |
| Connection type | Zugfederanschluss |
| Depth | 71.5 |
| Weight | 0.088 |
| Ambient temperature (during operation) | -25-55 |
| Ambient temperature (storage and transport) | -25-85 |
| Conductor cross-section | Rigid: 0.2-1.5 mm²,Flexible: 0.2-1.5 mm²,AWG: 24 ... 16 |
General data
|
Type |
R-IB IL 24 SEG/F-PAC | |
|
Weight 1) |
g |
59 |
|
Ambient temperature (operation) |
-25 °C ... +55 °C | |
|
Ambient temperature (storage/transport) |
-25 °C ... +85 °C | |
|
Permissible relative humidity (operation) |
10 % ... 95 %, EN 61131-2 | |
|
Permissible relative humidity (storage/transport) |
10 % ... 95 %, EN 61131-2 | |
|
Air pressure (operation) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
|
Air pressure (storage/transport) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
|
Protection type |
IP20, IEC 60529 | |
|
Protection class |
III, EN 61113-2, IEC 61113-2 | |
| 1) | Including plug |
Connection data
|
Type |
R-IB IL 24 SEG/F-PAC | |
|
Designation |
Inline connection plug | |
|
Connection type |
Tension spring modules | |
|
Conductor cross-section solid/flexible/AWG |
0.2 mm² ... 1.5 mm² 0.2 mm² ... 1.5 mm² 24 ... 16 |
|
Interface local bus
|
Type |
R-IB IL 24 SEG/F-PAC | |
|
Transmission speed 1) |
kBit/s MBit/s |
500 2 |
| 1) | Can be used with this transmission speed in Inline stations, if required |
|
24 V peripheral supply |
|
The voltage is fed in the bus coupler or in the feed module. Connections for the supply voltage are not needed at the segment module. The corresponding module points are available only for test purposes. |
Permissible total current in the potential jumpers of the main and segment circuits
|
Type |
R-IB IL 24 SEG/F-PAC | |
|
Permissible total current in the potential jumpers |
A |
8 |
|
Nominal module current |
A |
6 |
Protective devices
|
Type |
R-IB IL 24 SEG/F-PAC | |
|
Overload/short-circuit protection in the segment circuit |
Safety fuse 5 x 20 mm with 6.3 A time-lag (maximum value of fuse 8 A. For fuses with a value of greater than 2 A, only use slow fuses!) | |
|
Reverse polarity protection |
Protection components in the feed module or in the bus coupler | |
|
Overvoltage protection |
Protection components in the feed module or in the bus coupler | |
Electrical isolation/insulation of the voltage ranges
|
Type |
R-IB IL 24 SEG/F-PAC | |
|
Common potentials |
||
|
24 V main voltage UM, 24 V segment voltage US and GND are on the same potential. FE represents a separate potential area. |
||
|
Separate potentials in the system of bus coupler/feed module and I/O module |
||
|
Test distance |
Test voltage | |
|
5 V supply incoming remote bus/7.5 V supply (bus logic) |
500 V AC, 50 Hz, 1 min. | |
|
5 V supply to further remote bus/7.5 V supply (bus logic) |
500 V AC, 50 Hz, 1 min. | |
|
7.5 V supply (bus logic)/24 V supply (peripherals) |
500 V AC, 50 Hz, 1 min. | |
|
24 V supply (peripherals)/function earth |
500 V AC, 50 Hz, 1 min. | |
Error messages to the higher-level control or computer system
|
Type |
R-IB IL 24 SEG/F-PAC | |
|
Error message |
None | |
|
Approvals |
|
The current approvals can be found at www.boschrexroth.com. |
Dimensions
|
Type |
R-IB IL 24 SEG/F-PAC | |
|
A |
mm |
12.2 |
|
B |
mm |
120 |
|
C |
mm |
71.5 |
|
Note on dimensions |
The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715). | |