You are using an outdated browser. For a faster, safer browsing experience, upgrade for free today.

BOSCH REXROTH
R911170785


$816.38 USD
  • BOSCH REXROTH
  • Material:R911170785
  • Model:R-IBILTEMP2RTD-PAC

Quantity in stock: 0

Note: Sales tax, and shipping will be calculated at checkout.
***Disclaimer: The following summary contains information gathered from various sources such as product descriptions, technical specifications and catalogs. While efforts have been made to provide accurate details, inaccuracies may occur. It is advised to verify all information by contacting Bosch Rexroth directly.***
The Bosch Rexroth R-IB IL TEMP 2 RTD-PAC (R911170785) is a highly specialized input module that forms an integral part of an Inline station, designed to facilitate precise temperature monitoring and control within various applications. This two-channel input module is engineered to accommodate resistive temperature sensors, offering compatibility with platinum and nickel sensors that adhere to DIN standards as well as SAMA directives. Additionally, it supports a range of sensors including Cu10, Cu50, Cu100, KTY84-130, and KTY84-150 types, providing versatility in its use across different sensor technologies. The R-IB IL TEMP 2 RTD-PAC excels in delivering accurate temperature readings by converting the resistance values from the connected sensors into digital data. This data is then represented in a clear format using bit values across two process data words – one for each channel – enabling users to monitor temperatures with precision. The module's design ensures seamless integration into the Inline station architecture while maintaining high reliability and performance standards expected of industrial-grade components. With its robust construction and advanced functionality, the Bosch Rexroth R-IB IL TEMP 2 RTD-PAC module is an essential component for systems requiring meticulous temperature regulation. Whether used in manufacturing processes or other complex applications where temperature plays a critical role, this module delivers the accuracy and reliability needed to maintain optimal operating conditions.


Inline connector

The modular, compact equipment configuration of the I/O systems from Rexroth offers you maximum flexibility for the cost-effective implementation of your individual machine concepts. The I/O modules have robust design and mechanics, are easy to use, have a quick reaction time and are quick to install – both in the control cabinet and in the field. Open communication standards allow you perfect integration of the I/O modules with maximum availability.

Unpacked Weight: 0.096 kg

This module is designed for use within an Inline station. The module provides you with a two-channel input module for resistive temperature sensors. This module supports platinum and nickel sensors in accordance with the DIN standard and SAMA directive. Cu10, Cu50, Cu53, KTY81 and KTY84 sensors are also supported. The measuring temperature is displayed using 16-bits values in two process data words (one word per channel).

Air pressure (operation)70-106 kPa (up to 3,000 m above sea level)
Supported sensor typesPt, Ni, Cu, KTY
Width12.2
Productgroup ID4,6
Height136.8
International protection codeIP20
Permissible air humidity (storage)10-95
Permissible air humidity (transport)10-95
Number of channels2
Connection typeZugfederanschluss
Connection techniques2-, 3- und 4-Leitertechnik
Depth71.5
Weight0.096
Ambient temperature (during operation)-25-55
Ambient temperature (storage and transport)-25-85
Conductor cross-sectionRigid: 0.2-1.5 mm²,Flexible: 0.2-1.5 mm²,AWG: 24 ... 16

General data

Type

R-IB IL TEMP 2 RTD-PAC

Weight 1)

g

67

Operating mode

Process data mode with 2 words

Sensor connection type

2-, 3- and 4-wire technology

Ambient temperature (operation)

-25 °C ... +55 °C

Ambient temperature (storage/transport)

-25 °C ... +85 °C

Permissible relative humidity (operation)

10 % ... 95 % acc. to DIN EN 61131-2

Permissible relative humidity (storage/transport)

10 % ... 95 % acc. to DIN EN 61131-2

Air pressure (operation)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Air pressure (storage/transport)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Protection type

IP20, IEC 60529

Protection class

III, IEC 61140
1) Including plug

Connection data

Type

R-IB IL TEMP 2 RTD-PAC

Designation

Inline connection plug

Connection type

Tension spring modules

Conductor cross-section solid/flexible/AWG

0.2 mm² ... 1.5 mm²
0.2 mm² ... 1.5 mm²
24 ... 16

Interface local bus

Type

R-IB IL TEMP 2 RTD-PAC

Connection type

Data ranking

Transmission speed

kBit/s

500

Inline potentials/performance balance

Type

R-IB IL TEMP 2 RTD-PAC

Logic voltage UL

V DC

7.5

Typical current consumption from UL

mA

43

Maximum current consumption from UL

mA

60

Peripheral supply voltage UANA

V DC

24

Typical current consumption from UANA

mA

11

Maximum current consumption from UANA

mA

18

Typical power consumption total

mW

587

Maximum power consumption total

mW

882

Supply of module electronics and peripherals via bus coupler/power feed module

Type

R-IB IL TEMP 2 RTD-PAC

Connectivity technology

Potential jumpers

Analog inputs

Type

R-IB IL TEMP 2 RTD-PAC

Number of analog inputs 1)

2

Connectivity technology

2, 3 or 4-wire, shielded sensor cable

Supported sensor types (RTD)

Pt, Ni, Cu, KTY

Characteristics standards

DIN/SAMA

Typical conversion time for the A/D converter

µs

120

Process data update

Both channels in 2-wire technology

ms

20

One channel in 2-wire technology, one channel in 4-wire technology

ms

20

Both channels in 3-wire technology

ms

32
1) For resistive temperature sensors

Electrical isolation/insulation of the voltage ranges

Type

R-IB IL TEMP 2 RTD-PAC

Common potentials

24 V main voltage UM, 24 V segment voltage US and GND are on the same potential. FE represents a separate potential area.

Separate potentials in the module

Test distance

Test voltage

7.5 V power supply (bus logic)/24 V analog power supply (analog peripherals)

500 V AC, 50 Hz, 1 min.

7.5 V supply (bus logic)/function earth

500 V AC, 50 Hz, 1 min.

24 V analog supply (analog peripherals)/function earth

500 V AC, 50 Hz, 1 min.

Error messages to the higher-level control or computer system

Type

R-IB IL TEMP 2 RTD-PAC

Error message

Failure of the internal voltage supply
Upon failure or undershooting of the logic voltage UL: Peripheral error message to the bus coupler
-
-

Error messages about process data

Error message

Peripheral / user error

Approvals

The current approvals can be found at www.boschrexroth.com.

technical illustration-R911170785-Inline connector

Dimensions

Type

R-IB IL TEMP 2 RTD-PAC

A

mm

12.2

B

mm

136.8

C

mm

71.5

Note on dimensions

The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715).