You are using an outdated browser. For a faster, safer browsing experience, upgrade for free today.

BOSCH REXROTH
R911170756


$358.31 USD
  • BOSCH REXROTH
  • Material:R911170756
  • Model:R-IBIL24DO8-PAC

Quantity in stock: 0

Note: Sales tax, and shipping will be calculated at checkout.
***Disclaimer: The following summary contains information gathered from various sources such as product descriptions, technical specifications and catalogs. While efforts have been made to provide accurate details, inaccuracies may occur. It is advised to verify all information by contacting Bosch Rexroth directly.***
The Bosch Rexroth R-IB IL 24 DO 8-PAC (R911170756) is a high-quality digital output module designed for seamless integration within an Inline station. This module specializes in outputting digital signals, making it a critical component for automation tasks that require precise control and signal dispatch. The R-IB IL 24 DO 8-PAC is engineered to facilitate the management of digital outputs with efficiency and reliability. With its eight digital output channels, this module provides the capacity to handle multiple signal outputs simultaneously, which is essential for complex or large-scale operations. The robust design ensures that it can withstand the demands of continuous industrial use while maintaining accuracy and performance. Its compatibility with other components in an Inline station allows for a flexible and scalable system design, enabling users to tailor their setup to specific application requirements. The capability of the R-IB IL 24 DO 8-PAC to work within an integrated system makes it suitable for a variety of applications where digital signal processing is paramount. It offers users a dependable solution for controlling actuators, sensors, and other devices that form part of an automated process or machinery control system. Users can expect consistent output quality and stable operation from this Bosch Rexroth module, which is designed to meet stringent industry standards for digital output modules.


Inline connector

The modular, compact equipment configuration of the I/O systems from Rexroth offers you maximum flexibility for the cost-effective implementation of your individual machine concepts. The I/O modules have robust design and mechanics, are easy to use, have a quick reaction time and are quick to install – both in the control cabinet and in the field. Open communication standards allow you perfect integration of the I/O modules with maximum availability.

Unpacked Weight: 0.203 kg

This module is designed for use within an Inline station. It is used to output digital signals.

Air pressure (operation)70-106 kPa (up to 3,000 m above sea level)
Total current4
Air pressure (storage / transport)66-108 kPa (up to 3,500 m above sea level)
Width48.8
Productgroup ID4,6
Overload-/ short circuit protection in the segment circuitElectronic; by two 4-channel drivers
Height120
International protection codeIP20
Permissible air humidity (storage)10-95
Permissible air humidity (transport)10-95
Number of channels8
Connection typeZugfederanschluss
Connection techniques2-, 3- und 4-Leitertechnik
Depth71.5
Weight0.203
Ambient temperature (during operation)-25-55
Ambient temperature (storage and transport)-25-85
Conductor cross-sectionRigid: 0.08-0.5 mm²,Flexible: 0.08-0.5 mm²,AWG: 28 ... 16

General data

Type

R-IB IL 24 DO 8-PAC

Weight 1)

g

190

Operating mode

Process data operation with 1 byte

Actuator connection type

2-, 3- and 4-wire technology

Ambient temperature (operation)

-25 °C ... +55 °C

Ambient temperature (storage/transport)

-25 °C ... +85 °C

Permissible relative humidity (operation)

10 % ... 95 % acc. to DIN EN 61131-2

Permissible relative humidity (storage/transport)

10 % ... 95 % acc. to DIN EN 61131-2

Air pressure (operation)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Air pressure (storage/transport)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Protection type

IP 20, IEC 60529

Protection class

III, EN 61131-2, IEC 61131-2
1) Including plug

Connection data

Type

R-IB IL 24 DO 8-PAC

Designation

Inline connection plug

Connection type

Tension spring modules

Conductor cross-section solid/flexible/AWG

0.08 mm² ... 1.5 mm²
0.08 mm² ... 1.5 mm²
28 ... 16

Interface local bus

Type

R-IB IL 24 DO 8-PAC

Connection type

Data ranking

Transmission speed

kBit/s

500

Supply of module electronics and peripherals via bus coupler/power feed module

Type

R-IB IL 24 DO 8-PAC

Connectivity technology

Data ranking

Inline potentials/performance balance

Type

R-IB IL 24 DO 8-PAC

Logic voltage

V DC

7.5

Maximum current consumption from UL

mA

60

Maximum power consumption from UL

W

0.45

Segment supply voltage US

V DC

24

Nominal current consumption from US

≤4 A (8 x 0.5 A)

Digital outputs

Type

R-IB IL 24 DO 8-PAC

Number of digital outputs

8

Nominal output voltage UOut

V DC

24

Differential voltage at INenn

V

≤ 1

Nominal current INenn each channel

A

0.5

Nominal current tolerance

%

+ 10

Total current

A

4

Nominal load

Ohmic

48 Ω

W

12

Lamps

W

12

Inductance

1.2 H; 50 Ω

VA

12

Signal delay upon turning on of a

Ohmic nominal load

µs

100

Lamp nominal load 1)

ms

100

Inductive nominal load

1.2 H; 50 Ω

ms

100

Signal delay upon deactivating a

Ohmic nominal load

ms

1

Lamp nominal load

ms

1

Inductive nominal load

1.2 H; 50 Ω

ms

50

Maximum switching frequency for a

Ohmic nominal load

Hz

300

Lamp nominal load

Hz

300

Inductive nominal load

1.2 H; 48 Ω

Hz

0.5

Behavior for overload

Automatic restart

Response time for ohmic overload (12 Ω)

s

≈ 3

Restart frequency for ohmic overload

Hz

≈ 400

Restart frequency for lamp overload

Hz

≈ 400

Behavior for inductive overload

Output can be destroyed

Response time upon short-circuit

ms

≈ 400

Reverse voltage protection from short pulses

Reverse voltage protection

Resistance to permanently generated reverse voltage

A

≤ 2

Resistance to the polarity of the supply voltage

Protection elements of the bus coupler or the feed module

Resistance to permanently generated overload

No

Validity of the output data after switching on the 24 V supply voltage (power up)

Typ. 5 ms

Behavior when the voltage is deactivated (power down)

The output follows the power supply without delay

Limited inductive cut-off voltage

-15 V ≤ UDemag ≤ -46 V (UDemag = demagnetization voltage)

Unique maximum energy when free-wheeling

mJ

≤ 400

Type of external protection circuit

Integrated 45-V-Z diode in the output chip

Overcurrent cutoff

A

≥ 0.7

Output current in deactivated state

μA

≤ 300

Output voltage in deactivated state

V

≤ 2

Output current upon overvoltage in deactivated state

mA

≤ 25

Switching capacity upon overvoltage

Typ. 100 MW at 1 kΩ load resistance

Activation current for lamp load

Max. 1.5 A for 20 ms

Overload/short-circuit protection in the segment circuit

Electronic; via two 4-channel drivers

Overvoltage/reverse polarity protection supply voltage

Protective elements of the feed module; protection up to 33 V DC; the supply voltage must be fused. The power supply unit should be able to provide four times the nominal current of the fuse.
1) For switching frequencies up to 8 Hz; above this frequency, the lamp load responds like an ohmic load

Power dissipation

Formula for calculating the power dissipation in the electronics

technical illustration-R911170756-Inline connector

where:

PEL

Total power dissipation in the module

n

Number of set outputs (n = 1 to 8)

i

Running index

ILi

Load current of output i

Restriction of simultaneity, derating

Type

R-IB IL 24 DO 8-PAC

Derating

No restriction of simultaneity, no derating

Electrical isolation/insulation of the voltage ranges

Type

R-IB IL 24 DO 8-PAC

Common potentials

24 V main voltage UM, 24 V segment voltage US and GND are on the same potential. FE represents a separate potential area.

Separate potentials in the system of bus coupler/feed module and I/O module

Test distance

Test voltage

5 V supply incoming remote bus/7.5 V supply (bus logic)

500 V AC, 50 Hz, 1 min.

5 V supply to further remote bus/7.5 V supply (bus logic)

500 V AC, 50 Hz, 1 min.

7.5 V supply (bus logic)/24 V supply (peripherals)

500 V AC, 50 Hz, 1 min.

24 V supply (peripherals)/function earth

500 V AC, 50 Hz, 1 min.

Error messages to the higher-level control or computer system

Type

R-IB IL 24 DO 8-PAC

Error message

Short-circuit/overload of an output
Under or over the operating voltage

Approvals

The current approvals can be found at www.boschrexroth.com.

technical illustration-R911170756-Inline connector

Dimensions

Type

R-IB IL 24 DO 8-PAC

A

mm

48.8

B

mm

120

C

mm

71.5

Note on dimensions

The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715).