You are using an outdated browser. For a faster, safer browsing experience, upgrade for free today.

BOSCH REXROTH
R911170431


$833.78 USD
  • BOSCH REXROTH
  • Material:R911170431
  • Model:R-IBILTEMP2UTH-PAC

Quantity in stock: 0

Note: Sales tax, and shipping will be calculated at checkout.
***Disclaimer: The following summary contains information gathered from various sources such as product descriptions, technical specifications and catalogs. While efforts have been made to provide accurate details, inaccuracies may occur. It is advised to verify all information by contacting Bosch Rexroth directly.***
The Bosch Rexroth R-IB IL TEMP 2 UTH-PAC (R911170431) is a high-quality signal acquisition module designed for precise temperature measurement and monitoring applications. This advanced module is capable of interfacing with conventional thermocouples, showcasing its versatility in supporting various types such as those conforming to DIN EN standards and DIN standards. It is particularly adept at capturing a wide range of temperature signals thanks to its compatibility with different thermocouple types, ensuring that it can cater to diverse industrial requirements. The R-IB IL TEMP 2 UTH-PAC also features a linear voltage input range from 0 mV to 10 mV, which allows for the direct processing of low-level signals from other types of temperature sensors that output within this range. The module's ability to handle both thermocouple and millivolt inputs makes it an indispensable component in systems where precise temperature control and monitoring are critical. Engineered for reliability and accuracy, the R911170431 module exemplifies Bosch Rexroth's commitment to providing sophisticated solutions for complex automation tasks. Its integration into a control system ensures that users can expect consistent performance in their temperature-dependent processes. Whether it's utilized in manufacturing environments, process control settings, or any application where temperature data acquisition is essential, this module delivers the functionality needed to maintain optimal operational conditions.


Inline connector

The modular, compact equipment configuration of the I/O systems from Rexroth offers you maximum flexibility for the cost-effective implementation of your individual machine concepts. The I/O modules have robust design and mechanics, are easy to use, have a quick reaction time and are quick to install – both in the control cabinet and in the field. Open communication standards allow you perfect integration of the I/O modules with maximum availability.

Unpacked Weight: 0.094 kg

This module can be used to acquire signals from conventional thermocouples. It supports 13 different types of DIN EN 60584-1 and DIN 43710 thermocouples, as well as a linear voltage input of -15 mV to +85 mV.

Air pressure (operation)70-106 kPa (up to 3,000 m above sea level)
Measured value display16 bits (15 bits + sign)
13 bits (12 bits + sign)
16 bits (15 bits + sign)
Supported sensor typesB, C, E, J, K, L, N, R, S, T, U, W, HK
Width12.2
Productgroup ID4,6
Height136.8
International protection codeIP20
Permissible air humidity (storage)10-95
Permissible air humidity (transport)10-95
Number of channels2
Connection typeZugfederanschluss
Connection techniques2-Leitertechnik
Depth71.5
Weight0.094
Ambient temperature (during operation)-25-55
Ambient temperature (storage and transport)-25-85
Conductor cross-sectionRigid: 0.2-1.5 mm²,Flexible: 0.2-1.5 mm²,AWG: 24 ... 16

General data

Type

R-IB IL TEMP 2 UTH-PAC

Weight 1)

g

67

Operating mode

Process data mode with 2 words

Sensor connection type

2-wire technology

Ambient temperature (operation)

-25 °C ... +55 °C

Ambient temperature (storage/transport)

-25 °C ... +85 °C

Permissible relative humidity (operation)

10 % ... 95 % acc. to DIN EN 61131-2

Permissible relative humidity (storage/transport)

10 % ... 95 % acc. to DIN EN 61131-2

Air pressure (operation)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Air pressure (storage/transport)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Protection type

IP20, IEC 60529

Protection class

III, IEC 61140
1) Including plug

Connection data

Type

R-IB IL TEMP 2 UTH-PAC

Designation

Inline connection plug

Connection type

Tension spring modules

Conductor cross-section solid/flexible/AWG

0.2 mm² ... 1.5 mm²
0.2 mm² ... 1.5 mm²
24 ... 16

Interface local bus

Type

R-IB IL TEMP 2 UTH-PAC

Connection type

Data ranking

Transmission speed

kBit/s

500

Inline potentials/performance balance

Type

R-IB IL TEMP 2 UTH-PAC

Logic voltage UL

V DC

7.5

Typical current consumption from UL

mA

43

Analog supply voltage UANA

V DC

24

Typical current consumption from UANA

mA

11

Typical power consumption total

mW

590

Supply of module electronics and peripherals via bus coupler/power feed module

Type

R-IB IL TEMP 2 UTH-PAC

Connectivity technology

Potential jumpers

Analog inputs

Type

R-IB IL TEMP 2 UTH-PAC

Number of analog inputs 1)

2

Measurement representation

16 bits (15 bits + sign)
13 bits (12 bits + sign)
16 bits (15 bits + sign)
-
-
-

Connectivity technology

2-wire, shielded compensating cable for TC with enclosed sensors

Permissible cable length 2)

m

< 30

Supported sensor types (TC)

B, C, E, J, K, L, N, R, S, T, U, W, HK

Characteristics standards

DIN EN 60584-1: 1995 (B, E, J, K, N, R, S, T) DIN 43710 (U, L)

Voltage input range

-15 mV ... +85 mV

Temperature measurement unit

Optionally either Celsius, Fahrenheit or μV scale

Conversion process for the A/D converter

Successive approximation

Typical conversion time for the A/D converter

µs

120

Process data update 3)

Both channels in 2-wire technology

ms

≤ 30

Limit frequency of the analog filter

Hz

48

Overvoltage protected up to ±40 V

TC channels: Connections 1.2 and 2.2 as well as 1.3 and 2.3
1) For thermocouples or linear voltage
2) With shielded line
3) For both channels

Electrical isolation/insulation of the voltage ranges

Type

R-IB IL TEMP 2 UTH-PAC

Common potentials

24 V main voltage UM, 24 V segment voltage US and GND are on the same potential. FE represents a separate potential area.

Separate potentials in the system of bus coupler/feed module and an analog I/O module

Test distance

Test voltage

5 V supply incoming remote bus/7.5 V supply (bus logic)

500 V AC, 50 Hz, 1 min.

5 V supply to further remote bus/7.5 V supply (bus logic)

500 V AC, 50 Hz, 1 min.

7.5 V supply (bus logic)/24 V supply (peripherals)

500 V AC, 50 Hz, 1 min.

7.5 V power supply (bus logic)/24 V analog power supply (analog peripherals)

500 V AC, 50 Hz, 1 min.

24 V supply (peripherals)/function earth

500 V AC, 50 Hz, 1 min.

24 V analog supply (analog peripherals)/function earth

500 V AC, 50 Hz, 1 min.

Error messages to the higher-level control or computer system

Type

R-IB IL TEMP 2 UTH-PAC

Error message

Failure of the internal voltage supply
Upon failure or undershooting of the logic voltage UL: Peripheral error message to the bus coupler
-
-

Error messages about process data

Error message

Peripheral / user error

Approvals

The current approvals can be found at www.boschrexroth.com.

technical illustration-R911170431-Inline connector

Dimensions

Type

R-IB IL TEMP 2 UTH-PAC

A

mm

12.2

B

mm

136.8

C

mm

71.5

Note on dimensions

The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715).