You are using an outdated browser. For a faster, safer browsing experience, upgrade for free today.

BOSCH REXROTH
R911170428


$1,319.52 USD
  • BOSCH REXROTH
  • Material:R911170428
  • Model:R-IB IL TEMP 4/8 RTD-PAC

Quantity in stock: 0

Note: Sales tax, and shipping will be calculated at checkout.
***Disclaimer: The following summary contains information gathered from various sources such as product descriptions, technical specifications and catalogs. While efforts have been made to provide accurate details, inaccuracies may occur. It is advised to verify all information by contacting Bosch Rexroth directly.***
The Bosch Rexroth R-IB IL TEMP 4/8 RTD-PAC (R911170428) is a highly precise and versatile analog input module designed for integration into a Rexroth Inline station. This specific module offers four to eight channels for reading temperatures through resistive temperature detectors (RTDs), making it an essential component for industrial automation systems that require accurate temperature monitoring and control. The R-IB IL TEMP 4/8 RTD-PAC supports three linear resistance ranges, catering to a variety of resistive temperature sensors. This module utilizes a wire connection technique to ensure secure and reliable communication with RTDs. It is engineered to streamline the temperature sensing process, which is crucial in maintaining optimal conditions in various applications. The provided accessories, including a connection plug and labeling field, facilitate easy installation and maintenance, while also promoting clear identification within complex systems. The R-IB IL TEMP 4/8 RTD-PAC's capability to interface with multiple sensor types makes it an adaptable solution for different thermal measurement needs. Its precision in reading resistance changes translates into accurate temperature data, which is vital for processes where temperature plays a critical role in product quality or safety. The module's robust design ensures consistent performance even in demanding industrial environments.


Inline connector

The modular, compact equipment configuration of the I/O systems from Rexroth offers you maximum flexibility for the cost-effective implementation of your individual machine concepts. The I/O modules have robust design and mechanics, are easy to use, have a quick reaction time and are quick to install – both in the control cabinet and in the field. Open communication standards allow you perfect integration of the I/O modules with maximum availability.

Unpacked Weight: 0.26 kg

This module is designed for use within a Rexroth Inline station. This module provides you with an 8-channel input module with three linear resistance ranges for resistive temperature sensors.

Air pressure (operation)70-106 kPa (up to 3,000 m above sea level)
Supported sensor typesPt, Ni, Cu, KTY, lineare Widerstände
Width48.8
Productgroup ID4,6
Height136.8
International protection codeIP20
Permissible air humidity (storage)10-95
Permissible air humidity (transport)10-95
Number of channels8
Connection typeZugfederanschluss
Connection techniques4-Leitertechnik
Depth72
Weight0.26
Ambient temperature (during operation)-25-60
Ambient temperature (storage and transport)-25-85
Conductor cross-sectionRigid: 0.08-0.5 mm²,Flexible: 0.08-0.5 mm²,AWG: 28 ... 16

General data

Type

R-IB IL TEMP 4/8 RTD-EF-PAC

Color

Green

Weight 1)

g

190

Operating mode

Process data operation with 5 words/1 word PCP

Sensor connection type

4-wire technology

Ambient temperature (operation)

-25 °C ... +60 °C

Ambient temperature (storage/transport)

-25 °C ... +85 °C

Permissible relative humidity (operation)

10 % ... 95 % acc. to DIN EN 61131-2

Permissible relative humidity (storage/transport)

10 % ... 95 % acc. to DIN EN 61131-2

Air pressure (operation)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Air pressure (storage/transport)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Protection type

IP20, IEC 60529

Protection class

III, IEC 61140, EN 61140, VDE 0140-1
1) Including plug

Connection data

Type

R-IB IL TEMP 4/8 RTD-EF-PAC

Designation

Inline connection plug

Connection type

Spring-cage connection

Conductor cross-section solid/flexible/AWG

0.08 mm² ... 1.5 mm²
0.08 mm² ... 1.5 mm²
28 ... 16

Interface local bus

Type

R-IB IL TEMP 4/8 RTD-EF-PAC

Connection type

Inline data jumper

Transmission speed

kBit/s

500

Inline potentials/performance balance

Type

R-IB IL TEMP 4/8 RTD-EF-PAC

Logic voltage UL

V

7.5

Typical current consumption from UL

mA

95

Peripheral supply voltage UANA

V DC

24

Typical current consumption from UANA

mA

6

Typical power consumption total

W

0.85

Supply of module electronics and peripherals via bus coupler/power feed module

Type

R-IB IL TEMP 4/8 RTD-EF-PAC

Connectivity technology

Potential jumpers

Analog inputs

Type

R-IB IL TEMP 4/8 RTD-EF-PAC

Number of analog inputs 1)

8

Resolution of the A/D converter

bits

24

Measurement representation

16 bits (15 bits + sign)
-
-
-
-
-

Measurement representation

Standardized for

Degrees Celsius (°C), degrees Fahrenheit (°F) and linear resistance in ohms (Ω)

Resolution (quantization)

In the °C range

0.1 K/LSB (factory setting); 0.01 K/LSB

In the °F range

0.1 °F/LSB; 0.01 °F/LSB

In the linear Ω range

0.01 Ω/LSB; 0.1 Ω/LSB; 1 Ω/LSB

Connectivity technology

4-wire, shielded sensor line (e.g. LiYCY (TP))

Permissible cable length 2)

m

250

Crosstalk attenuation

Typ. 98.6 dB (channel/channel, external Pt100 connection, resolution 0.01 K/LSB)
Typ. 100 dB (channel/channel, sensor type RLin500, resolution 0.01 Ω/LSB)
Typ. 88 dB (channel/channel, sensor type RLin5000, resolution 0.1 Ω/LSB)

Supported sensor types (RTD)

Pt, Ni, Cu, KTY, linear resistors

Characteristics standards

DIN EN 60751: 07/1996 / SAMA RC 21-4-1966

Process data update

Depending on the filter time

Differential non-linearity

Typ. 1 ppm/±0.0001 % (in all areas)

Integral non-linearity

Typ. 30 ppm/±0.003 % (Pt100)
Typ. 20 ppm/±0.002 % (RLin 500 Ω)
Typ. 200 ppm/±0.02 % (RLin 5000 Ω)
1) 4-wire RTD for resistive temperature sensors
2) 4-wire connection with LiYCY (TP) 2 x 2 x 0.5 mm²

Conformity

Type

R-IB IL TEMP 4/8 RTD-EF-PAC

Conforms with

Testing of interference immunity acc. to EN 61000-6-2

Electro-magnetic fields

Criterion A; level: 10 V/m; additional tolerance of the measurement range end value: < 0.1 % acc. to EN 61000-4-3/IEC 61000-4-3

Fast transients (burst)

Criterion A; level: 1.1 kV acc. to EN 61000-4-4/IEC 61000-4-4

Line-fed disturbances

Criterion A; level: 150 kHz ... 80 MHz, test voltage 10 V, 80 % AM (1 kHz) acc. to EN 61000-4-6/IEC 61000-4-6

Line-fed disturbances (ODS)

Criterion A; level: 150 kHz ... 300 MHz, test voltage 30 V, 80 % AM (1 kHz) acc. to EN 61000-4-6/IEC 61000-4-6

Protective devices

Type

R-IB IL TEMP 4/8 RTD-EF-PAC

Transient protection of the inputs

Yes

Sensor supply voltage

Yes

Electrical isolation/insulation of the voltage ranges

Type

R-IB IL TEMP 4/8 RTD-EF-PAC

For the potential separation of the logic layer from the peripheral area, it is necessary to use separate power supplies when supplying the station's bus coupler and the sensors that are connected to the analog input terminal described here. A connection to the supply units in the 24 V range is not allowed.

Common potentials

24 V main voltage, 24 V segment voltage and GND are on the same potential. FE represents a separate potential area.

Separate potentials in the system of bus coupler/feed module and I/O module

Test distance

Test voltage

5 V supply incoming remote bus/7.5 V supply (bus logic)

500 V AC, 50 Hz, 1 min.

5 V supply to further remote bus/7.5 V supply (bus logic)

500 V AC, 50 Hz, 1 min.

7.5 V supply (bus logic), 24 V supply UANA/peripherals

500 V AC, 50 Hz, 1 min.

7.5 V supply (bus logic), 24 V supply UANA/function earth

500 V AC, 50 Hz, 1 min.

Peripherals/function earth

500 V AC, 50 Hz, 1 min.

Error messages to the higher-level control or computer system

Type

R-IB IL TEMP 4/8 RTD-EF-PAC

Error message

Failure of the internal, galvanically-isolated peripheral voltage supply
Failure or undershooting of the logic voltage UL
-
-

Error messages about process data

Error message

Peripheral / user error

Approvals

The current approvals can be found at www.boschrexroth.com.

technical illustration-R911170428-Inline connector

Dimensions

Type

R-IB IL TEMP 4/8 RTD-EF-PAC

A

mm

48.8

B

mm

136.8

C

mm

72

Note on dimensions

The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715).