BOSCH REXROTH
R911170426
$1,382.44 USD
- BOSCH REXROTH
- Material:R911170426
- Model:R-IB IL AI 4/EF-PAC
Quantity in stock: 0
The Bosch Rexroth R-IB IL AI 4/EF-PAC (R911170426) is an advanced analog input module designed for seamless integration within an Inline station. This high-precision module specializes in the acquisition of analog voltage or current signals, providing a versatile solution for various automation tasks. The unit features differential input channels that can handle a range of inputs including ...mA to ...mA, mA; as well as ...V to V, ...V, and V levels, accommodating a broad spectrum of signal requirements. The module's connection capabilities are robust, offering both 2-wire and 3-wire connection options to ensure compatibility with different sensor types and configurations. This flexibility makes it suitable for diverse application scenarios where precise signal processing is critical. The R-IB IL AI 4/EF-PAC comes complete with necessary accessories such as a connection plug and a labeling field, which simplifies installation and maintenance processes. Designed with practicality in mind, this input module boasts protection type IP20, ensuring it is safeguarded against touch by fingers and objects greater than 12 millimeters but not protected against water. This level of protection is appropriate for indoor use where exposure to moisture is not a concern. In summary, the Bosch Rexroth R-IB IL AI 4/EF-PAC (R911170426) stands out as an essential component for industrial automation systems requiring accurate and reliable analog signal acquisition. Its compatibility with various signal ranges, ease of installation, and protective features make it an indispensable tool for ensuring operational efficiency in complex automated environments.
Inline connector
The modular, compact equipment configuration of the I/O systems from Rexroth offers you maximum flexibility for the cost-effective implementation of your individual machine concepts. The I/O modules have robust design and mechanics, are easy to use, have a quick reaction time and are quick to install – both in the control cabinet and in the field. Open communication standards allow you perfect integration of the I/O modules with maximum availability.
Unpacked Weight: 0.254 kg
This module is designed for use within an Inline station. It is used to acquire analog voltage or current signals.
| Data Sheet | Download Data Sheet |
| 3D CAD | Download 3D CAD |
| Manual | Download Manual |
| Air pressure (operation) | 70-106 kPa (up to 3,000 m above sea level) |
| Width | 48.8 |
| Productgroup ID | 4,6 |
| Height | 136.8 |
| International protection code | IP20 |
| Permissible air humidity (storage) | 10-95 |
| Permissible air humidity (transport) | 10-95 |
| A/D conversion time | 10 |
| Voltage input signal | 0-10 V; ±10 V; 0-5 V; ±5 V |
| Number of channels | 4 |
| Current input signal | 0-20 mA; ±20 mA 4-20 mA |
| Resolution A/D | 16 Bit |
| Connection type | Tension spring modules |
| Connectivity technology | 2-, 3-, 4-wire technology (shielded) |
| Depth | 72 |
| Weight | 0.254 |
| Ambient temperature (during operation) | -25-55 |
| Ambient temperature (storage and transport) | -25-85 |
| Conductor cross-section | Rigid: 0.08-0.5 mm²,Flexible: 0.08-0.5 mm²,AWG: 28 ... 16 |
General data
|
Type |
R-IB IL AI 4/EF-PAC | |
|
Weight 1) |
g |
210 |
|
Operating mode |
Process data operation with 5 words/1 word PCP | |
|
Sensor connection type |
2-, 3-, 4-wire technology (shielded) | |
|
Ambient temperature (operation) |
-25 °C ... +55 °C | |
|
Ambient temperature (storage/transport) |
-25 °C ... +85 °C | |
|
Permissible relative humidity (operation) |
10 % ... 95 % acc. to DIN EN 61131-2 | |
|
Permissible relative humidity (storage/transport) |
10 % ... 95 % acc. to DIN EN 61131-2 | |
|
Air pressure (operation) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
|
Air pressure (storage/transport) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
|
Protection type |
IP20, IEC 60529 | |
|
Protection class |
III, VDE 0106, IEC 60536 | |
| 1) | Including plug |
Connection data
|
Type |
R-IB IL AI 4/EF-PAC | |
|
Designation |
Inline connection plug | |
|
Connection type |
Tension spring modules | |
|
Conductor cross-section solid/flexible/AWG |
0.08 mm² ... 1.5 mm² 0.08 mm² ... 1.5 mm² 28 ... 16 |
|
Interface local bus
|
Type |
R-IB IL AI 4/EF-PAC | |
|
Connection type |
Data ranking | |
|
Transmission speed |
kBit/s |
500 |
Inline potentials/performance balance
|
Type |
R-IB IL AI 4/EF-PAC | |
|
Logic voltage UL |
V DC |
7.5 |
|
Typical current consumption from UL |
mA |
85 |
|
Maximum current consumption from UL |
mA |
100 |
|
Peripheral supply voltage UANA |
V DC |
24 |
|
Typical current consumption from UANA |
mA |
13 |
|
Maximum current consumption from UANA |
mA |
20 |
|
Typical power consumption total |
mW |
950 |
|
Maximum power consumption total |
mW |
1250 |
Supply of module electronics and peripherals via bus coupler/power feed module
|
Type |
R-IB IL AI 4/EF-PAC | |
|
Connectivity technology |
Potential jumpers | |
Sensor supply voltage UIS via feed from UM
|
Type |
R-IB IL AI 4/EF-PAC | |
|
Nominal value UIS |
V DC |
24 |
|
Nominal current IIS per channel |
mA |
50 |
|
Guarantee |
Internal, channel electronic fuse, short-circuit protected with single-channel diagnostics - - - |
|
|
Short-circuit protection |
Short-circuit protection with electronic fuse | |
Analog inputs
|
Type |
R-IB IL AI 4/EF-PAC | |
|
Number of analog inputs 1) |
4 | |
|
A/D conversion time |
µs |
≤ 10 |
|
Limit frequency (3 dB) |
Hz |
500 |
|
Measurement representation |
16 bits (15 bits + sign) 13 bits (12 bits + sign) 16 bits (15 bits + sign) 16 bits (15 bits + sign) - - |
|
|
Data formats |
IB IL, IB ST, S7-compatible, standardized representation | |
|
Average |
None or averaged over 4, 16 or 32 measured valuesdefault setting: 16 measured values | |
|
Process data update |
ms |
< 1 |
|
Bus synchronicity |
Yes | |
|
Transient protection of the inputs |
Via diverter | |
| 1) | Analog differential inputs |
Differential inputs, voltage
|
Type |
R-IB IL AI 4/EF-PAC | |
|
Number of inputs |
4 | |
|
Voltage input signal |
0 V … 10 V; ±10 V 0 V … 5 V; ±5 V - - |
|
|
Typical input resistance voltage input |
kΩ |
≈ 300 |
|
Open circiut response |
Goes to 0 V | |
|
Common-mode voltage range signal ‒ ground |
-50 V DC … 50 V DC | |
Differential inputs, current
|
Type |
R-IB IL AI 4/EF-PAC | |
|
Number of inputs |
4 | |
|
Current input signal |
0 mA … 20 mA; ±20 mA 4 mA … 20 mA - |
|
|
Typical input resistance power input 1) |
Ω |
≈ 110 |
|
Open circiut response |
Goes to 0 mA | |
|
Maximum overload protection |
Overload protected; max. ±30 V DC | |
| 1) | Measuring resistance |
Mechanical tests
|
Type |
R-IB IL AI 4/EF-PAC | |
|
Shock 1) |
Load 15 g for 11 ms, half sinusoidal wave, three shocks per spatial direction and orientationLoad 25 g for 6 ms, half sinusoidal wave, three shocks per spatial direction and orientation acc. to EN 60068-2-27/IEC 60068-2-27 | |
| 1) | Deviations compared to the common technical data given in the application description DOK-CONTRL-ILSYSPRO***-AW..-DE-P |
Conformity
|
Type |
R-IB IL AI 4/EF-PAC | ||
|
Conforms with |
|||
|
Testing of interference immunity acc. to EN 61000-6-2 1) |
Discharge of static electricity (ESD) |
Criterion B; 6 kV contact discharge; 8 kV air discharge acc. to EN 61000-4-2/IEC 61000-4-2 | |
| 1) | Deviations compared to the common technical data given in the application description DOK-CONTRL-ILSYSPRO***-AW..-DE-P |
Tolerance and temperature behavior of the inputs
| Tolerance absolute, typical | Tolerance absolute, maximum | Tolerance relative, typical | Tolerance relative, maximum | |||
|
TU = 25 °C |
||||||
|
Measurement range |
0 V ... 5 V ±5 V |
± 2.5 mV | ± 7.5 mV | ± 0.05 % | ± 0.15 % | |
|
0 V ... 10 V ±10 V |
± 2.5 mV | ± 10 mV | ± 0.025 % | ± 0.1 % | ||
|
0 mA ... 20 mA 4 mA ... 20 mA±20 mA |
± 14 μA | ± 40 μA | ± 0.07 % | ± 0.2 % | ||
|
TU = -25 °C … +55 °C |
||||||
|
Measurement range |
0 V ... 5 V ±5 V |
± 9 mV | ± 20 mV | ± 0.18 % | ± 0.4 % | |
|
0 V ... 10 V ±10 V |
± 13 mV | ± 30 mV | ± 0.13 % | ± 0.3 % | ||
|
0 mA ... 20 mA 4 mA ... 20 mA±20 mA |
± 22 μA | ± 80 μA | ± 0.11 % | ± 0.4 % | ||
Additional tolerances under the influence of electromagnetic fields
|
Type |
R-IB IL AI 4/EF-PAC | ||
|
Type of electromagnetic interference |
Typical deviation from the measurement range end value ‒ relative |
||
|
Electro-magnetic fields Field strength 10 V/macc. to EN 61000-4-3/IEC 61000-4-3 |
Voltage input |
% |
< ± 1 |
|
Current input |
% |
< ± 1 | |
|
Line-fed disturbances III (test voltage 10 V)acc. to EN 61000-4-6/IEC 61000-4-6 |
Voltage input |
% |
< ± 1 |
|
Current input |
% |
< ± 1 | |
|
Fast transient disturbances (burst) supply 4 kV, input 2 kVacc. to EN 61000-4-4/IEC 61000-4-4 |
Voltage input |
% |
< ± 1 |
|
Current input |
% |
< ± 1 | |
Electrical isolation/insulation of the voltage ranges
|
Type |
R-IB IL AI 4/EF-PAC | |
|
Common potentials |
||
|
24 V main voltage UM, 24 V segment voltage US and GND are on the same potential. FE represents a separate potential area. |
||
|
Separate potentials in the system of bus coupler/feed module and I/O module |
||
|
Test distance |
Test voltage | |
|
7.5 V supply (bus logic), 24 V supply UANA/analog peripherals |
500 V AC, 50 Hz, 1 min. | |
|
7.5 V supply (bus logic), 24 V supply UANA/function earth |
500 V AC, 50 Hz, 1 min. | |
|
Analog peripherals/function earth |
500 V AC, 50 Hz, 1 min. | |
Error messages to the higher-level control or computer system
|
Type |
R-IB IL AI 4/EF-PAC | |
|
Error message |
Upon failure of the internal peripheral voltage supply: Peripheral error message to the bus coupler Upon failure or undershooting of the logic voltage UL: Peripheral error message to the bus coupler Upon peripheral / user error: Error signal via input process data |
|
|
Approvals |
|
The current approvals can be found at www.boschrexroth.com. |
Dimensions
|
Type |
R-IB IL AI 4/EF-PAC | |
|
A |
mm |
48.8 |
|
B |
mm |
136.8 |
|
C |
mm |
72 |
|
Note on dimensions |
The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715). | |