***Disclaimer: The following summary contains information gathered from various sources such as product descriptions, technical specifications and catalogs. While efforts have been made to provide accurate details, inaccuracies may occur. It is advised to verify all information by contacting Bosch Rexroth directly.***
The Bosch Rexroth R-IB IL AI 4/EF-PAC (R911170426) is an advanced analog input module designed for seamless integration within an Inline station. This high-precision module specializes in the acquisition of analog voltage or current signals, providing a versatile solution for various automation tasks. The unit features differential input channels that can handle a range of inputs including ...mA to ...mA, mA; as well as ...V to V, ...V, and V levels, accommodating a broad spectrum of signal requirements. The module's connection capabilities are robust, offering both 2-wire and 3-wire connection options to ensure compatibility with different sensor types and configurations. This flexibility makes it suitable for diverse application scenarios where precise signal processing is critical. The R-IB IL AI 4/EF-PAC comes complete with necessary accessories such as a connection plug and a labeling field, which simplifies installation and maintenance processes. Designed with practicality in mind, this input module boasts protection type IP20, ensuring it is safeguarded against touch by fingers and objects greater than 12 millimeters but not protected against water. This level of protection is appropriate for indoor use where exposure to moisture is not a concern. In summary, the Bosch Rexroth R-IB IL AI 4/EF-PAC (R911170426) stands out as an essential component for industrial automation systems requiring accurate and reliable analog signal acquisition. Its compatibility with various signal ranges, ease of installation, and protective features make it an indispensable tool for ensuring operational efficiency in complex automated environments.


Inline connector

The modular, compact equipment configuration of the I/O systems from Rexroth offers you maximum flexibility for the cost-effective implementation of your individual machine concepts. The I/O modules have robust design and mechanics, are easy to use, have a quick reaction time and are quick to install – both in the control cabinet and in the field. Open communication standards allow you perfect integration of the I/O modules with maximum availability.

Unpacked Weight: 0.254 kg

This module is designed for use within an Inline station. It is used to acquire analog voltage or current signals.

Air pressure (operation)70-106 kPa (up to 3,000 m above sea level)
Width48.8
Productgroup ID4,6
Height136.8
International protection codeIP20
Permissible air humidity (storage)10-95
Permissible air humidity (transport)10-95
A/D conversion time10
Voltage input signal0-10 V; ±10 V; 0-5 V; ±5 V
Number of channels4
Current input signal0-20 mA; ±20 mA
4-20 mA
Resolution A/D16 Bit
Connection typeTension spring modules
Connectivity technology2-, 3-, 4-wire technology (shielded)
Depth72
Weight0.254
Ambient temperature (during operation)-25-55
Ambient temperature (storage and transport)-25-85
Conductor cross-sectionRigid: 0.08-0.5 mm²,Flexible: 0.08-0.5 mm²,AWG: 28 ... 16

General data

Type

R-IB IL AI 4/EF-PAC

Weight 1)

g

210

Operating mode

Process data operation with 5 words/1 word PCP

Sensor connection type

2-, 3-, 4-wire technology (shielded)

Ambient temperature (operation)

-25 °C ... +55 °C

Ambient temperature (storage/transport)

-25 °C ... +85 °C

Permissible relative humidity (operation)

10 % ... 95 % acc. to DIN EN 61131-2

Permissible relative humidity (storage/transport)

10 % ... 95 % acc. to DIN EN 61131-2

Air pressure (operation)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Air pressure (storage/transport)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Protection type

IP20, IEC 60529

Protection class

III, VDE 0106, IEC 60536
1) Including plug

Connection data

Type

R-IB IL AI 4/EF-PAC

Designation

Inline connection plug

Connection type

Tension spring modules

Conductor cross-section solid/flexible/AWG

0.08 mm² ... 1.5 mm²
0.08 mm² ... 1.5 mm²
28 ... 16

Interface local bus

Type

R-IB IL AI 4/EF-PAC

Connection type

Data ranking

Transmission speed

kBit/s

500

Inline potentials/performance balance

Type

R-IB IL AI 4/EF-PAC

Logic voltage UL

V DC

7.5

Typical current consumption from UL

mA

85

Maximum current consumption from UL

mA

100

Peripheral supply voltage UANA

V DC

24

Typical current consumption from UANA

mA

13

Maximum current consumption from UANA

mA

20

Typical power consumption total

mW

950

Maximum power consumption total

mW

1250

Supply of module electronics and peripherals via bus coupler/power feed module

Type

R-IB IL AI 4/EF-PAC

Connectivity technology

Potential jumpers

Sensor supply voltage UIS via feed from UM

Type

R-IB IL AI 4/EF-PAC

Nominal value UIS

V DC

24

Nominal current IIS per channel

mA

50

Guarantee

Internal, channel electronic fuse, short-circuit protected with single-channel diagnostics
-
-
-

Short-circuit protection

Short-circuit protection with electronic fuse

Analog inputs

Type

R-IB IL AI 4/EF-PAC

Number of analog inputs 1)

4

A/D conversion time

µs

≤ 10

Limit frequency (3 dB)

Hz

500

Measurement representation

16 bits (15 bits + sign)
13 bits (12 bits + sign)
16 bits (15 bits + sign)
16 bits (15 bits + sign)
-
-

Data formats

IB IL, IB ST, S7-compatible, standardized representation

Average

None or averaged over 4, 16 or 32 measured valuesdefault setting: 16 measured values

Process data update

ms

< 1

Bus synchronicity

Yes

Transient protection of the inputs

Via diverter
1) Analog differential inputs

Differential inputs, voltage

Type

R-IB IL AI 4/EF-PAC

Number of inputs

4

Voltage input signal

0 V … 10 V; ±10 V
0 V … 5 V; ±5 V
-
-

Typical input resistance voltage input

≈ 300

Open circiut response

Goes to 0 V

Common-mode voltage range signal ‒ ground

-50 V DC … 50 V DC

Differential inputs, current

Type

R-IB IL AI 4/EF-PAC

Number of inputs

4

Current input signal

0 mA … 20 mA; ±20 mA
4 mA … 20 mA
-

Typical input resistance power input 1)

Ω

≈ 110

Open circiut response

Goes to 0 mA

Maximum overload protection

Overload protected; max. ±30 V DC
1) Measuring resistance

Mechanical tests

Type

R-IB IL AI 4/EF-PAC

Shock 1)

Load 15 g for 11 ms, half sinusoidal wave, three shocks per spatial direction and orientationLoad 25 g for 6 ms, half sinusoidal wave, three shocks per spatial direction and orientation acc. to EN 60068-2-27/IEC 60068-2-27
1) Deviations compared to the common technical data given in the application description DOK-CONTRL-ILSYSPRO***-AW..-DE-P

Conformity

Type

R-IB IL AI 4/EF-PAC

Conforms with

Testing of interference immunity acc. to EN 61000-6-2 1)

Discharge of static electricity (ESD)

Criterion B; 6 kV contact discharge; 8 kV air discharge acc. to EN 61000-4-2/IEC 61000-4-2
1) Deviations compared to the common technical data given in the application description DOK-CONTRL-ILSYSPRO***-AW..-DE-P

Tolerance and temperature behavior of the inputs

Tolerance absolute, typical Tolerance absolute, maximum Tolerance relative, typical Tolerance relative, maximum

TU = 25 °C

Measurement range

0 V ... 5 V ±5 V

± 2.5 mV ± 7.5 mV ± 0.05 % ± 0.15 %

0 V ... 10 V ±10 V

± 2.5 mV ± 10 mV ± 0.025 % ± 0.1 %

0 mA ... 20 mA

4 mA ... 20 mA±20 mA
± 14 μA ± 40 μA ± 0.07 % ± 0.2 %

TU = -25 °C … +55 °C

Measurement range

0 V ... 5 V ±5 V

± 9 mV ± 20 mV ± 0.18 % ± 0.4 %

0 V ... 10 V ±10 V

± 13 mV ± 30 mV ± 0.13 % ± 0.3 %

0 mA ... 20 mA

4 mA ... 20 mA±20 mA
± 22 μA ± 80 μA ± 0.11 % ± 0.4 %

Additional tolerances under the influence of electromagnetic fields

Type

R-IB IL AI 4/EF-PAC

Type of electromagnetic interference

Typical deviation from the measurement range end value ‒ relative

Electro-magnetic fields

Field strength 10 V/macc. to EN 61000-4-3/IEC 61000-4-3

Voltage input

%

< ± 1

Current input

%

< ± 1

Line-fed disturbances

III (test voltage 10 V)acc. to EN 61000-4-6/IEC 61000-4-6

Voltage input

%

< ± 1

Current input

%

< ± 1

Fast transient disturbances (burst)

supply 4 kV, input 2 kVacc. to EN 61000-4-4/IEC 61000-4-4

Voltage input

%

< ± 1

Current input

%

< ± 1

Electrical isolation/insulation of the voltage ranges

Type

R-IB IL AI 4/EF-PAC

Common potentials

24 V main voltage UM, 24 V segment voltage US and GND are on the same potential. FE represents a separate potential area.

Separate potentials in the system of bus coupler/feed module and I/O module

Test distance

Test voltage

7.5 V supply (bus logic), 24 V supply UANA/analog peripherals

500 V AC, 50 Hz, 1 min.

7.5 V supply (bus logic), 24 V supply UANA/function earth

500 V AC, 50 Hz, 1 min.

Analog peripherals/function earth

500 V AC, 50 Hz, 1 min.

Error messages to the higher-level control or computer system

Type

R-IB IL AI 4/EF-PAC

Error message

Upon failure of the internal peripheral voltage supply: Peripheral error message to the bus coupler
Upon failure or undershooting of the logic voltage UL: Peripheral error message to the bus coupler
Upon peripheral / user error: Error signal via input process data

Approvals

The current approvals can be found at www.boschrexroth.com.

technical illustration-R911170426-Inline connector

Dimensions

Type

R-IB IL AI 4/EF-PAC

A

mm

48.8

B

mm

136.8

C

mm

72

Note on dimensions