BOSCH REXROTH
R911170411
$832.85 USD
- BOSCH REXROTH
- Material:R911170411
- Model:R-IB IL 24 DO 32/HD-NPN-PAC
Quantity in stock: 0
The Bosch Rexroth R-IB IL 24 DO 32/HD-NPN-PAC (R911170411) is a robust digital output module designed to be integrated within an Inline station for the purpose of outputting digital signals. This particular model is engineered to deliver high-density performance with 32 NPN switching outputs, making it a suitable choice for complex automation tasks that require a significant number of control signals. The module operates with a voltage output of VDC and can handle current in mA, ensuring compatibility with a wide range of industrial equipment and sensors. The R-IB IL 24 DO 32/HD-NPN-PAC features an efficient connection plug system and comes equipped with labeling fields, which simplifies installation and maintenance processes by allowing for clear and easy identification of connections. The utilization of NPN switching wire connection technique ensures reliable operation in various applications, including but not limited to automated manufacturing processes, conveyor systems, and other machinery that requires precise control over digital outputs. Designed to meet the high standards of quality and reliability associated with Bosch Rexroth products, this digital output module is an essential component for users looking to enhance the functionality and efficiency of their automation systems. Its ability to seamlessly integrate into existing Inline stations further adds to its versatility, making it a valuable addition to any industrial control system requiring high-density digital signal output capabilities.
Inline connector
The modular, compact equipment configuration of the I/O systems from Rexroth offers you maximum flexibility for the cost-effective implementation of your individual machine concepts. The I/O modules have robust design and mechanics, are easy to use, have a quick reaction time and are quick to install – both in the control cabinet and in the field. Open communication standards allow you perfect integration of the I/O modules with maximum availability.
Unpacked Weight: 0.215 kg
This module is designed for use within an Inline station. It is used to output digital signals.
| Data Sheet | Download Data Sheet |
| Manual | Download Manual |
| Total current | 8 |
| Width | 48.8 |
| Productgroup ID | 4,6 |
| Overload-/ short circuit protection in the segment circuit | Electronic; by 16 2-channel drivers |
| Height | 120 |
| International protection code | IP20 |
| Permissible air humidity (storage) | 10-95 |
| Permissible air humidity (transport) | 10-95 |
| Number of channels | 32 |
| Connection type | Zugfederanschluss |
| Connection techniques | 1-Leitertechnik |
| Depth | 71.5 |
| Weight | 0.215 |
| Ambient temperature (during operation) | -25-55 |
| Ambient temperature (storage and transport) | -25-85 |
| Conductor cross-section | Rigid: 0.08-0.5 mm²,Flexible: 0.08-0.5 mm²,AWG: 28 ... 16 |
General data
|
Type |
R-IB IL 24 DO 32/HD-NPN-PAC | |
|
Weight 1) |
g |
195 |
|
Operating mode |
Process data operation with 4 bytes | |
|
Actuator connection type |
1-wire technology | |
|
Ambient temperature (operation) |
-25 °C ... +55 °C | |
|
Ambient temperature (storage/transport) |
-25 °C ... +85 °C | |
|
Permissible relative humidity (operation) |
10 % ... 95 % acc. to DIN EN 61131-2 | |
|
Permissible relative humidity (storage/transport) |
10 % ... 95 % acc. to DIN EN 61131-2 | |
|
Air pressure (storage/transport) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
|
Protection type |
IP20, IEC 60529 | |
|
Protection class |
III, VDE 0106, IEC 60536 | |
| 1) | Including plug |
Connection data
|
Type |
R-IB IL 24 DO 32/HD-NPN-PAC | |
|
Designation |
Inline connection plug | |
|
Connection type |
Tension spring modules | |
|
Conductor cross-section solid/flexible/AWG |
0.08 mm² ... 1.5 mm² 0.08 mm² ... 1.5 mm² 28 ... 16 |
|
Interface local bus
|
Type |
R-IB IL 24 DO 32/HD-NPN-PAC | |
|
Connection type |
Data ranking | |
|
Transmission speed |
kBit/s |
500 |
Supply of module electronics and peripherals via bus coupler/power feed module
|
Type |
R-IB IL 24 DO 32/HD-NPN-PAC | |
|
Connectivity technology |
Potential jumpers | |
Inline potentials/performance balance
|
Type |
R-IB IL 24 DO 32/HD-NPN-PAC | |
|
Logic voltage |
V DC |
7.5 |
|
Maximum current consumption from UL |
mA |
140 |
|
Maximum power consumption from UL |
W |
1.05 |
|
Segment supply voltage US |
V DC |
24 |
|
Nominal current consumption from US |
≤8 A (16 x 0.5 A/32 x 0.25 A) | |
Digital outputs
|
Type |
R-IB IL 24 DO 32/HD-NPN-PAC | |||
|
Number of digital outputs |
32 | |||
|
Nominal output voltage UOut |
V DC |
24 | ||
|
Differential voltage at INenn |
V |
≤ 1 | ||
|
Nominal current INenn each channel |
A |
0.5 | ||
|
Nominal current tolerance |
% |
+ 10 | ||
|
Total current |
A |
8 | ||
|
Nominal load |
Ohmic |
48 Ω |
W |
12 |
|
Lamps |
W |
12 | ||
|
Inductance |
1.2 H; 50 Ω |
VA |
12 | |
|
Typical signal delay upon activating a |
Ohmic nominal load |
µs |
500 | |
|
Lamp nominal load 1) |
ms |
100 | ||
|
Inductive nominal load |
1.2 H; 50 Ω |
ms |
100 | |
|
Typical signal delay upon deactivating a |
Ohmic nominal load |
ms |
1 | |
|
Lamp nominal load |
ms |
1 | ||
|
Inductive nominal load |
1.2 H; 50 Ω |
ms |
50 | |
|
Maximum switching frequency for a |
Ohmic nominal load |
Hz |
300 | |
|
Lamp nominal load |
Hz |
8 | ||
|
Inductive nominal load |
1.2 H; 50 Ω |
Hz |
0.5 | |
|
Behavior for overload |
Automatic restart | |||
|
Response time for ohmic overload (12 Ω) |
s |
≈ 3 | ||
|
Restart frequency for ohmic overload |
Hz |
≈ 400 | ||
|
Restart frequency for lamp overload |
Hz |
≈ 400 | ||
|
Behavior for inductive overload |
Output can be destroyed | |||
|
Response time upon short-circuit |
s |
≈ 3 | ||
|
Validity of the output data after switching on the 24 V supply voltage (power up) |
Typ. 5 ms | |||
|
Behavior when the voltage is deactivated (power down) |
The output follows the power supply without delay | |||
|
Limited inductive cut-off voltage |
V |
45 | ||
|
Unique maximum energy when free-wheeling 2) |
mJ |
≤ 100 | ||
|
Type of external protection circuit |
Integrated 45-V-Z diode in the output chip | |||
|
Overcurrent cutoff |
A |
≥ 0.7 | ||
|
Output current in deactivated state |
μA |
≤ 300 | ||
|
Activation current for lamp load |
Max. 1.5 A for 20 ms | |||
|
Overload/short-circuit protection in the segment circuit |
Electronic; via 16 2-channel driver | |||
|
Overvoltage/reverse polarity protection supply voltage |
Protective elements of the feed module; protection up to 33 V DC; the supply voltage must be fused. The power supply unit should be able to provide four times the nominal current of the fuse. | |||
| 1) | For switching frequencies up to 8 Hz; above this frequency, the lamp load responds like an ohmic load |
| 2) | Where applicable, an external free-wheeling circuit or a circuit against inductive switch-off capacities is required |
|
Power dissipation |
|
|
Formula for calculating the power dissipation in the electronics |
|
|
|
|
where: |
|
|
PEL |
Total power dissipation in the module |
|
n |
Number of set outputs (n = 1 to 32) |
|
i |
Running index |
|
ILi |
Load current of output i |
Power dissipation
|
Type |
R-IB IL 24 DO 32/HD-NPN-PAC | |
|
Power dissipation in the housing PHOU 1) |
W |
≤ 2.8 |
| 1) | Within the admissible operating temperature |
Restriction of simultaneity, derating
|
Ambient temperature TU |
-25 °C ≤ TU < +40 °C | +40 °C ≤ TU < +45 °C | +45 °C ≤ TU < +50 °C | +50 °C ≤ TU < +55 °C | |
|
Maximum load current at 100 % simultaneity |
A |
0.25 | 0.21 | 0.18 | 0.15 |
|
Maximum load current at 50 % simultaneity |
A |
0.5 | 0.45 | 0.4 | 0.35 |
Electrical isolation/insulation of the voltage ranges
|
Type |
R-IB IL 24 DO 32/HD-NPN-PAC | |
|
Common potentials |
||
|
24 V main voltage UM, 24 V segment voltage US and GND are on the same potential. FE represents a separate potential area. |
||
|
Separate potentials in the system of bus coupler/feed module and I/O module |
||
|
Test distance |
Test voltage | |
|
5 V supply incoming remote bus/7.5 V supply (bus logic) |
500 V AC, 50 Hz, 1 min. | |
|
5 V supply to further remote bus/7.5 V supply (bus logic) |
500 V AC, 50 Hz, 1 min. | |
|
7.5 V supply (bus logic)/24 V supply (peripherals) |
500 V AC, 50 Hz, 1 min. | |
|
24 V supply (peripherals)/function earth |
500 V AC, 50 Hz, 1 min. | |
Error messages to the higher-level control or computer system
|
Type |
R-IB IL 24 DO 32/HD-NPN-PAC | |
|
Error message |
None | |
|
Approvals |
|
The current approvals can be found at www.boschrexroth.com. |
Dimensions
|
Type |
R-IB IL 24 DO 32/HD-NPN-PAC | |
|
A |
mm |
48.8 |
|
B |
mm |
120 |
|
C |
mm |
71.5 |
|
Note on dimensions |
The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715). | |