You are using an outdated browser. For a faster, safer browsing experience, upgrade for free today.

BOSCH REXROTH
R911170411


$832.85 USD
  • BOSCH REXROTH
  • Material:R911170411
  • Model:R-IB IL 24 DO 32/HD-NPN-PAC

Quantity in stock: 0

Note: Sales tax, and shipping will be calculated at checkout.
***Disclaimer: The following summary contains information gathered from various sources such as product descriptions, technical specifications and catalogs. While efforts have been made to provide accurate details, inaccuracies may occur. It is advised to verify all information by contacting Bosch Rexroth directly.***
The Bosch Rexroth R-IB IL 24 DO 32/HD-NPN-PAC (R911170411) is a robust digital output module designed to be integrated within an Inline station for the purpose of outputting digital signals. This particular model is engineered to deliver high-density performance with 32 NPN switching outputs, making it a suitable choice for complex automation tasks that require a significant number of control signals. The module operates with a voltage output of VDC and can handle current in mA, ensuring compatibility with a wide range of industrial equipment and sensors. The R-IB IL 24 DO 32/HD-NPN-PAC features an efficient connection plug system and comes equipped with labeling fields, which simplifies installation and maintenance processes by allowing for clear and easy identification of connections. The utilization of NPN switching wire connection technique ensures reliable operation in various applications, including but not limited to automated manufacturing processes, conveyor systems, and other machinery that requires precise control over digital outputs. Designed to meet the high standards of quality and reliability associated with Bosch Rexroth products, this digital output module is an essential component for users looking to enhance the functionality and efficiency of their automation systems. Its ability to seamlessly integrate into existing Inline stations further adds to its versatility, making it a valuable addition to any industrial control system requiring high-density digital signal output capabilities.


Inline connector

The modular, compact equipment configuration of the I/O systems from Rexroth offers you maximum flexibility for the cost-effective implementation of your individual machine concepts. The I/O modules have robust design and mechanics, are easy to use, have a quick reaction time and are quick to install – both in the control cabinet and in the field. Open communication standards allow you perfect integration of the I/O modules with maximum availability.

Unpacked Weight: 0.215 kg

This module is designed for use within an Inline station. It is used to output digital signals.

Total current8
Width48.8
Productgroup ID4,6
Overload-/ short circuit protection in the segment circuitElectronic; by 16 2-channel drivers
Height120
International protection codeIP20
Permissible air humidity (storage)10-95
Permissible air humidity (transport)10-95
Number of channels32
Connection typeZugfederanschluss
Connection techniques1-Leitertechnik
Depth71.5
Weight0.215
Ambient temperature (during operation)-25-55
Ambient temperature (storage and transport)-25-85
Conductor cross-sectionRigid: 0.08-0.5 mm²,Flexible: 0.08-0.5 mm²,AWG: 28 ... 16

General data

Type

R-IB IL 24 DO 32/HD-NPN-PAC

Weight 1)

g

195

Operating mode

Process data operation with 4 bytes

Actuator connection type

1-wire technology

Ambient temperature (operation)

-25 °C ... +55 °C

Ambient temperature (storage/transport)

-25 °C ... +85 °C

Permissible relative humidity (operation)

10 % ... 95 % acc. to DIN EN 61131-2

Permissible relative humidity (storage/transport)

10 % ... 95 % acc. to DIN EN 61131-2

Air pressure (storage/transport)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Protection type

IP20, IEC 60529

Protection class

III, VDE 0106, IEC 60536
1) Including plug

Connection data

Type

R-IB IL 24 DO 32/HD-NPN-PAC

Designation

Inline connection plug

Connection type

Tension spring modules

Conductor cross-section solid/flexible/AWG

0.08 mm² ... 1.5 mm²
0.08 mm² ... 1.5 mm²
28 ... 16

Interface local bus

Type

R-IB IL 24 DO 32/HD-NPN-PAC

Connection type

Data ranking

Transmission speed

kBit/s

500

Supply of module electronics and peripherals via bus coupler/power feed module

Type

R-IB IL 24 DO 32/HD-NPN-PAC

Connectivity technology

Potential jumpers

Inline potentials/performance balance

Type

R-IB IL 24 DO 32/HD-NPN-PAC

Logic voltage

V DC

7.5

Maximum current consumption from UL

mA

140

Maximum power consumption from UL

W

1.05

Segment supply voltage US

V DC

24

Nominal current consumption from US

≤8 A (16 x 0.5 A/32 x 0.25 A)

Digital outputs

Type

R-IB IL 24 DO 32/HD-NPN-PAC

Number of digital outputs

32

Nominal output voltage UOut

V DC

24

Differential voltage at INenn

V

≤ 1

Nominal current INenn each channel

A

0.5

Nominal current tolerance

%

+ 10

Total current

A

8

Nominal load

Ohmic

48 Ω

W

12

Lamps

W

12

Inductance

1.2 H; 50 Ω

VA

12

Typical signal delay upon activating a

Ohmic nominal load

µs

500

Lamp nominal load 1)

ms

100

Inductive nominal load

1.2 H; 50 Ω

ms

100

Typical signal delay upon deactivating a

Ohmic nominal load

ms

1

Lamp nominal load

ms

1

Inductive nominal load

1.2 H; 50 Ω

ms

50

Maximum switching frequency for a

Ohmic nominal load

Hz

300

Lamp nominal load

Hz

8

Inductive nominal load

1.2 H; 50 Ω

Hz

0.5

Behavior for overload

Automatic restart

Response time for ohmic overload (12 Ω)

s

≈ 3

Restart frequency for ohmic overload

Hz

≈ 400

Restart frequency for lamp overload

Hz

≈ 400

Behavior for inductive overload

Output can be destroyed

Response time upon short-circuit

s

≈ 3

Validity of the output data after switching on the 24 V supply voltage (power up)

Typ. 5 ms

Behavior when the voltage is deactivated (power down)

The output follows the power supply without delay

Limited inductive cut-off voltage

V

45

Unique maximum energy when free-wheeling 2)

mJ

≤ 100

Type of external protection circuit

Integrated 45-V-Z diode in the output chip

Overcurrent cutoff

A

≥ 0.7

Output current in deactivated state

μA

≤ 300

Activation current for lamp load

Max. 1.5 A for 20 ms

Overload/short-circuit protection in the segment circuit

Electronic; via 16 2-channel driver

Overvoltage/reverse polarity protection supply voltage

Protective elements of the feed module; protection up to 33 V DC; the supply voltage must be fused. The power supply unit should be able to provide four times the nominal current of the fuse.
1) For switching frequencies up to 8 Hz; above this frequency, the lamp load responds like an ohmic load
2) Where applicable, an external free-wheeling circuit or a circuit against inductive switch-off capacities is required

Power dissipation

Formula for calculating the power dissipation in the electronics

technical illustration-R911170411-Inline connector

where:

PEL

Total power dissipation in the module

n

Number of set outputs (n = 1 to 32)

i

Running index

ILi

Load current of output i

Power dissipation

Type

R-IB IL 24 DO 32/HD-NPN-PAC

Power dissipation in the housing PHOU 1)

W

≤ 2.8
1) Within the admissible operating temperature

Restriction of simultaneity, derating

Ambient temperature TU

-25 °C ≤ TU < +40 °C +40 °C ≤ TU < +45 °C +45 °C ≤ TU < +50 °C +50 °C ≤ TU < +55 °C

Maximum load current at 100 % simultaneity

A

0.25 0.21 0.18 0.15

Maximum load current at 50 % simultaneity

A

0.5 0.45 0.4 0.35

Electrical isolation/insulation of the voltage ranges

Type

R-IB IL 24 DO 32/HD-NPN-PAC

Common potentials

24 V main voltage UM, 24 V segment voltage US and GND are on the same potential. FE represents a separate potential area.

Separate potentials in the system of bus coupler/feed module and I/O module

Test distance

Test voltage

5 V supply incoming remote bus/7.5 V supply (bus logic)

500 V AC, 50 Hz, 1 min.

5 V supply to further remote bus/7.5 V supply (bus logic)

500 V AC, 50 Hz, 1 min.

7.5 V supply (bus logic)/24 V supply (peripherals)

500 V AC, 50 Hz, 1 min.

24 V supply (peripherals)/function earth

500 V AC, 50 Hz, 1 min.

Error messages to the higher-level control or computer system

Type

R-IB IL 24 DO 32/HD-NPN-PAC

Error message

None

Approvals

The current approvals can be found at www.boschrexroth.com.

technical illustration-R911170411-Inline connector

Dimensions

Type

R-IB IL 24 DO 32/HD-NPN-PAC

A

mm

48.8

B

mm

120

C

mm

71.5

Note on dimensions

The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715).