BOSCH REXROTH
R911170404
$641.58 USD
- BOSCH REXROTH
- Material:R911170404
- Model:R-IBIL24DI16-NPN-PAC
Quantity in stock: 0
The Bosch Rexroth R-IB IL 24 DI 16-NPN-PAC (R911170404) is a digital input module designed to integrate seamlessly into an Inline station for the purpose of acquiring digital input signals. This model boasts 16 digital inputs, which allows for significant expansion of control and monitoring capabilities within an automation system. The inputs are compatible with NPN transistor output type, which is commonly used in industrial environments, ensuring versatility and ease of integration with a variety of sensors and switches. The module operates with a nominal input voltage of 24 V DC, making it suitable for standard industrial power supplies. Its compact design ensures that it does not occupy excessive space on the DIN rail, allowing for efficient use of control cabinet real estate. The R-IB IL 24 DI 16-NPN-PAC module is engineered to perform reliably in demanding conditions, adhering to the high-quality standards expected from Bosch Rexroth components. With its robust construction and proven performance, this input module is an ideal choice for applications requiring precise digital signal processing. Its capacity to handle multiple signals makes it an essential component in complex automation tasks where accurate data acquisition is critical. Whether used in manufacturing systems, process control or other automated environments, the Bosch Rexroth R-IB IL 24 DI 16-NPN-PAC (R911170404) offers a reliable solution for expanding the functionality of an Inline station with additional digital inputs.
Inline connector
The modular, compact equipment configuration of the I/O systems from Rexroth offers you maximum flexibility for the cost-effective implementation of your individual machine concepts. The I/O modules have robust design and mechanics, are easy to use, have a quick reaction time and are quick to install – both in the control cabinet and in the field. Open communication standards allow you perfect integration of the I/O modules with maximum availability.
Unpacked Weight: 0.235 kg
This module is designed for use within an Inline station. It is used to acquire digital input signals.
| Data Sheet | Download Data Sheet |
| 3D CAD | Download 3D CAD |
| Manual | Download Manual |
| Air pressure (operation) | 70-106 kPa (up to 3,000 m above sea level) |
| Air pressure (storage / transport) | 70-106 kPa (up to 3,000 m above sea level) |
| Width | 48.8 |
| Productgroup ID | 4,6 |
| Height | 140.5 |
| International protection code | IP20 |
| Permissible air humidity (storage) | 10-95 |
| Permissible air humidity (transport) | 10-95 |
| Number of channels | 16 |
| Connection type | Zugfederanschluss |
| Connection techniques | 2-, 3-Leitertechnik |
| Depth | 71.5 |
| Weight | 0.235 |
| Ambient temperature (during operation) | -25-55 |
| Ambient temperature (storage and transport) | -25-85 |
| Conductor cross-section | Rigid: 0.08-0.5 mm²,Flexible: 0.08-0.5 mm²,AWG: 28 ... 16 |
General data
|
Type |
R-IB IL 24 DI 16-NPN-PAC | |
|
Weight 1) |
g |
210 |
|
Operating mode |
Process data operation with 2 bytes | |
|
Sensor connection type |
2-, 3-wire technology | |
|
Ambient temperature (operation) |
-25 °C ... +55 °C | |
|
Ambient temperature (storage/transport) |
-25 °C ... +85 °C | |
|
Permissible relative humidity (operation) |
10 % ... 95 %, EN 61131-2 | |
|
Permissible relative humidity (storage/transport) |
10 % ... 95 %, EN 61131-2 | |
|
Air pressure (operation) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
|
Air pressure (storage/transport) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
|
Protection type |
IP20, IEC 60529 | |
|
Protection class |
III, VDE 0106, IEC 60536 | |
| 1) | Including plug |
Connection data
|
Type |
R-IB IL 24 DI 16-NPN-PAC | |
|
Designation |
Inline connection plug | |
|
Connection type |
Tension spring modules | |
|
Conductor cross-section solid/flexible/AWG |
0.08 mm² ... 1.5 mm² 0.08 mm² ... 1.5 mm² 28 ... 16 |
|
Interface local bus
|
Type |
R-IB IL 24 DI 16-NPN-PAC | |
|
Connection type |
Data ranking | |
|
Transmission speed |
kBit/s |
500 |
Inline potentials/performance balance
|
Type |
R-IB IL 24 DI 16-NPN-PAC | |
|
Logic voltage |
V DC |
7.5 |
|
Maximum current consumption from UL |
mA |
60 |
|
Maximum power consumption from UL |
W |
0.45 |
|
Segment supply voltage US 1) |
V DC |
24 |
|
Nominal current consumption from US |
≤ 4 A (16 x 0,25 A) | |
| 1) | Rated value |
Supply of module electronics and peripherals via bus coupler/power feed module
|
Type |
R-IB IL 24 DI 16-NPN-PAC | |
|
Connectivity technology |
Potential jumpers | |
Digital inputs
|
Type |
R-IB IL 24 DI 16-NPN-PAC | ||
|
Number of digital inputs |
16 | ||
|
Description of the input |
Acc. to EN 61131-2 type 1 | ||
|
Definition of switching thresholds |
Maximum voltage of the low level ULmax |
V |
< 5 |
|
Minimum voltage of the high level UHmin |
V |
> 15 | |
|
Common potentials |
Segment supply, ground, digital inputs | ||
|
Nominal input voltage UIN |
V DC |
24 | |
|
Permissible range |
-30 V < UIN < +30 V DC | ||
|
Nominal input current at UIN |
mA |
≥ 3 | |
|
Delay time |
None | ||
|
Use of AC sensors |
AC sensors in the voltage range < UIN can only be applied to a limited extent (according to the layout of the inputs) | ||
|
Overload protection in the segment circuit |
No | ||
|
Overvoltage protection |
Protective elements of the feed module | ||
|
Reverse polarity protection |
Protective elements of the feed module | ||
|
Power dissipation |
|
|
Formula for calculating the power dissipation in the electronics |
|
|
|
|
where: |
|
|
PEL |
Total power dissipation in the module |
|
n |
Number of set inputs (n = 1 to 16) |
|
i |
Running index |
|
UINi |
Input voltage of input i |
Power dissipation
|
Type |
R-IB IL 24 DI 16-NPN-PAC | |
|
Power dissipation in the housing PHOU 1) |
W |
≤ 2.8 |
| 1) | Within the admissible operating temperature |
Restriction of simultaneity, derating
|
Type |
R-IB IL 24 DI 16-NPN-PAC | |
|
Derating |
No restriction of simultaneity, no derating | |
Electrical isolation/insulation of the voltage ranges
|
Type |
R-IB IL 24 DI 16-NPN-PAC | |
|
Common potentials |
||
|
24 V main voltage UM, 24 V segment voltage US and GND are on the same potential. FE represents a separate potential area. |
||
|
Separate potentials in the system of bus coupler/feed module and I/O module |
||
|
Test distance |
Test voltage | |
|
5 V supply incoming remote bus/7.5 V supply (bus logic) |
500 V AC, 50 Hz, 1 min. | |
|
5 V supply to further remote bus/7.5 V supply (bus logic) |
500 V AC, 50 Hz, 1 min. | |
|
7.5 V supply (bus logic)/24 V supply (peripherals) |
500 V AC, 50 Hz, 1 min. | |
|
24 V supply (peripherals)/function earth |
500 V AC, 50 Hz, 1 min. | |
Error messages to the higher-level control or computer system
|
Type |
R-IB IL 24 DI 16-NPN-PAC | |
|
Error message |
None | |
|
Approvals |
|
The current approvals can be found at www.boschrexroth.com. |
Dimensions
|
Type |
R-IB IL 24 DI 16-NPN-PAC | |
|
A |
mm |
48.8 |
|
B |
mm |
140.5 |
|
C |
mm |
71.5 |
|
Note on dimensions |