You are using an outdated browser. For a faster, safer browsing experience, upgrade for free today.

BOSCH REXROTH
R911172542


$495.15 USD
  • BOSCH REXROTH
  • Material:R911172542
  • Model:S20-DO-16/1

Quantity in stock: 0

Note: Sales tax, and shipping will be calculated at checkout.
***Disclaimer: The following summary contains information gathered from various sources such as product descriptions, technical specifications and catalogs. While efforts have been made to provide accurate details, inaccuracies may occur. It is advised to verify all information by contacting Bosch Rexroth directly.***
The Bosch Rexroth S20-DO-16/1 (R911172542) is a state-of-the-art digital output module designed to integrate seamlessly into S IO cabinet configurations. This module boasts 16 digital outputs, each capable of handling 24 V DC with a current up to 0.5 A, making it suitable for a wide range of applications requiring reliable digital signal processing. The outputs are designed with the conductor connection technique, ensuring secure and efficient connectivity. Compact and modular, the S20-DO-16/1 is engineered for space-saving installation on top hat rails, allowing for optimal use of cabinet space without compromising performance. Its innovative assembly and installation concept ensures that modules can be combined individually, providing flexibility and customization according to specific system requirements. The module also features diagnostic and status indicators that allow for easy monitoring and troubleshooting. Each output is short-circuit proof and protected against overload, enhancing the durability and reliability of the system it's integrated into. The unit also includes an electronic device nameplate for easy identification and management within complex systems. With its robust design and advanced features, the Bosch Rexroth S20-DO-16/1 digital output module represents a versatile solution for controlling actuators using 2-wire connection technology. It excels in environments where precise control of digital signals is crucial, ensuring uninterrupted operation and system integrity.


S20 I/O cabinet

Digital output module, 16 outputs, 24 V DC, 500 mA, 1-conductor connection technique

Unpacked Weight: 0.184 kg

This module is designed for use within an S20 station. It is used to output digital signals. The outputs are protected against short circuits and overload.

Innovative assembly and installation concept
Individually combinable modules
Space-saving I/O technology for top hat rail mounting
Compact, modular and simple
Type code extensionS20-DO-16/1
Productgroup ID4,6
ctrlX configuratorhttps://www.boschrexroth.com/ctrlx-configurator/
Number of channels16
EPLANhttps://ecad-configuration.boschrexroth.com/?rootpartnr=BOS.S20-DO-16%2F1**&downloads=true
Weight0.184

General data

Type

S20-DO-16/1

Color

Gray

Weight 1)

g

134

Ambient temperature (operation)

-25 °C ... +60 °C

Ambient temperature (storage/transport)

-40 °C ... +85 °C

Permissible relative humidity (operation)

5 % ... 95 %, no dewing

Permissible relative humidity (storage/transport)

5 % ... 95 %, no dewing

Air pressure (operation)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Air pressure (storage/transport)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Protection type

IP20

Protection class

III, IEC 61140, EN 61140, VDE 0140-1
1) Including plug and bus base module

Connection data

Type

S20-DO-16/1

Designation

S20 connector

Connection type

Spring-cage connection with direct plug technology

Conductor cross-section solid/flexible/AWG

0.2 mm² ... 1.5 mm²
0.2 mm² ... 1.5 mm²
24 ... 16

Stripping length

mm

8

Interface local bus

Type

S20-DO-16/1

Connection type

Bus base module

Transmission speed

MBit/s

100

Power supply to logic

Type

S20-DO-16/1

Logic voltage UBus 1)

V DC

5

Maximum current consumption from UBus

mA

180

Maximum power consumption from UBus

mW

900
1) Via bus base module

Power supply to peripherals

Type

S20-DO-16/1

Feed to digital output modules UO

V DC

24

Maximum permitted voltage range 1)

​19.2 V DC ... ​30 V DC

Current consumption from UO 2)

A

8

Typical power consumption from UO 3)

mW

320

Maximum power consumption from UO 4)

W

240

Overvoltage/reverse polarity protection supply voltage

Electronic (35 V, 0.5 s) / parallel diode; with external security 5 A (only for commissioning)

Guarantee 5)

A

≤ 8
1) Including all tolerances, including ripple
2) Secure externally
3) Without actuators
4) From that, 560 mW internal losses
5) Reverse polarity protection up to 5 A

Digital outputs

Type

S20-DO-16/1

Number of digital outputs

16

Connection type

Direct plug-in technology

Connectivity technology

1-wire technology

Nominal output voltage

24 V DC

Output current per channel

mA

≤ 500

Output current per device 1)

A

≤ 8

Nominal load

Ohmic

48 Ω; for nominal voltage

W

≤ 12

Lamps

for nominal voltage

W

≤ 12

Inductance

1.2 H, 48 Ω; for nominal voltage

VA

≤ 12

Signal delay upon activation

µs

≤ 100

Signal delay upon deactivation 2)

µs

≤ 100

Switching frequency

Max. 10000 per second (for minimum 50 mA load current)
Max. 1 per second (for inductive nominal load)
Max. 16 per second (for lamp nominal load)

Load

Ω

≥ 10

Energy consumption

See diagram

Limited inductive cut-off voltage

-25.8 V ... -15 V

Output voltage in deactivated state

V

≤ 1

Output current in deactivated state

μA

≤ 300

Behavior

For overload

Shutdown with automatic restart

For inductive overload

Output can be destroyed

Reverse voltage protection from short pulses

Limited reverse voltage protection up to 0.5 A for 1 s

Overcurrent cutoff

A

> 0.7

Output current upon overvoltage in deactivated state

mA

< 1

Short-circuit protection, overload protection of the outputs

Electronic
1) Secure externally
2) With at least 50 mA load current

PROFIBUS telegram data

Type

S20-DO-16/1

Need for parameter data

byte

3

Need for configuration data

byte

6

Error messages to the higher-level control or computer system

Type

S20-DO-16/1

Error message

Short-circuit/overload of digital outputs

Electrical isolation/insulation of the voltage ranges

Type

S20-DO-16/1

Test distance

Test voltage

5 V supply (logic)/24 V supply (peripherals)

500 V AC, 50 Hz, 1 min.

5 V supply (logic)/function earth

500 V AC, 50 Hz, 1 min.

24 V supply (peripherals)/function earth

500 V AC, 50 Hz, 1 min.

Mechanical tests

Type

S20-DO-16/1

Vibration resistance 1)

g

5

Shock 2)

30 g, 11 ms duration, semi-sinusoidal shock pulse

Continuous shock 2)

g

10
1) Acc. to EN 60068-2-6/IEC 60068-2-6
2) Acc. to EN 60068-2-27/IEC 60068-2-27

Conformity

Type

S20-DO-16/1

Conforms with

Testing of interference immunity acc. to EN 61000-6-2

Discharge of static electricity (ESD)

Criterion B; 6 kV contact discharge; 8 kV air discharge acc. to EN 61000-4-2/IEC 61000-4-2

Electro-magnetic fields

Criterion A; field strength: 10 V/m acc. to EN 61000-4-3/IEC 61000-4-3

Fast transients (burst)

Criterion B; 2 kV acc. to EN 61000-4-4/IEC 61000-4-4

Transient overvoltage (surge)

Criterion B; supply lines DC: ±0.5 kV/±0.5 kV (symmetric/asymmetric) acc. to EN 61000-4-5/IEC 61000-4-5

Line-fed disturbances

Criterion A; test voltage 10 V acc. to EN 61000-4-6/IEC 61000-4-6

Testing of disturbance transmission acc. to EN 61000-6-3

Radio disturbance characteristics

Class B acc. to EN 55022

Approvals

The current approvals can be found at www.boschrexroth.com.

technical illustration-R911172542-S20 I/O cabinet

Dimensions

Type

S20-DO-16/1

A

mm

35

B

mm

126.1

C

mm

54

Note on dimensions

The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715).