BOSCH REXROTH
R911172535
$705.82 USD
- BOSCH REXROTH
- Material:R911172535
- Model:S20-DO-32/1
Quantity in stock: 0
The Bosch Rexroth S20-DO-32/1 (R911172535) is an advanced digital output module that offers a seamless integration into cabinet IO systems. This module is engineered to provide a high degree of flexibility, allowing for the cost-effective realization of customized machine concepts. With its compact and modular design, the S20-DO-32/1 ensures space-saving installation on DIN rails and facilitates easy handling and quick assembly. The robust mechanics of this IO module are complemented by forced ventilation via an axial fan, ensuring reliable operation even in demanding environments. The S20-DO-32/1 features innovative installation concepts that reduce setup time both in the control cabinet and in the field. It boasts open communication standards for optimal integration with other components, ensuring high availability and fast reaction times for your automation tasks. The module includes diagnostic and status indicators that enhance maintenance efficiency and minimize downtime. Equipped with 32 digital outputs operating at 24 VDC with a current rating of 0.5 A each, this module is capable of driving a wide range of actuators using 2-wire connection technology. Additionally, these outputs are designed to be short-circuit proof, providing added protection to your system against potential electrical faults. The electronic device nameplate feature offers easy identification and management within the system architecture. This particular model is specifically designed for incorporation into an S station setup where it serves as a reliable solution for outputting digital signals. Its integration capabilities make it an ideal choice for applications requiring precise control over digital output functions within industrial automation systems.
Cabinet I/O S20
The modular, compact device design of the I/O systems from Rexroth provides you with maximum flexibility for cost-effective implementation of your custom machine concepts. The I/O modules have a robust design and mechanics, Forced ventilated - Axial fan 230Vre easy to handle, have a fast reaction time and are quick to install – both in the control cabinet as well as in the field. Open communication standards allow you to perfectly integrate the I/O modules with maximum availability.
Unpacked Weight: 0.231 kg
This module is designed for use within an S20 station. It is used to output digital signals. The outputs are protected against short circuits and overload.
Innovative assembly and installation concept |
Individually combinable modules |
Space-saving I/O technology for top hat rail mounting |
Compact, modular and simple |
2D CAD | Download 2D CAD |
3D CAD | Download 3D CAD |
Type code extension | S20-DO-32/1 |
Productgroup ID | 4,6 |
ctrlX configurator | https://www.boschrexroth.com/ctrlx-configurator/ |
Number of channels | 32 |
EPLAN | https://ecad-configuration.boschrexroth.com/?rootpartnr=BOS.S20-DO-32%2F1**&downloads=true |
Weight | 0.231 |
General data
Type |
S20-DO-32/1 | |
Color |
Gray | |
Weight |
g |
191 |
Ambient temperature (operation) |
-25 °C ... +60 °C | |
Ambient temperature (storage/transport) |
-40 °C ... +85 °C | |
Permissible relative humidity (operation) |
5 % ... 95 % acc. to DIN EN 61131-2 | |
Permissible relative humidity (storage/transport) |
5 % ... 95 % acc. to DIN EN 61131-2 | |
Air pressure (operation) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
Air pressure (storage/transport) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
Protection type |
IP20 | |
Protection class |
III, IEC 61140, EN 61140, VDE 0140-1 |
Connection data
Type |
S20-DO-32/1 | |
Designation |
S20 connector | |
Connection type |
Spring-cage connection with direct plug technology | |
Conductor cross-section solid/flexible/AWG |
0.2 mm² ... 1.5 mm² 0.2 mm² ... 1.5 mm² 24 ... 16 |
|
Stripping length |
mm |
8 |
Interface local bus
Type |
S20-DO-32/1 | |
Connection type |
Bus base module | |
Transmission speed |
MBit/s |
100 |
Power supply to logic
Type |
S20-DO-32/1 | |
Logic voltage UBus 1) |
V DC |
5 |
Maximum current consumption from UBus |
mA |
180 |
Maximum power consumption from UBus |
mW |
900 |
1) | Via bus base module |
Power supply to peripherals
Type |
S20-DO-32/1 | |
Feed to digital output modules UO |
V DC |
24 |
Maximum permitted voltage range 1) |
19.2 V DC ... 30 V DC | |
Current consumption from UO 2) |
A |
8 |
Overvoltage/reverse polarity protection supply voltage |
Electronic (35 V, 0.5 s) / parallel diode; with external security 5 A (only for commissioning) | |
Guarantee 3) |
A |
≤ 8 |
1) | Including all tolerances, including ripple |
2) | Secure externally |
3) | Reverse polarity protection up to 5 A |
Digital outputs
Type |
S20-DO-32/1 | |||
Number of digital outputs |
32 | |||
Connection type |
Direct plug-in technology | |||
Connectivity technology |
1-wire technology | |||
Nominal output voltage |
24 V DC | |||
Output current per channel |
mA |
≤ 500 | ||
Output current per device 1) |
A |
≤ 8 | ||
Nominal load |
Ohmic |
48 Ω; for nominal voltage |
W |
≤ 12 |
Lamps |
for nominal voltage |
W |
≤ 12 | |
Inductance |
1.2 H, 48 Ω; for nominal voltage |
VA |
≤ 12 | |
Signal delay upon activation |
µs |
≤ 150 | ||
Signal delay upon deactivation 2) |
µs |
≤ 200 | ||
Switching frequency |
Max. 5500 per second (for ohmic nominal load) Max. 1 per second (for inductive nominal load) Max. 16 per second (for lamp nominal load) |
|||
Load |
kΩ |
≥ 10 | ||
Energy consumption |
See diagram | |||
Limited inductive cut-off voltage |
UDemag = UO - 47 V (UDemag = demagnetization voltage) | |||
Output voltage in deactivated state |
V |
≤ 1 | ||
Output current in deactivated state |
μA |
≤ 300 | ||
Behavior |
For overload |
Shutdown with automatic restart | ||
For inductive overload |
Output can be destroyed | |||
Reverse voltage protection from short pulses |
Limited reverse voltage protection up to 0.5 A for 1 s | |||
Overcurrent cutoff |
A |
> 0.7 | ||
Output current upon overvoltage in deactivated state |
mA |
< 1 | ||
Short-circuit protection, overload protection of the outputs |
Electronic |
1) | Secure externally |
2) | With ohmic nominal load |
Error messages to the higher-level control or computer system
Type |
S20-DO-32/1 | |
Error message |
Short-circuit/overload of digital outputs |
Electrical isolation/insulation of the voltage ranges
Type |
S20-DO-32/1 | |
Test distance |
Test voltage | |
5 V supply (logic)/24 V supply (peripherals) |
500 V AC, 50 Hz, 1 min. | |
5 V supply (logic)/function earth |
500 V AC, 50 Hz, 1 min. | |
24 V supply (peripherals)/function earth |
500 V AC, 50 Hz, 1 min. |
Mechanical tests
Type |
S20-DO-32/1 | |
Vibration resistance 1) |
g |
5 |
Shock 2) |
25 g, 11 ms duration, semi-sinusoidal shock pulse | |
Continuous shock 3) |
g |
10 |
1) | Acc. to IEC 60068-2-6 |
2) | Acc. to IEC 60068-2-27 |
3) | Acc. to EN 60068-2-29 |
Conformity
Type |
S20-DO-32/1 | ||
Conforms with |
|||
Testing of interference immunity acc. to EN 61000-6-2 |
Discharge of static electricity (ESD) |
Criterion B; 6 kV contact discharge; 8 kV air discharge acc. to EN 61000-4-2/IEC 61000-4-2 | |
Electro-magnetic fields |
Criterion A; field strength: 10 V/m acc. to EN 61000-4-3/IEC 61000-4-3 | ||
Fast transients (burst) |
Criterion B; 2 kV acc. to EN 61000-4-4/IEC 61000-4-4 | ||
Transient overvoltage (surge) |
Criterion B; supply lines DC: ±0.5 kV/±0.5 kV (symmetric/asymmetric) acc. to EN 61000-4-5/IEC 61000-4-5 | ||
Line-fed disturbances |
Criterion A; test voltage 10 V acc. to EN 61000-4-6/IEC 61000-4-6 | ||
Testing of disturbance transmission acc. to EN 61000-6-3 |
Radio disturbance characteristics |
Class B acc. to EN 55022 |
Approvals |
The current approvals can be found at www.boschrexroth.com. |
Dimensions
Type |
S20-DO-32/1 | |
A |
mm |
53.6 |
B |
mm |
126.1 |
C |
mm |
54 |
Note on dimensions |
The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715). |