You are using an outdated browser. For a faster, safer browsing experience, upgrade for free today.

BOSCH REXROTH
R911170875


$1,409.07 USD
  • BOSCH REXROTH
  • Material:R911170875
  • Model:R-ILS3BKDI8DO4-PAC

Quantity in stock: 0

Note: Sales tax, and shipping will be calculated at checkout.
***Disclaimer: The following summary contains information gathered from various sources such as product descriptions, technical specifications and catalogs. While efforts have been made to provide accurate details, inaccuracies may occur. It is advised to verify all information by contacting Bosch Rexroth directly.***
The Bosch Rexroth R-IL S3 BK DI8 DO4-PAC (R911170875) is an advanced bus coupler designed to seamlessly integrate into a third-generation Sercos network, serving as a crucial interface for the Inline installation system. This device enables the connection of numerous Inline participants, creating a cohesive station that can support a substantial number of local bus participants. The R-IL S3 BK DI8 DO4-PAC itself is considered as the initial local bus participant within this configuration, with its inputs and outputs representing the first and second participants in the network hierarchy. This bus coupler is engineered to facilitate efficient communication and control within complex automation systems, ensuring reliable data exchange between connected devices. It boasts eight digital inputs and four digital outputs, providing sufficient I/O capabilities for various application requirements. The device's compatibility with Sercos III networks makes it an essential component for users looking to leverage the speed and synchronization benefits of this communication standard. The robust design and technical specifications of the R-IL S3 BK DI8 DO4-PAC make it suitable for a wide range of industrial applications where precise coordination between multiple devices is necessary. Its capacity to support numerous local bus participants means that it can be effectively utilized in systems requiring extensive sensor and actuator integration. Furthermore, its firmware revision ensures up-to-date functionality and performance, aligning with contemporary automation demands.


Inline connector

The modular, compact equipment configuration of the I/O systems from Rexroth offers you maximum flexibility for the cost-effective implementation of your individual machine concepts. The I/O modules have robust design and mechanics, are easy to use, have a quick reaction time and are quick to install – both in the control cabinet and in the field. Open communication standards allow you perfect integration of the I/O modules with maximum availability.

Unpacked Weight: 0.332 kg

Effective as of firmware revision 1.60.

The bus coupler is designed for use within a third generation Sercos network and is the connection to the Inline installation system. You can use the bus coupler to connect up to 61 Inline participants to an existing Sercos network. The bus coupler and the Inline participants form one station with a maximum 63 local bus participants, the inputs and outputs of the bus coupler are to be regarded as the first and second local bus participant.

Air pressure (operation)70-106 kPa (up to 3,000 m above sea level)
Total current2
Width80
Short circuit protection, overload protection of the outputsFree-wheeling circuit in the output driver
Productgroup ID4,6
Height120
International protection codeIP20
Permissible air humidity (storage)10-95
CommunicationSercos slave
Permissible air humidity (transport)10-95
Number of channels12
Connection typeZugfederanschluss
Connection techniques2-, 3-Leitertechnik
Depth71.5
Weight0.332
Ambient temperature (during operation)-25-60
Ambient temperature (storage and transport)-45-85
Conductor cross-sectionRigid: 0.08-0.5 mm²,Flexible: 0.08-0.5 mm²,AWG: 28 ... 16

General data

Type

R-IL S3 BK DI8 DO4-PAC

Color

Gray

Weight 1)

g

375

Ambient temperature (operation)

-25 °C ... +60 °C

Ambient temperature (storage/transport)

-45 °C ... +85 °C

Permissible relative humidity (operation)

10 % ... 95 % acc. to DIN EN 61131-2

Permissible relative humidity (storage/transport)

10 % ... 95 % acc. to DIN EN 61131-2

Air pressure (operation)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Air pressure (storage/transport)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Protection type

IP20

Protection class

III, IEC 61140, EN 61140, VDE 0140-1
1) Including plug

Connection data

Type

R-IL S3 BK DI8 DO4-PAC

Designation

Inline connection plug

Connection type

Spring-cage connection

Conductor cross-section solid/flexible/AWG

0.08 mm² ... 1.5 mm²
0.08 mm² ... 1.5 mm²
28 ... 16

Interface fieldbus

Type

R-IL S3 BK DI8 DO4-PAC

Number of interfaces

2

Connection type

RJ45 socket, autonegotiation

Transmission speed

​100 MBit/s

Transfer physics

Ethernet in RJ45 twisted pair
-
-
-

Transmission length

m

≤ 100

Interface local bus

Type

R-IL S3 BK DI8 DO4-PAC

Connection type

Inline data jumper

Transmission speed

500 kbits/s, 2 Mbits/s (automatic detection, no mixed system)

System boundaries

Type

R-IL S3 BK DI8 DO4-PAC

Number of process data

Max. 512 bytes (per data direction)

Number of supported participants per station

≤ 63

Number of subsequent local bus participants

Max. 61 (I/Os on board are two participants)

Number of participants with parameter channel

≤ 16

Sercos

Type

R-IL S3 BK DI8 DO4-PAC

Device type

Sercos slave

Device profile

FSP_IO

Update rate

µs

250

Supply of module electronics

Type

R-IL S3 BK DI8 DO4-PAC

Connection type

Spring-cage connection

Designation

Bus coupler supply UBK; from the bus coupler supply, the logic supply UL (7.5 V) and the analog supply UANA (24 V) are generated.

Supply voltage

V DC

24

Supply voltage range

19.2 V DC ... 30 V DC (including all tolerances, including ripple)

Supply current

mA

≤ 150

Maximum current consumption from UBK

A

1.05

Power dissipation

Typ. 3.2 W (device total)

Overvoltage/reverse polarity protection supply voltage

35 V, suppressor diode

Inline potentials/performance balance

Type

R-IL S3 BK DI8 DO4-PAC

Supply to the main circuit UM

VDC

24

Supply voltage range UM

19.2 V DC ... 30 V DC (including all tolerances, including ripple)

Power supply to UM

Max. 8 A (total of UM + US)

Current consumption from UM

A

≤ 8

Logic voltage UL

7.5 V DC ±5 %

Power supply to UL

A

≤ 0.8

Peripheral supply voltage UANA

V DC

24

Supply voltage range UANA

19.2 V DC ... 30 V DC (including all tolerances, including ripple)

Power supply to UANA

A

≤ 0.5

Maximum current consumption from UBK

A

1.05

Segment supply voltage US

V DC

24

Supply voltage range US

19.2 V DC ... 30 V DC (including all tolerances, including ripple)

Power supply to US

Max. 8 A (total of UM + US)

Current consumption from US

A

≤ 8

Power dissipation

Typ. 3.2 W (device total)

Digital inputs

Type

R-IL S3 BK DI8 DO4-PAC

Number of digital inputs

8 (IEC 61131-2 type 1)

Connection type

Inline connection plug

Connectivity technology

2-, 3-wire

Nominal input voltage

V DC

24

Nominal input current

mA

3

Current profile

Limited to maximum 3 mA

Input voltage range "0" signal

-30 V DC ... 5 V DC

Input voltage range "1" signal

15 V DC ... 30 V DC

Delay time upon signal change from 0 to 1

Typ. 11 µs

Delay time upon signal change from 1 to 0

Typ. 140 µs

Permissible cable length to sensor

m

100

Reverse polarity protection

Reverse polarity protection diode

Digital outputs

Type

R-IL S3 BK DI8 DO4-PAC

Number of digital outputs

4

Connection type

Inline connection plug

Connectivity technology

2-, 3-wire

Nominal output voltage

24 V DC

Output current per channel

mA

≤ 500

Output current per device

A

≤ 2

Nominal load ohmic

W

12

Nominal load lamps

W

12

Nominal load inductive

1.2 H; 48 Ω

VA

12

Signal delay upon power-up of ohmic nominal load 1)

µs

≤ 50

Signal delay upon turning off an ohmic nominal load 1)

µs

≤ 250

Maximum switching frequency for inductive nominal load

1.2 H; 48 Ω

Hz

0.5

Behavior when the voltage is switched off

The output follows the power supply without delay

Limited inductive cut-off voltage

V

≈ - 30

Output current in deactivated state 2)

μA

≤ 10

Behavior for overload

Automatic restart

Inductive overload

Output can be destroyed

Reverse voltage protection from short pulses

Reverse voltage protection

Resistance to permanently generated reverse voltage

A

≤ 2

Overcurrent cutoff

A

≥ 0.7

Output current upon overvoltage in deactivated state

mA

≤ 25

Short-circuit protection, overload protection of the outputs

Freewheeling circuit in the output driver
1) With 0.5 A load
2) In the unloaded state, a voltage can also be measured at an output that is not set.

Error messages to the higher-level control or computer system

Type

R-IL S3 BK DI8 DO4-PAC

Error message

Short-circuit/overload of digital outputs
Failure in sensor supply
Failure in actuator supply

Mechanical tests

Type

R-IL S3 BK DI8 DO4-PAC

Vibration resistance 1)

g

5

Shock 2)

25 g, 11 ms duration, semi-sinusoidal shock pulse
1) Acc. to EN 60068-2-6/IEC 60068-2-6
2) Acc. to EN 60068-2-27/IEC 60068-2-27

Conformity

Type

R-IL S3 BK DI8 DO4-PAC

Conforms with

Testing of interference immunity acc. to EN 61000-6-2

Discharge of static electricity (ESD)

Criterion B; 6 kV contact discharge; 8 kV air discharge acc. to EN 61000-4-2/IEC 61000-4-2

Electro-magnetic fields

Criterion A; field strength: 10 V/m acc. to EN 61000-4-3/IEC 61000-4-3

Fast transients (burst)

Criterion A; all interfaces 1 kV; criterion B; all interfaces 2 kV acc. to EN 61000-4-4/IEC 61000-4-4

Transient overvoltage (surge)

Criterion B; supply lines DC: ±0.5 kV/±0.5 kV (symmetric/asymmetric); fieldbus cable shielding: ±1 kV acc. to EN 61000-4-5/IEC 61000-4-5

Line-fed disturbances

Criterion A; test voltage 10 V acc. to EN 61000-4-6/IEC 61000-4-6

Testing of disturbance transmission acc. to EN 61000-6-4

Testing of line-fed disturbance transmission

Class A acc. to EN 55011

Approvals

The current approvals can be found at www.boschrexroth.com.

technical illustration-R911170875-Inline connector

Dimensions

Type

R-IL S3 BK DI8 DO4-PAC

A

mm

80

B

mm

120

C

mm

71.5

Note on dimensions

The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715).