BOSCH REXROTH
R911170875
$1,409.07 USD
- BOSCH REXROTH
- Material:R911170875
- Model:R-ILS3BKDI8DO4-PAC
Quantity in stock: 0
The Bosch Rexroth R-IL S3 BK DI8 DO4-PAC (R911170875) is an advanced bus coupler designed to seamlessly integrate into a third-generation Sercos network, serving as a crucial interface for the Inline installation system. This device enables the connection of numerous Inline participants, creating a cohesive station that can support a substantial number of local bus participants. The R-IL S3 BK DI8 DO4-PAC itself is considered as the initial local bus participant within this configuration, with its inputs and outputs representing the first and second participants in the network hierarchy. This bus coupler is engineered to facilitate efficient communication and control within complex automation systems, ensuring reliable data exchange between connected devices. It boasts eight digital inputs and four digital outputs, providing sufficient I/O capabilities for various application requirements. The device's compatibility with Sercos III networks makes it an essential component for users looking to leverage the speed and synchronization benefits of this communication standard. The robust design and technical specifications of the R-IL S3 BK DI8 DO4-PAC make it suitable for a wide range of industrial applications where precise coordination between multiple devices is necessary. Its capacity to support numerous local bus participants means that it can be effectively utilized in systems requiring extensive sensor and actuator integration. Furthermore, its firmware revision ensures up-to-date functionality and performance, aligning with contemporary automation demands.
Inline connector
The modular, compact equipment configuration of the I/O systems from Rexroth offers you maximum flexibility for the cost-effective implementation of your individual machine concepts. The I/O modules have robust design and mechanics, are easy to use, have a quick reaction time and are quick to install – both in the control cabinet and in the field. Open communication standards allow you perfect integration of the I/O modules with maximum availability.
Unpacked Weight: 0.332 kg
Effective as of firmware revision 1.60.
The bus coupler is designed for use within a third generation Sercos network and is the connection to the Inline installation system. You can use the bus coupler to connect up to 61 Inline participants to an existing Sercos network. The bus coupler and the Inline participants form one station with a maximum 63 local bus participants, the inputs and outputs of the bus coupler are to be regarded as the first and second local bus participant.
| Data Sheet | Download Data Sheet |
| 3D CAD | Download 3D CAD |
| Manual | Download Manual |
| Air pressure (operation) | 70-106 kPa (up to 3,000 m above sea level) |
| Total current | 2 |
| Width | 80 |
| Short circuit protection, overload protection of the outputs | Free-wheeling circuit in the output driver |
| Productgroup ID | 4,6 |
| Height | 120 |
| International protection code | IP20 |
| Permissible air humidity (storage) | 10-95 |
| Communication | Sercos slave |
| Permissible air humidity (transport) | 10-95 |
| Number of channels | 12 |
| Connection type | Zugfederanschluss |
| Connection techniques | 2-, 3-Leitertechnik |
| Depth | 71.5 |
| Weight | 0.332 |
| Ambient temperature (during operation) | -25-60 |
| Ambient temperature (storage and transport) | -45-85 |
| Conductor cross-section | Rigid: 0.08-0.5 mm²,Flexible: 0.08-0.5 mm²,AWG: 28 ... 16 |
General data
|
Type |
R-IL S3 BK DI8 DO4-PAC | |
|
Color |
Gray | |
|
Weight 1) |
g |
375 |
|
Ambient temperature (operation) |
-25 °C ... +60 °C | |
|
Ambient temperature (storage/transport) |
-45 °C ... +85 °C | |
|
Permissible relative humidity (operation) |
10 % ... 95 % acc. to DIN EN 61131-2 | |
|
Permissible relative humidity (storage/transport) |
10 % ... 95 % acc. to DIN EN 61131-2 | |
|
Air pressure (operation) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
|
Air pressure (storage/transport) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
|
Protection type |
IP20 | |
|
Protection class |
III, IEC 61140, EN 61140, VDE 0140-1 | |
| 1) | Including plug |
Connection data
|
Type |
R-IL S3 BK DI8 DO4-PAC | |
|
Designation |
Inline connection plug | |
|
Connection type |
Spring-cage connection | |
|
Conductor cross-section solid/flexible/AWG |
0.08 mm² ... 1.5 mm² 0.08 mm² ... 1.5 mm² 28 ... 16 |
|
Interface fieldbus
|
Type |
R-IL S3 BK DI8 DO4-PAC | |
|
Number of interfaces |
2 | |
|
Connection type |
RJ45 socket, autonegotiation | |
|
Transmission speed |
100 MBit/s | |
|
Transfer physics |
Ethernet in RJ45 twisted pair - - - |
|
|
Transmission length |
m |
≤ 100 |
Interface local bus
|
Type |
R-IL S3 BK DI8 DO4-PAC | |
|
Connection type |
Inline data jumper | |
|
Transmission speed |
500 kbits/s, 2 Mbits/s (automatic detection, no mixed system) | |
System boundaries
|
Type |
R-IL S3 BK DI8 DO4-PAC | |
|
Number of process data |
Max. 512 bytes (per data direction) | |
|
Number of supported participants per station |
≤ 63 | |
|
Number of subsequent local bus participants |
Max. 61 (I/Os on board are two participants) | |
|
Number of participants with parameter channel |
≤ 16 | |
Sercos
|
Type |
R-IL S3 BK DI8 DO4-PAC | |
|
Device type |
Sercos slave | |
|
Device profile |
FSP_IO | |
|
Update rate |
µs |
250 |
Supply of module electronics
|
Type |
R-IL S3 BK DI8 DO4-PAC | |
|
Connection type |
Spring-cage connection | |
|
Designation |
Bus coupler supply UBK; from the bus coupler supply, the logic supply UL (7.5 V) and the analog supply UANA (24 V) are generated. | |
|
Supply voltage |
V DC |
24 |
|
Supply voltage range |
19.2 V DC ... 30 V DC (including all tolerances, including ripple) | |
|
Supply current |
mA |
≤ 150 |
|
Maximum current consumption from UBK |
A |
1.05 |
|
Power dissipation |
Typ. 3.2 W (device total) | |
|
Overvoltage/reverse polarity protection supply voltage |
35 V, suppressor diode | |
Inline potentials/performance balance
|
Type |
R-IL S3 BK DI8 DO4-PAC | |
|
Supply to the main circuit UM |
VDC |
24 |
|
Supply voltage range UM |
19.2 V DC ... 30 V DC (including all tolerances, including ripple) | |
|
Power supply to UM |
Max. 8 A (total of UM + US) | |
|
Current consumption from UM |
A |
≤ 8 |
|
Logic voltage UL |
7.5 V DC ±5 % | |
|
Power supply to UL |
A |
≤ 0.8 |
|
Peripheral supply voltage UANA |
V DC |
24 |
|
Supply voltage range UANA |
19.2 V DC ... 30 V DC (including all tolerances, including ripple) | |
|
Power supply to UANA |
A |
≤ 0.5 |
|
Maximum current consumption from UBK |
A |
1.05 |
|
Segment supply voltage US |
V DC |
24 |
|
Supply voltage range US |
19.2 V DC ... 30 V DC (including all tolerances, including ripple) | |
|
Power supply to US |
Max. 8 A (total of UM + US) | |
|
Current consumption from US |
A |
≤ 8 |
|
Power dissipation |
Typ. 3.2 W (device total) | |
Digital inputs
|
Type |
R-IL S3 BK DI8 DO4-PAC | |
|
Number of digital inputs |
8 (IEC 61131-2 type 1) | |
|
Connection type |
Inline connection plug | |
|
Connectivity technology |
2-, 3-wire | |
|
Nominal input voltage |
V DC |
24 |
|
Nominal input current |
mA |
3 |
|
Current profile |
Limited to maximum 3 mA | |
|
Input voltage range "0" signal |
-30 V DC ... 5 V DC | |
|
Input voltage range "1" signal |
15 V DC ... 30 V DC | |
|
Delay time upon signal change from 0 to 1 |
Typ. 11 µs | |
|
Delay time upon signal change from 1 to 0 |
Typ. 140 µs | |
|
Permissible cable length to sensor |
m |
100 |
|
Reverse polarity protection |
Reverse polarity protection diode | |
Digital outputs
|
Type |
R-IL S3 BK DI8 DO4-PAC | ||
|
Number of digital outputs |
4 | ||
|
Connection type |
Inline connection plug | ||
|
Connectivity technology |
2-, 3-wire | ||
|
Nominal output voltage |
24 V DC | ||
|
Output current per channel |
mA |
≤ 500 | |
|
Output current per device |
A |
≤ 2 | |
|
Nominal load ohmic |
W |
12 | |
|
Nominal load lamps |
W |
12 | |
|
Nominal load inductive |
1.2 H; 48 Ω |
VA |
12 |
|
Signal delay upon power-up of ohmic nominal load 1) |
µs |
≤ 50 | |
|
Signal delay upon turning off an ohmic nominal load 1) |
µs |
≤ 250 | |
|
Maximum switching frequency for inductive nominal load |
1.2 H; 48 Ω |
Hz |
0.5 |
|
Behavior when the voltage is switched off |
The output follows the power supply without delay | ||
|
Limited inductive cut-off voltage |
V |
≈ - 30 | |
|
Output current in deactivated state 2) |
μA |
≤ 10 | |
|
Behavior for overload |
Automatic restart | ||
|
Inductive overload |
Output can be destroyed | ||
|
Reverse voltage protection from short pulses |
Reverse voltage protection | ||
|
Resistance to permanently generated reverse voltage |
A |
≤ 2 | |
|
Overcurrent cutoff |
A |
≥ 0.7 | |
|
Output current upon overvoltage in deactivated state |
mA |
≤ 25 | |
|
Short-circuit protection, overload protection of the outputs |
Freewheeling circuit in the output driver | ||
| 1) | With 0.5 A load |
| 2) | In the unloaded state, a voltage can also be measured at an output that is not set. |
Error messages to the higher-level control or computer system
|
Type |
R-IL S3 BK DI8 DO4-PAC | |
|
Error message |
Short-circuit/overload of digital outputs Failure in sensor supply Failure in actuator supply |
|
Mechanical tests
|
Type |
R-IL S3 BK DI8 DO4-PAC | |
|
Vibration resistance 1) |
g |
5 |
|
Shock 2) |
25 g, 11 ms duration, semi-sinusoidal shock pulse | |
| 1) | Acc. to EN 60068-2-6/IEC 60068-2-6 |
| 2) | Acc. to EN 60068-2-27/IEC 60068-2-27 |
Conformity
|
Type |
R-IL S3 BK DI8 DO4-PAC | ||
|
Conforms with |
|||
|
Testing of interference immunity acc. to EN 61000-6-2 |
Discharge of static electricity (ESD) |
Criterion B; 6 kV contact discharge; 8 kV air discharge acc. to EN 61000-4-2/IEC 61000-4-2 | |
|
Electro-magnetic fields |
Criterion A; field strength: 10 V/m acc. to EN 61000-4-3/IEC 61000-4-3 | ||
|
Fast transients (burst) |
Criterion A; all interfaces 1 kV; criterion B; all interfaces 2 kV acc. to EN 61000-4-4/IEC 61000-4-4 | ||
|
Transient overvoltage (surge) |
Criterion B; supply lines DC: ±0.5 kV/±0.5 kV (symmetric/asymmetric); fieldbus cable shielding: ±1 kV acc. to EN 61000-4-5/IEC 61000-4-5 | ||
|
Line-fed disturbances |
Criterion A; test voltage 10 V acc. to EN 61000-4-6/IEC 61000-4-6 | ||
|
Testing of disturbance transmission acc. to EN 61000-6-4 |
Testing of line-fed disturbance transmission |
Class A acc. to EN 55011 | |
|
Approvals |
|
The current approvals can be found at www.boschrexroth.com. |
Dimensions
|
Type |
R-IL S3 BK DI8 DO4-PAC | |
|
A |
mm |
80 |
|
B |
mm |
120 |
|
C |
mm |
71.5 |
|
Note on dimensions |
The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715). | |