BOSCH REXROTH
R-IBIL24DI32/HD-PAC
R911170753
I/O Rexroth Inline Digital: Input
BOSCH REXROTH
MATERIAL: R911170753
SUMMARY: I/O Rexroth Inline Digital: Input
Quantity in stock: 1
Quantity Details:- Hydrotech Stock: 0 can ship April 22, 2024
- Factory Stock: 1 can ship June 10, 2024
This module is designed for use within an Inline station. It is used to acquire digital input signals.
General data
Type |
R-IB IL 24 DI 32/HD-PAC | |
Weight 1) |
g |
185 |
Operating mode |
Process data operation with 4 bytes | |
Sensor connection type |
1-wire technology | |
Ambient temperature (operation) |
-25 °C ... +55 °C | |
Ambient temperature (storage/transport) |
-25 °C ... +85 °C | |
Permissible relative humidity (operation) |
10 % ... 95 % acc. to DIN EN 61131-2 | |
Permissible relative humidity (storage/transport) |
10 % ... 95 % acc. to DIN EN 61131-2 | |
Air pressure (operation) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
Air pressure (storage/transport) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
Protection type |
IP20, IEC 60529 | |
Protection class |
III, VDE 0106, IEC 60536 |
1) | Including plug |
Connection data
Type |
R-IB IL 24 DI 32/HD-PAC | |
Designation |
Inline connection plug | |
Connection type |
Tension spring modules | |
Conductor cross-section solid/flexible/AWG |
0.2 mm² ... 1.5 mm² 0.2 mm² ... 1.5 mm² 24 ... 16 |
Interface local bus
Type |
R-IB IL 24 DI 32/HD-PAC | |
Connection type |
Data ranking | |
Transmission speed |
kBit/s |
500 |
Inline potentials/performance balance
Type |
R-IB IL 24 DI 32/HD-PAC | |
Logic voltage |
V DC |
7.5 |
Maximum current consumption from UL |
mA |
90 |
Maximum power consumption from UL |
W |
0.675 |
Supply of module electronics and peripherals via bus coupler/power feed module
Type |
R-IB IL 24 DI 32/HD-PAC | |
Connectivity technology |
Potential jumpers |
Digital inputs
Type |
R-IB IL 24 DI 32/HD-PAC | ||
Number of digital inputs |
32 | ||
Dimensioning of inputs |
Acc. to EN 61131-2 type 1 | ||
Definition of switching thresholds |
Maximum voltage of the low level ULmax |
V |
< 5 |
Minimum voltage of the high level UHmin |
V |
> 15 | |
Common potentials |
Segment supply, ground | ||
Nominal input voltage UIN |
V DC |
24 | |
Permissible range |
-3 V < UIN < +30 V DC | ||
Nominal input current at UIN |
mA |
2.8 | |
Delay time |
ton = 2 ms, toff = 4 ms | ||
Use of AC sensors |
AC sensors in the voltage range < UIN can only be applied to a limited extent (according to the layout of the inputs) | ||
Overload protection in the segment circuit |
No | ||
Overvoltage protection |
Protective elements of the feed module | ||
Reverse polarity protection |
Protective elements of the feed module |
Power dissipation |
|
Formula for calculating the power dissipation in the electronics |
|
where: |
|
PEL |
Total power dissipation in the module |
n |
Number of set inputs (n = 1 to 32) |
i |
Running index |
UINi |
Input voltage of input i |
IINi |
Input current of input i matching the input characteristic |
Restriction of simultaneity, derating
Type |
R-IB IL 24 DI 32/HD-PAC | |
Derating |
No restriction of simultaneity, no derating |
Electrical isolation/insulation of the voltage ranges
Type |
R-IB IL 24 DI 32/HD-PAC | |
Common potentials |
||
24 V peripheral voltage, 24 V segment voltage and GND are on the same potential. FE represents a separate potential area. |
||
Separate potentials in the system of bus coupler/feed module and I/O module |
||
Test distance |
Test voltage | |
5 V supply incoming remote bus/7.5 V supply (bus logic) |
500 V AC, 50 Hz, 1 min. | |
5 V supply to further remote bus/7.5 V supply (bus logic) |
500 V AC, 50 Hz, 1 min. | |
7.5 V supply (bus logic)/24 V supply (peripherals) |
500 V AC, 50 Hz, 1 min. | |
24 V supply (peripherals)/function earth |
500 V AC, 50 Hz, 1 min. |
Error messages to the higher-level control or computer system
Type |
R-IB IL 24 DI 32/HD-PAC | |
Error message |
None |
Approvals |
The current approvals can be found at www.boschrexroth.com. |
Dimensions
Type |
R-IB IL 24 DI 32/HD-PAC | |
A |
mm |
48.8 |
B |
mm |
120 |
C |
mm |
71.5 |
Note on dimensions |
The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715). |