ABZMS-41-1X/1200/RTA/DC-K24
R901269294
Level Sensors

Level display & meas. equipments (Std)

$1,565.16

BOSCH REXROTH

MATERIAL:  R901269294

SUMMARY:  Level display & meas. equipments (Std)

Add to Cart

Float switches are switching devices operated by a float moved by fluid. These are used to control fluid levels in power unit tanks.

 

Three series are available:

Float switches typeABZMS…M with a maximum of four adjustable switching contacts normally closed contact/ normally open contact or a maximum of three switching contacts and optionally fixedly set temperature contact as normally closed contact for 60 °C, 70 °C or 80 °C Float switches type ABZMS…RTA with resistance measuring chain (level) and resistance thermometer (temperature) with analog output from 4 to 20 mA. Float switches type ABZMS…D with resistance measuring chain and resistance thermometer as with type ABZMS...RTA and additional display and control unit for level and temperature setting.

Level function

Level contacts:

The sliding tubes contain the adjustable reed contacts (normally closed contact and normally open contact) that are switched by the permanent magnets installed in the float.

If with decreasing oil level, the float reaches the switching points, the contacts are magnetically operated. The spool positions of the contacts are maintained until the float passes the switching points once again due to the increasing oil level.

The switching points can be adjusted in the device.

Rotating the contacts by 180° changes the switching function; the normally closed contact type becomes a normally open contact or vice versa.

 

Resistance measuring chain:

The sliding tube contains the resistance measuring chain (contact distance 5 mm / resolution) for the continuous recording of the filling level height. If the individual reed contact is switched (closed) by the permanent magnet located in the float, a resistance will in each case be activated.

The added resistance value is converted by a transformer into 4 … 20 mA.

 

Temperature function

Temperature contact:

At the lowest point within the sliding tube, the bi-metal temperature contacts are attached to the circuit board and secured by means of a shrinkable tubing (the same procedure is used with the versions with PT 100 temperature sensor and resistance thermometer with analog output 4 … 20 mA). If the desired temperature switching point is reached, the bi-metal contact is opened or closed.

 

Temperature sensor PT100:

The PT100 consists of a temperature sensor guaranteeing continuous temperature recording. In this connection, the max. cable length of [si]6 m[/si][mp]236 in[/imp] is to be observed.

 

Resistance thermometer with measuring transducer, output 4 … 20 mA:

The PT100 resistance thermometer with measuring transducer is also attached to the circuit board in the sliding tube. The temperature-dependent signal is converted into a linear current change from 4 … 20 mA.

 

Display and control unit function (version D)

The micro-processor controlled display and control unit processes the analog input signals for the analysis of the level and temperature control. Level and temperature can be set at the control unit in an easy menu navigation by means of pushbuttons and the settings can be read off at the LED display.

The display and control unit has a four-digit, red seven-segment LED display and 3 pushbuttons for the operation as well as up to 4 LEDs integrated in the front plate for the display of alarm conditions.

Apart from that, the device has four freely adjustable PNP switching outputs plus the adjustable switch-back points (version D1) and alternatively (version D2) two freely programmable PNP switching outputs and 2 x 4 … 20 mA output for the continuous measurement of oil level and temperature. The switching conditions are shown in the display.

 

The output 4 … 20 mA can optionally be set to 0 … 10 V, 2 … 10 V or 0 … 5 V.

Depending on the setting, the display shows the measured temperature or filling level value in the desired unit (°C, °F, L, cm, %, inch or mm). By default, the temperature display is set to °C.

During the setting and/or programming of the corresponding process parameters, the parameter values and/or the related menu items are shown in the display.

In case of energy supply failure, all input values will be stored, the max/min values can be called from a permanent memory, if necessary.

 

Parameterization

The menu navigation is based on the VDMA standard sheet for fluid sensors 24574-1.

The operating menu is designed hierarchically as tree structure.

That means that frequently used functions and adjustment points are quickly accessible and rarely used menu items can be found in a submenu.

Using the ▲ and ▼ keys, the corresponding parameters are set and/or the next menu item is displayed.

Using the ► key, the selected menu item is selected and/or the set parameter is accepted and stored.

The parameter may be a numerical value and a selection of functions (e.g. NO [output as normally open contact], NC [output as normally closed contact] or i1 [analog output 4 … 20 mA]).

After confirmation of a parameter or function selection by means of the ► key, the display will switch back to the current menu item. Then, you can use ▲ and ▼ to display the next menu item and ► to select it.

Ordering code

01

02

03

04

05

06

07

08

ABZM

S

41

1X

/

/

/

Power unit accessories

01

Measuring devices

ABZM

02

Float switches

S

03

Version

41

04

Component series 10 ... 19 (10 ... 19: unchanged installation and connection dimensions)

1X

Ordering length in mm

05

L = 370 mm

0370

L = 500 mm

0500

L = 800 mm

0800

L = 1000 mm

1000

L = 1200 mm

1200

Level and temperature measurement 1)

06

Number of level contacts normally closed contact/normally open contact 2)

1 x

M1

2 x

M2

3 x

M3

4 x

M4

Number of level contacts normally closed contact/normally open contact and temperature contact 70 °C normally closed contact 3)

1 x

M1-T70F

2 x

M2-T70F

3 x

M3-T70F

Number of level contacts normally closed contact/normally open contact and temperature sensor PT100, output resistance signal Ω

1 x

M1-TS

2 x

M2-TS

3 x

M3-TS

Number of level contacts normally closed contact/normally open contact and resistance thermometer, output 4 … 20 mA

1 x

M1-TA

2 x

M2-TA

3 x

M3-TA

06

Resistance measuring chain (level) and resistance thermometer analog output 4 … 20 mA

RTA

Display and control unit with resistance measuring chain and resistance thermometer with four programmable PNP switching outputs

D1

Display and control unit with resistance measuring chain and resistance thermometer with two programmable PNP switching outputs and two analog outputs 4 … 20 mA

D2

Voltage

07

VDC 10 … 36

DC

VAC 10 … 230

AC

Without temperature contact

no code

Electrical connection 4)

08

Connector, 4-pole M12 x 1 (standard)

K24

Connector 4-pole (3 + PE) DIN EN 175301-803

K14

Connector 7-pole (6 + PE) DIN EN 175201-804

K6

1) Combination possibilities function / electrical connection
2) Pinout, see “Electrical connection”
3) Option:
Temperature contact 60 °C = T60F
Temperature contact 80 °C = T80F
4) Mating connectors, separate order (see R.08006)
Order example:
Float switch with flange connection, ordering length 370 mm, two pre-set level contacts and temperature contact, normally closed contact at 70 °C, connector K24:
ABZMS-S-41-1X/0370/M2-T70/DC-K24

Function

Voltage

VDC 10-36

VAC 10-230

K24

2K24

K14

K6

K14

K6

M1

X

X

X

X

X

M2

X

X

X

X

X

M3

X

M4

X

M1-T70F

X

X

X

X

X

M2-T70F

X

X

X

M3-T70F

X

M1-TS

X

X

M2-TS

X

X

M3-TS

X

M1-TA

X

X

M2-TA

X

X

M3-TA

X

RTA

X

D1

X

D2

X

Resistance

Hydraulic fluids

Mineral oils

Mineral oil

HLP

according to DIN 51524

Resistant

Flame-resistant hydraulic fluids

Emulsions

HFA-E

according to DIN 24320

Water solutions

HFC

according to VDMA 24317

Phosphoric acid esters

HFD-R

Organic esters

HFD-U

Fast bio-degradable hydraulic fluids

Triglycerides (rape seed oil)

HETG

according to VDMA 24568

Synthetic esters

HEES

Polyglycols

HEPG

electrical

Plug-in connection

4-pole M12 x 1 (material: metal) (K24)
4-pole (3 + PE) DIN EN 175301-803 (K14)
7-pole (6 + PE) DIN EN 175201-804 (K6)

Reed contacts of the float switches
with connection K24, K14, K6/DC

Switching voltage range

V DC

10 … 36

Maximum switching current

A

0.5

Maximal contact load

VA

10

Temperature contacts of the float switches
with connection K24, K14, K6/DC

Switching voltage range

V DC

10 … 50

Maximum switching current

A

0.5

Maximal contact load

VA

10

Maximum switching cycles

100000

Response tolerance

K

± 3

Hysteresis

K

≤10

Maximum temperature change velocity

K/min

1

Reed contacts of the float switches
with connection K14 according to DIN EN 175301-803 / K6 according to DIN EN 175201-804/AC

Switching voltage range

V AC/DC

10 … 230

Maximum switching current

A

0.5

Maximal contact load

VA

10

Temperature contacts of the float switches
with connection K14 according to DIN EN 175301-803 / K6 according to DIN EN 175201-804/AC

Switching voltage range

V AC/DC

10 … 230

Maximum switching current

A

2.5

Maximal contact load

VA

100

Maximum switching cycles

100000

Response tolerance

K

± 3

Hysteresis

K

≤10

Maximum temperature change velocity

K/min

1

Temperature sensor Pt100

Sensor element

Pt100 class B DIN EN 60751

Temperature measuring range

°C

0 … 100

Accuracy

K

± 0.8

Resistance measuring chain and resistance thermometer
with connection K24 for mating connector M12 x 1; 4-pole

Outlet 1)

mA

4 … 20

Resolution resistance measuring chain

mm

5

Maximum load resistance

(U ‒ 9 V) / (0.02 A)

Temperature measuring range

°C

0 … 100
1) Alternatively 0 … 20, 2 … 10 or 0 … 5 V adjustable

Display and control unit

Power supply

V DC

10 … 32

Display range

°C

-20 … +120

Alarm adjustment range

Temperature

°C

​0 … ​100

Level

%

​0 … ​100

l

​0 … ​999

Switching points

4 programmable switching outputs (2 level + 2 temperature)

Housing design

PA, IP65 (antistatisch)

Current consumption upon switch-on

more than 100 ms

mA

≈ 100

Current consumption during operation

with UB 24 V

mA

≈50

Switching output

 

PNP

Maximum switching power

A

0.5

Operation

3 keys

For applications outside these parameters, please consult us!

With two switching contacts

technical illustration-ABZMS-41-1X/1200/RTA/DC-K24-Level display & meas. equipments   (Std)

With two switching contacts and one temperature contact

technical illustration-ABZMS-41-1X/1200/RTA/DC-K24-Level display & meas. equipments   (Std)

With resistance measuring chain/resistance thermometer

technical illustration-ABZMS-41-1X/1200/RTA/DC-K24-Level display & meas. equipments   (Std)

With display and control unit, resistance measuring chain/resistance thermometer

technical illustration-ABZMS-41-1X/1200/RTA/DC-K24-Level display & meas. equipments   (Std)

Connection versions and pin assignment

technical illustration-ABZMS-41-1X/1200/RTA/DC-K24-Level display & meas. equipments   (Std)technical illustration-ABZMS-41-1X/1200/RTA/DC-K24-Level display & meas. equipments   (Std)technical illustration-ABZMS-41-1X/1200/RTA/DC-K24-Level display & meas. equipments   (Std)technical illustration-ABZMS-41-1X/1200/RTA/DC-K24-Level display & meas. equipments   (Std)technical illustration-ABZMS-41-1X/1200/RTA/DC-K24-Level display & meas. equipments   (Std)

By default, the switching point L1 is set as normally closed contact and switching points L2 to L4 as normally open contact. The switching points can be adjusted in the device.

Rotating the contacts by 180° changes the switching function; the normally closed contact type becomes a normally open contact or vice versa.

Pre-set switching points Type M

Float switch Ordering

length "L"

Number of switching points

Switching points pre-set

 

1

2

3

4

mm

mm

mm

mm

mm

370 L1 220 220 220 280
L2 - 140 140 220
L3 - - 60 140
L4 - - - 60
500 L1 280 280 280 340
L2 - 160 160 280
L3 - - 60 160
L4 - - - 60
800 L1 600 600 600 700
L2 - 400 400 600
L3 - - 200 400
L4 - - - 200
1000 L1 700 700 700 800
L2 - 500 500 700
L3 - - 200 500
L4 - - - 200
1200 L1 800 800 800 1000
L2 - 600 600 800
L3 - - 300 600
L4 - - - 300

Dimensions:

Float switch with level and temperature contacts (version M - T..F)Float switch with resistance measuring chain and resistance thermometer (version RTA)

Dimensions in mm

technical illustration-ABZMS-41-1X/1200/RTA/DC-K24-Level display & meas. equipments   (Std)

1

Switching points

2

Flat seal

3

Stilling tube from L = 500 mm

4

Name plate

5

Installation opening of the tank

6

Mating connector for plug-in connections K24 (M12 x 1), see table "Mating connector"

7

Connector K24; 4-pole M12 x 1

8

Stroke limitation ring set to 20 mA (Type RTA)

Version M: L1 = min. 70 mm

Version RTA: L1 = L ‒ min. 57 mm

Dimensions: Float switch with display and control unit (version D..)

Dimensions in mm

technical illustration-ABZMS-41-1X/1200/RTA/DC-K24-Level display & meas. equipments   (Std)

1

Measuring range 4 … 20 mA

2

Flat seal

3

Stilling tube from L = 500 mm

4

Name plate

5

Installation opening of the tank

6

Mating connector for plug-in connections K24 (M12 x 1), see table "Mating connector"

7

Connector K24; 4-pole M12 x 1

8

Stroke limitation ring set to 20 mA (Type RTA)

9

LEDs for the display of alarm switching points

Oil volume specification for float switch

Type M with two switching contacts

technical illustration-ABZMS-41-1X/1200/RTA/DC-K24-Level display & meas. equipments   (Std)

1

Residual quantity with switching point L1

2

Residual quantity with switching point L2

Float switch Ordering

length "L"

Switching points pre-set

Residual hydraulic fluid volume at switching point

 

 

AB 40-40, AB 40-43, AB 40-44

L1

L2

NG

L1

L2

mm

mm

mm

l

l

370 220 140 63 28 42
220 140 100 45 67
220 140 160 74 100
220 140 250 120 174
220 140 400 190 277
220 140 630 365 475
220 140 800 460 600
500 280 160 1000 490 740
280 160 1250 780 1030
280 160 1600 990 1310
280 160 2000 1380 1730

Attention!

Before the commissioning, the switching contacts are to be set according to the necessary operating conditions.

 

Adjustment of the switching height

The contacts installed in the float switch are screwed to a contact strip within the sliding tube. They are set to the switching points according to the preceding table and can be adjusted to higher or lower values retroactively (observe minimum distances!). For adjusting the contacts, proceed as follows:

Interrupt the voltage supply Loosen the plug-in connection Loosen the screws of the connector base and pull out the connector base with the contact strip Loosen the contact from the strip and fasten it at the desired position (it can be adjusted in steps of 10 mm) Carefully insert the contact strip Fasten the connector base by means of the screws Re-establish the plug-in connection and the power connection

Type RTA, D1 and D2

in tank according to AB 40-40, AB 40-43 and AB 40-44

Tank size DN100 to 800
Dimensions in mm

technical illustration-ABZMS-41-1X/1200/RTA/DC-K24-Level display & meas. equipments   (Std)

Tank size DN1000 to 2000
Dimensions in mm

technical illustration-ABZMS-41-1X/1200/RTA/DC-K24-Level display & meas. equipments   (Std)

Installation opening of the tank cover

Dimensions in mm

technical illustration-ABZMS-41-1X/1200/RTA/DC-K24-Level display & meas. equipments   (Std)

Standard breakthrough AB 03-39.73 similar to DIN 24557 part 2

Fastening screws:

6 HEXAGONSOCKET HEAD CAP SCREWS ISO4762-M5X18-8.8-A2P; Material no. R900202612

Assembly information

Vertical installation according to technical data (see "Technical Data") Avoid flows Do not expose the switch to strong impact and bends Avoid external magnetic fields. They may impair the function of the reed contacts.

 

Electrical connections:

Electrical connections may only be performed by specialists Before performing any works at electrical parts, the voltage supply is to be interrupted Tighten round connector M12 x 1 or mating connectors after connection Only plug in the round connector M12 x 1 or mating connector if it is de-energized Do not overload the contacts (see technical data) In case of inductive load, provide for a protective circuit!

Normative reference

AB 24-02

Cable sets and distributors

 

AB 40-40

Tank made of steel, form AN, cover form C, oil pan according to WHG

 

AB 40-43

Tank made of steel, cover form C

 

AB 40-44

Tank made of steel, with frame

 

R.08006

Mating connectors for controlling electric valves and sensors

 

DIN 24320

Flame-resistant fluids - Hydraulic fluids of categories HFAE and HFAS - Properties and requirements

 

DIN 51524

Hydraulic fluids; hydraulic oils

 

DIN EN 175201-804

Detail specification - Circular connectors - Round contacts, size diameter 1.6mm, threaded coupling; German version EN 175201-804:1999

 

DIN EN 175301-803

Detail specification: Rectangular connectors - Flat contacts, 0,8mm thickness, locking screw not detachable; German version EN 175301-803:1999

 

DIN EN 60751

Industrial platinum resistance thermometers and platinum temperature sensors (IEC 60751:2008)

 

DIN EN 60529

Protection classes by housing

 

VDMA 24317

Fluid technology – Flame-resistant fluids – Technical minimum requirements

 

VDMA 24568

Fluid technology – Fast bio-degradable fluids – Technical minimum requirements

 

VDMA 24574-1

Fluid technology – Terms, menu navigation and electrical connection for fluid sensors

Mating connectors

For detailed information see data sheet 08006

Mating connector for connector K14 according to DIN EN 175301-803

Mating connector for connector K6 according to DIN EN 175201-804

Denomination

Part number

Denomination

Part number

LEITUNGSDOSE 4P Z14 M SW SPEZ

R901017012

LEITUNGSDOSE 7P Z6 N6RFFK

R900002803

 

Mating connector for connector K24

Mating connector for connector K24 with potted-in PVC cable, 3 m long

Denomination

Part number

Denomination

Part number

LEITUNGSDOSE 4P Z24 SPEZ

R900031155

LEITUNGSDOSE 4P Z24M12X1+3MSPEZ

R900064381

Mating connectors for mechanical pressure switches with connector “K14”, without circuitry, standard

4P Z14

technical illustration-ABZMS-41-1X/1200/RTA/DC-K24-Level display & meas. equipments   (Std)

Mating connectors for mechanical pressure switches with connector “K14”, without circuitry, standard

4P Z14

For mechanical pressure switches with connector “K14”, according to EN 175301-803 and ISO 4400, 3-pole + PE, “large cubic connector”

Data sheet

Spare parts & repair

Mating connectors for sensors and valves with connector “K24”, “K35” and “K72”, M12 x 1

4P Z24

technical illustration-ABZMS-41-1X/1200/RTA/DC-K24-Level display & meas. equipments   (Std)

Mating connectors for sensors and valves with connector “K24”, “K35” and “K72”, M12 x 1

4P Z24

For sensors and valves with connector “K24”, “K35” and “K72” Mating connectors M12, 4-pole, line cross-section 0.75 mm2

Data sheet

Spare parts & repair

Mating connectors for sensors and valves with connector “K24”, “K35” and “K72”, M12 x 1, with assembled connection line

4P Z24 +

technical illustration-ABZMS-41-1X/1200/RTA/DC-K24-Level display & meas. equipments   (Std)

Mating connectors for sensors and valves with connector “K24”, “K35” and “K72”, M12 x 1, with assembled connection line

4P Z24 +

For sensors and valves with connector “K24”, “K35” and “K72” Mating connectors M12, 4-pole, line cross-section 0.75 mm2

Data sheet

Spare parts & repair

Mating connectors for mechanical position switches, mechanical pressure switches and valves with central connection with connector “K6” and “DK6L”, 6-pole + PE

7P Z6

technical illustration-ABZMS-41-1X/1200/RTA/DC-K24-Level display & meas. equipments   (Std)

Mating connectors for mechanical position switches, mechanical pressure switches and valves with central connection with connector “K6” and “DK6L”, 6-pole + PE

7P Z6

Mating connectors for mechanical position switches, mechanical pressure switches and valves with central connection with connector “K6”

Data sheet

Spare parts & repair

Use in explosive areas according to directive 94/9/EC (ATEX)

The float switches ABZMS-41 are not suitable for the use in explosive areas.