BOSCH REXROTH
R-IBIL24/230DOR4/W-PAC
R911170758
I/O Rexroth Inline Digital: Output
BOSCH REXROTH
MATERIAL: R911170758
SUMMARY: I/O Rexroth Inline Digital: Output
Quantity in stock: 2
Quantity Details:- Hydrotech Stock: 0 can ship April 22, 2024
- Factory Stock: 2 can ship June 10, 2024
This module is designed for use within an Inline station. It has four SPDT relay contacts that are brought out floating.
General data
Type |
R-IB IL 24/230 DOR 4/W-PAC | |
Weight 1) |
g |
153 |
Operating mode |
Process data operation with 4 bits | |
Actuator connection type |
Floating SPDT relay contact | |
Ambient temperature (operation) |
-25 °C ... +55 °C | |
Ambient temperature (storage/transport) |
-25 °C ... +85 °C | |
Permissible relative humidity (operation) |
10 % ... 95 % acc. to DIN EN 61131-2 | |
Permissible relative humidity (storage/transport) |
10 % ... 95 % acc. to DIN EN 61131-2 | |
Air pressure (operation) |
80 kPa ... 106 kPa (up to 2000 m above sea level) | |
Air pressure (storage/transport) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
Protection type |
IP20, IEC 60529 |
1) | Including plug |
Connection data
Type |
R-IB IL 24/230 DOR 4/W-PAC | |
Designation |
Inline connection plug | |
Connection type |
Tension spring modules | |
Conductor cross-section solid/flexible/AWG |
0.2 mm² ... 1.5 mm² 0.2 mm² ... 1.5 mm² 24 ... 16 |
Interface local bus
Type |
R-IB IL 24/230 DOR 4/W-PAC | |
Connection type |
Data ranking | |
Transmission speed |
kBit/s |
500 |
Inline potentials/performance balance
Type |
R-IB IL 24/230 DOR 4/W-PAC | ||
Logic voltage |
V DC |
7.5 | |
Current consumption from UL |
OFF |
22 mA | |
ON |
187 mA | ||
Power consumption from UL |
OFF |
0.17 W | |
ON |
1.4 W |
Supply of module electronics and peripherals via bus coupler/power feed module
Type |
R-IB IL 24/230 DOR 4/W-PAC | |
Connectivity technology |
Potential jumpers |
Relay output
Type |
R-IB IL 24/230 DOR 4/W-PAC | |||
Number of outputs |
4 | |||
Contact material |
AgSnO2, hard gold-plated | |||
Transfer resistance of the contact |
At 100 mA/6 V |
50 mΩ | ||
Limiting continous current |
At maximum ambient temperature |
3 A | ||
Maximum switching voltage |
253 V AC 250 V DC |
|||
Maximum switching power 1) |
AC/DC |
750 VA | ||
Minimum load |
5 V 10 mA |
|||
Switching current |
At 30 V DC |
3 A | ||
At 250 V DC |
0.15 A | |||
Maximum inrush current peak 2) |
For lamp loads and capacitive loads |
6 A | ||
Nominal current consumption of the coil (at 20 °C) |
From 7.5 V power supply |
330 mW | ||
Resistance of the coil (at 20 °C) |
±12 Ω |
119 Ω | ||
Maximum switching frequency |
No load |
Switching cycles/minute |
1200 GHz | |
At nominal load |
Switching cycles/minute |
6 GHz | ||
Typical response delay |
5 ms | |||
Typical bouncing time |
5 ms | |||
Typical release time |
6 ms | |||
Service life |
Mechanical |
Switching cycles |
2 x 107 | |
Electrical 3) |
Switching cycles |
105 | ||
Common potentials |
All contacts floating |
1) | See derating |
2) | For T = 200 μs |
3) | With 20 switching cycles/minute |
Power dissipation |
|
Formula for calculating the power dissipation in the module |
|
PEL = PBUS + (PREL) + PL |
|
where: |
|
PEL |
Total power dissipation in the module |
PBUS |
Power dissipation due to the bus operation |
PREL |
Power dissipation in relay coil |
PL |
Power dissipation due to load current over the contacts |
n |
Number of set inputs (n = 1 to 4) |
i |
Running index |
IL |
Load current of output |
Power dissipation of housing dependent on the ambient temperature |
|
PGEH = 2.7 W |
-25 °C < TU ≤ +25 °C |
PGEH = 2.7 W ‒ ((TU ‒ 25 °C) x 0.02 W/°C) |
+25 °C < TU ≤ +55 °C |
where: |
|
PGEH |
Admissible power dissipation of housing |
TU |
Ambient temperature |
Error messages to the higher-level control or computer system
Type |
R-IB IL 24/230 DOR 4/W-PAC | |
Error message |
None |
Air and creepage distances (acc. to EN 50178, VDE 0109, VDE 0110)
Partition section |
Relay contact/bus logic | Contact/contact | Contact/PE | |
Clearance |
mm |
≥ 5.5 | ≥ 3.1 | ≥ 3.1 |
Creepage distance |
mm |
≥ 5.5 | ≥ 3.1 | ≥ 3.1 |
Test voltage |
4 kV, 50 Hz, 1 min. | 1 kV, 50 Hz, 1 min. |
Mechanical tests
Type |
R-IB IL 24/230 DOR 4/W-PAC | |
Vibration resistance 1) |
Load 2 g, 2 h per spatial direction | |
Shock 2) |
Load 2 g for 11 ms, half sinusoidal wave, 3 shocks per spatial direction and orientation |
1) | Acc. to IEC 60068-2-6; EN 60068-2-6 |
2) | Acc. to IEC 60068-2-27; EN 60068-2-27 |
Approvals |
The current approvals can be found at www.boschrexroth.com. |
Dimensions
Type |
R-IB IL 24/230 DOR 4/W-PAC | |
A |
mm |
48.8 |
B |
mm |
120 |
C |
mm |
71.5 |
Note on dimensions |
The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715). |