Hydrotech Acquires Isaacs
Hydrotech ecommerce supports the continental US only

BOSCH REXROTH
R-IBIL24/230DOR4/W-PAC
R911170758

I/O Rexroth Inline Digital: Output

$447.48

BOSCH REXROTH

MATERIAL:  R911170758

SUMMARY:  I/O Rexroth Inline Digital: Output

Quantity in stock: 2

Quantity Details:
  • Hydrotech Stock: 0 can ship April 22, 2024
  • Factory Stock: 2 can ship June 10, 2024
Add to Cart

This module is designed for use within an Inline station. It has four SPDT relay contacts that are brought out floating.

General data

Type

R-IB IL 24/230 DOR 4/W-PAC

Weight 1)

g

153

Operating mode

Process data operation with 4 bits

Actuator connection type

Floating SPDT relay contact

Ambient temperature (operation)

-25 °C ... +55 °C

Ambient temperature (storage/transport)

-25 °C ... +85 °C

Permissible relative humidity (operation)

10 % ... 95 % acc. to DIN EN 61131-2

Permissible relative humidity (storage/transport)

10 % ... 95 % acc. to DIN EN 61131-2

Air pressure (operation)

80 kPa ... 106 kPa (up to 2000 m above sea level)

Air pressure (storage/transport)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Protection type

IP20, IEC 60529
1) Including plug

Connection data

Type

R-IB IL 24/230 DOR 4/W-PAC

Designation

Inline connection plug

Connection type

Tension spring modules

Conductor cross-section solid/flexible/AWG

0.2 mm² ... 1.5 mm²
0.2 mm² ... 1.5 mm²
24 ... 16

Interface local bus

Type

R-IB IL 24/230 DOR 4/W-PAC

Connection type

Data ranking

Transmission speed

kBit/s

500

Inline potentials/performance balance

Type

R-IB IL 24/230 DOR 4/W-PAC

Logic voltage

V DC

7.5

Current consumption from UL

OFF

22 mA

ON

187 mA

Power consumption from UL

OFF

0.17 W

ON

1.4 W

Supply of module electronics and peripherals via bus coupler/power feed module

Type

R-IB IL 24/230 DOR 4/W-PAC

Connectivity technology

Potential jumpers

Relay output

Type

R-IB IL 24/230 DOR 4/W-PAC

Number of outputs

4

Contact material

AgSnO2, hard gold-plated

Transfer resistance of the contact

At 100 mA/6 V

50 mΩ

Limiting continous current

At maximum ambient temperature

3 A

Maximum switching voltage

253 V AC
250 V DC

Maximum switching power 1)

AC/DC

750 VA

Minimum load

5 V
10 mA

Switching current

At 30 V DC

3 A

At 250 V DC

0.15 A

Maximum inrush current peak 2)

For lamp loads and capacitive loads

6 A

Nominal current consumption of the coil (at 20 °C)

From 7.5 V power supply

330 mW

Resistance of the coil (at 20 °C)

±12 Ω

119 Ω

Maximum switching frequency

No load

Switching cycles/minute

1200 GHz

At nominal load

Switching cycles/minute

6 GHz

Typical response delay

5 ms

Typical bouncing time

5 ms

Typical release time

6 ms

Service life

Mechanical

Switching cycles

2 x 107

Electrical 3)

Switching cycles

105

Common potentials

All contacts floating
1) See derating
2) For T = 200 μs
3) With 20 switching cycles/minute

Power dissipation

Formula for calculating the power dissipation in the module

PEL = PBUS + (PREL) + PL

technical illustration-R-IBIL24/230DOR4/W-PAC-I/O Rexroth Inline Digital: Output

where:

PEL

Total power dissipation in the module

PBUS

Power dissipation due to the bus operation

PREL

Power dissipation in relay coil

PL

Power dissipation due to load current over the contacts

n

Number of set inputs (n = 1 to 4)

i

Running index

IL

Load current of output

Power dissipation of housing dependent on the ambient temperature

PGEH = 2.7 W

-25 °C < TU ≤ +25 °C

PGEH = 2.7 W ‒ ((TU ‒ 25 °C) x 0.02 W/°C)

+25 °C < TU ≤ +55 °C

where:

PGEH

Admissible power dissipation of housing

TU

Ambient temperature

Error messages to the higher-level control or computer system

Type

R-IB IL 24/230 DOR 4/W-PAC

Error message

None

Air and creepage distances (acc. to EN 50178, VDE 0109, VDE 0110)

Partition section

Relay contact/bus logic Contact/contact Contact/PE

Clearance

mm

≥ 5.5 ≥ 3.1 ≥ 3.1

Creepage distance

mm

≥ 5.5 ≥ 3.1 ≥ 3.1

Test voltage

4 kV, 50 Hz, 1 min. 1 kV, 50 Hz, 1 min.

Mechanical tests

Type

R-IB IL 24/230 DOR 4/W-PAC

Vibration resistance 1)

Load 2 g, 2 h per spatial direction

Shock 2)

Load 2 g for 11 ms, half sinusoidal wave, 3 shocks per spatial direction and orientation
1) Acc. to IEC 60068-2-6; EN 60068-2-6
2) Acc. to IEC 60068-2-27; EN 60068-2-27

Approvals

The current approvals can be found at www.boschrexroth.com.

technical illustration-R-IBIL24/230DOR4/W-PAC-I/O Rexroth Inline Digital: Output

Dimensions

Type

R-IB IL 24/230 DOR 4/W-PAC

A

mm

48.8

B

mm

120

C

mm

71.5

Note on dimensions

The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715).