BOSCH REXROTH
S20-DI-32/1
R911172533
All Other Products

I/O IndraControl S20 Digital:Input

$594.37

BOSCH REXROTH

MATERIAL:  R911172533

SUMMARY:  I/O IndraControl S20 Digital:Input

Quantity in stock: 2

Quantity Details:
  • Hydrotech Stock: 1 can ship March 29, 2024
  • Factory Stock: 1 can ship May 17, 2024
Add to Cart

This module is designed for use within an S20 station. It is used to acquire digital signals. The filter times for the inputs can be adjusted to increase the interference immunity. Filter times of 100 μs allow the user to applicatively implement a counting function using an input frequency of maximum 5 kHz.

General data

Type

S20-DI-32/1

Color

Gray

Weight

g

167

Ambient temperature (operation)

-25 °C ... +60 °C

Ambient temperature (storage/transport)

-40 °C ... +85 °C

Permissible relative humidity (operation)

5 % ... 95 % acc. to DIN EN 61131-2

Permissible relative humidity (storage/transport)

5 % ... 95 % acc. to DIN EN 61131-2

Air pressure (operation)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Air pressure (storage/transport)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Protection type

IP20

Protection class

III, IEC 61140, EN 61140, VDE 0140-1

Connection data

Type

S20-DI-32/1

Designation

S20 connector

Connection type

Spring-cage connection with direct plug technology

Conductor cross-section solid/flexible/AWG

0.2 mm² ... 1.5 mm²
0.2 mm² ... 1.5 mm²
24 ... 16

Stripping length

mm

8

Interface local bus

Type

S20-DI-32/1

Connection type

Bus base module

Transmission speed

MBit/s

100

Power supply to logic

Type

S20-DI-32/1

Logic voltage UBus 1)

V DC

5

Maximum current consumption from UBus

mA

120

Maximum power consumption from UBus

mW

600
1) Via bus base module

Power supply to peripherals

Type

S20-DI-32/1

Feed to digital input modules UI

V DC

24

Maximum permitted voltage range 1)

​19.2 V DC ... ​30 V DC

Current consumption from UI

mA

≥ 50

Typical power consumption from UI

mW

960

Maximum power consumption from UI

W

1.2

Overvoltage/reverse polarity protection supply voltage

Electronic (35 V, 0.5 s) / parallel diode; with external security 5 A (only for commissioning)

Guarantee 2)

A

≤ 8
1) Including all tolerances, including ripple
2) Reverse polarity protection up to 5 A

Digital inputs

Type

S20-DI-32/1

Number of digital inputs

32

Connection type

Direct plug-in technology

Connectivity technology

1-wire technology

Description of the input

Acc. to EN 61131-2 type 1 and type 3

Nominal input voltage

V DC

24

Nominal input current

mA

2.4

Current profile

Linear up to nominal current, then constant around 2.4 mA

Input voltage range "0" signal

-3 V DC ... 5 V DC

Input voltage range "1" signal

11 V DC ... 30 V DC

Input filter time

3000 μs (default); 1000 μs; < 100 μs

Reverse polarity protection

Parallel diode (30 V, 5 s)

Error messages to the higher-level control or computer system

Type

S20-DI-32/1

Error message

Failure in peripheral supply

Electrical isolation/insulation of the voltage ranges

Type

S20-DI-32/1

Test distance

Test voltage

5 V supply (logic)/24 V supply (peripherals)

500 V AC, 50 Hz, 1 min.

5 V supply (logic)/function earth

500 V AC, 50 Hz, 1 min.

24 V supply (peripherals)/function earth

500 V AC, 50 Hz, 1 min.

Mechanical tests

Type

S20-DI-32/1

Vibration resistance 1)

g

5

Shock 2)

25 g, 11 ms duration, semi-sinusoidal shock pulse

Continuous shock 3)

g

10
1) Acc. to IEC 60068-2-6
2) Acc. to IEC 60068-2-27
3) Acc. to EN 60068-2-29

Conformity

Type

S20-DI-32/1

Conforms with

Testing of interference immunity acc. to EN 61000-6-2

Discharge of static electricity (ESD)

Criterion B; 6 kV contact discharge; 8 kV air discharge acc. to EN 61000-4-2/IEC 61000-4-2

Electro-magnetic fields

Criterion A; field strength: 10 V/m acc. to EN 61000-4-3/IEC 61000-4-3

Fast transients (burst)

Criterion B; 2 kV acc. to EN 61000-4-4/IEC 61000-4-4

Transient overvoltage (surge)

Criterion B; supply lines DC: ±0.5 kV/±0.5 kV (symmetric/asymmetric) acc. to EN 61000-4-5/IEC 61000-4-5

Line-fed disturbances

Criterion A; test voltage 10 V acc. to EN 61000-4-6/IEC 61000-4-6

Testing of disturbance transmission acc. to EN 61000-6-3

Radio disturbance characteristics

Class B acc. to EN 55022

Approvals

The current approvals can be found at www.boschrexroth.com.

technical illustration-S20-DI-32/1-I/O IndraControl S20 Digital:Input

Dimensions

Type

S20-DI-32/1

A

mm

53.6

B

mm

126.1

C

mm

54

Note on dimensions

The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715).