Hydrotech Acquires Isaacs
Hydrotech ecommerce supports the continental US only

BOSCH REXROTH
R-IBIL24PWRIN/R/L-0.8A-PAC
R911172896
All Other Products

I/O Rexroth Inline PWR modules

$402.75

BOSCH REXROTH

MATERIAL:  R911172896

SUMMARY:  I/O Rexroth Inline PWR modules

Quantity in stock: 2

Quantity Details:
  • Hydrotech Stock: 0 can ship April 26, 2024
  • Factory Stock: 2 can ship June 14, 2024
Add to Cart

This module is designed for use within an Inline station. If the maximum load on the bus coupler for the logic voltage (UL) has been reached, then you can use this module in order to provide this voltage again. To do so, a 24 V DC voltage (U24 V) is applied at the module; this voltage generates the logic voltage (UL).

General data

Type

R-IB IL 24 PWR IN/R/L-0.8A-PAC

Color

Gray

Weight 1)

g

65

Mounting type

Support rail

Ambient temperature (operation)

-25 °C ... +55 °C

Ambient temperature (storage/transport)

-25 °C ... +85 °C

Permissible relative humidity (operation)

10 % ... 95 %, EN 61131-2

Permissible relative humidity (storage/transport)

10 % ... 95 %, EN 61131-2

Air pressure (operation)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Air pressure (storage/transport)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Protection type

IP20

Protection class

III, IEC 61140, EN 61140, VDE 0140-1
1) Including plug

Connection data

Type

R-IB IL 24 PWR IN/R/L-0.8A-PAC

Designation

Inline connection plug

Connection type

Spring-cage connection

Conductor cross-section solid/flexible/AWG

0.08 mm² ... 1.5 mm²
0.08 mm² ... 1.5 mm²
28 ... 16

Interface local bus

Type

R-IB IL 24 PWR IN/R/L-0.8A-PAC

Transmission speed

kBit/s

MBit/s

500
2

Inline potentials/performance balance

Type

R-IB IL 24 PWR IN/R/L-0.8A-PAC

24 V power feed U24V for generating UL

V DC

24

Supply voltage range U24V

19.2 V DC ... 30 V DC (including all tolerances, including ripple)

Minimum current consumption from U24V

mA

13

Maximum current consumption from U24V

mA

274

Logic voltage UL 1)

7.5 V DC ±5 %

Power supply to UL

A

≤ 0.8

Overvoltage protection

Yes; input protection diodes are destroyed by permanent overload. Pulse loads up to 1500 W are short-circuited by the input protection diode.

Reverse polarity protection

Serial diode in the feed path of the mains power supply; in the event of a fault, only low current flows. In the event of a fault no fuse is tripped in the external mains power supply.
If you want to install a fuse for the 24-V power feed, use a fuse with 2 A time-lag.
1) Via potential jumpers

Power dissipation

Type

R-IB IL 24 PWR IN/R/L-0.8A-PAC

Power dissipation (device)

≤0.6 W (device total)

PROFIBUS telegram data

Type

R-IB IL 24 PWR IN/R/L-0.8A-PAC

Need for parameter data

byte

0

Need for configuration data

byte

0

Electrical isolation/insulation of the voltage ranges

Type

R-IB IL 24 PWR IN/R/L-0.8A-PAC

Test distance

Test voltage

7.5 V-logic, 24 V analog supply/function earth

500 V AC, 50 Hz, 1 min.

7.5 V logic, 24 V analog supply/24 V main, 24 V segment supply

500 V AC, 50 Hz, 1 min.

24 V main, 24 V segment supply/function earth

500 V AC, 50 Hz, 1 min.

Error messages to the higher-level control or computer system

Type

R-IB IL 24 PWR IN/R/L-0.8A-PAC

Error message

None

Approvals

The current approvals can be found at www.boschrexroth.com.

technical illustration-R-IBIL24PWRIN/R/L-0.8A-PAC-I/O Rexroth Inline PWR modules

Dimensions

Type

R-IB IL 24 PWR IN/R/L-0.8A-PAC

A

mm

12.2

B

mm

120

C

mm

71.5

Note on dimensions

The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715).