BOSCH REXROTH
R-IBILAI8/IS-PAC
R911308494
I/O Rexroth Inline Analogue modules
BOSCH REXROTH
MATERIAL: R911308494
SUMMARY: I/O Rexroth Inline Analogue modules
Quantity in stock: 1
Quantity Details:- Hydrotech Stock: 0 can ship April 25, 2024
- Factory Stock: 1 can ship June 13, 2024
This module is designed for use within an Inline station. It is used to acquire analog current signals from active and passive sensors.
General data
Type |
R-IB IL AI 8/IS-PAC | |
Weight 1) |
g |
215 |
Operating mode |
Process data operation with 4 bytes | |
Sensor connection type |
2-, 3-wire technology | |
Ambient temperature (operation) |
-25 °C ... +55 °C | |
Ambient temperature (storage/transport) |
-25 °C ... +85 °C | |
Permissible relative humidity (operation) |
10 % ... 95 % acc. to DIN EN 61131-2 | |
Permissible relative humidity (storage/transport) |
10 % ... 95 % acc. to DIN EN 61131-2 | |
Air pressure (operation) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
Air pressure (storage/transport) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
Protection type |
IP20, IEC 60529 | |
Protection class |
III, VDE 0106, IEC 60536 |
1) | Including plug |
Connection data
Type |
R-IB IL AI 8/IS-PAC | |
Designation |
Inline connection plug | |
Connection type |
Tension spring modules | |
Conductor cross-section solid/flexible/AWG |
0.2 mm² ... 1.5 mm² 0.2 mm² ... 1.5 mm² 24 ... 16 |
Interface local bus
Type |
R-IB IL AI 8/IS-PAC | |
Connection type |
Data ranking | |
Transmission speed |
kBit/s |
500 |
Inline potentials/performance balance
Type |
R-IB IL AI 8/IS-PAC | |
Logic voltage UL |
V DC |
7.5 |
Typical current consumption from UL |
mA |
52 |
Maximum current consumption from UL |
mA |
65 |
Peripheral supply voltage UANA |
V DC |
24 |
Typical current consumption from UANA |
mA |
31 |
Maximum current consumption from UANA |
mA |
40 |
Typical power consumption total |
mW |
1134 |
Supply of module electronics and peripherals via bus coupler/power feed module
Type |
R-IB IL AI 8/IS-PAC | |
Connectivity technology |
Potential jumpers |
Sensor supply voltage UIS via feed from UM
Type |
R-IB IL AI 8/IS-PAC | |
Nominal value UIS |
V |
+ 24 |
Permissible range |
+10 V … +30 V | |
Permissible temperature range (Tu) |
-25 °C ... +55 °C | |
Nominal current IIS per channel |
mA |
+ 20 |
Nominal current IISMAX ‒ peripheral plug 1) |
mA |
+ 50 |
Guarantee |
Internal, electronic fuse, short-circuit protected - - - |
1) | Total current for two channels |
Analog inputs
Type |
R-IB IL AI 8/IS-PAC | ||
Number of analog inputs 1) |
8 | ||
A/D conversion time |
µs |
≤ 10 | |
Measurement representation |
16 bits (15 bits + sign) 13 bits (12 bits + sign) 16 bits (15 bits + sign) 16 bits (15 bits + sign) 16 bits - |
||
Data formats |
IB IL, IB ST, IB RT, standardized representation, PIO | ||
Average |
None or averaged over 4, 16 or 32 measured valuesdefault setting: 16 measured values | ||
Process data update |
Bus synchronous | ||
Firmware runtime depending on the command |
0x00hex |
µs |
< 800 |
5x00hex |
µs |
< 850 | |
7000hex/7100hex |
µs |
< 1500 | |
7400hex/7500hex/7600hex/7700hex |
µs |
< 1300 |
1) | Analog single-ended inputs |
Analog input levels
Type |
R-IB IL AI 8/IS-PAC | |
Input resistance 1) |
Ω |
25 |
Cut-off frequency (–3 dB) of the input filter |
Hz |
3.5 |
Behavior upon sensor interruption |
Regulating toward 0 mA or 4 mA | |
Maximum permissible voltage between analog current inputs and analog reference potential or between two power inputs 2) |
V |
± 2.5 |
Maximum permissible current in each input 3) |
mA |
± 100 |
1) | Measuring resistance |
2) | Equal to 100 mA due to the measuring resistances |
3) | Destruction limit |
Electrical isolation/insulation of the voltage ranges
Type |
R-IB IL AI 8/IS-PAC | |
Common potentials |
||
24 V main voltage UM, 24 V segment voltage US and GND are on the same potential. FE represents a separate potential area. |
||
Separate potentials in the system of bus coupler/feed module and I/O module |
||
Test distance |
Test voltage | |
5 V supply incoming remote bus/7.5 V supply (bus logic) |
500 V AC, 50 Hz, 1 min. | |
5 V supply to further remote bus/7.5 V supply (bus logic) |
500 V AC, 50 Hz, 1 min. | |
7.5 V supply (bus logic), 24 V supply UANA/peripherals |
500 V AC, 50 Hz, 1 min. | |
7.5 V supply (bus logic), 24 V supply UANA/function earth |
500 V AC, 50 Hz, 1 min. | |
Peripherals/function earth |
500 V AC, 50 Hz, 1 min. |
Error messages to the higher-level control or computer system
Type |
R-IB IL AI 8/IS-PAC | |
Error message |
Upon failure of the voltage supply UANA: Peripheral error message Upon peripheral / user error: Error signal via input process data |
Approvals |
The current approvals can be found at www.boschrexroth.com. |
Dimensions
Type |
R-IB IL AI 8/IS-PAC | |
A |
mm |
48.8 |
B |
mm |
136.8 |
C |
mm |
72 |
Note on dimensions |
The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715). |